7.7.12 AIN2 Level 1
[ ]
Warning limit level for ANALOG INPUT 2
Step:
1
C
Range:
-100 - 10000
°C
Default:
80°C
7.7.13 AIN2 Level 2
[ ]
Shutdown limit level for ANALOG INPUT 2
Step:
1
C
Range:
-100 - 10000
°C
Default:
90°C
7.7.14 AIN2 Del
[s]
Delay for ANALOG INPUT 2 alarm.
Step:
1s
Range:
0 - 180s
Default:
5s
N
OTE
:
Analog input 2 is usually determined to Engine Temperature measurement and it is resistive type of
input with range 0-2500Ohm.
7.7.15 AIN3 Level 1
[ ]
Warning limit level for ANALOG INPUT 3
Step:
1 %
Range:
-100 - +10000%
Default:
20%
7.7.16 AIN3 Level 2
[ ]
Shutdown limit level for ANALOG INPUT 3
Step:
10%
Range:
-100 - +10000%
Default:
10%
7.7.17 AIN3 Del
[s]
Delay for ANALOG INPUT 3
Step:
1s
Range:
0 - 180s
Default:
10s