6.1.4 Shut down (Sd)
When the shutdown alarm comes up, ID-Lite opens all outputs e.g. FUEL SOLENOID, STARTER and
PRESTART to stop the engine immediately. Alarm outputs and common shutdown output are closed. Active or
not reset protection disables start.
Note:
Engine running only alarms are activated after
, after the engine RPM >
during the engine starting procedure.
Note:
If
is active engine does not react on shutdown protection only for Emergency
stop and Overspeed protection.
Sensor fail Fls is detected when measured value is 6 % out of range. Controller screen displays in this case
string #### instead measured value.
Note:
For list of possible shut-down alarms
see List of possible alarms on page 76
6.1.5 List of possible alarms
Events
specification
Protection
type
Information on binary
output available
198)
Description
Wrn Oil Press
WRN
YES
Oil pressure is smaller than Wrn Oil
press setpoint.
Sd Oil Press
SD
YES
Oil pressure is smaller than Sd Oil
press setpoint.
Sd NotOilPress
SD
YES
No information about the oil
pressure from the binary oil pressure
sensor.
Wrn Engine Temp
WRN
YES
Water temperature is greater than
Wrn Water temp setpoint.
Sd Engine Temp
SD
YES
Water temperature is greater than
Sd Water temp setpoint.
Wrn Fuel Level
WRN
YES
Fuel level is smaller than Wrn Fuel
Level setpoint.
Sd Fuel Level
SD
YES
Fuel level is smaller than Sd Fuel
Level setpoint.
Ubat
WRN
YES
Battery voltage is out of limits given
by Batt overvolt and Batt undervolt
setpoints.
Wrn AIN
WRN
YES
Warning alarm configurable on the
input of the controller.
Sd AIN
SD
YES
Shutdown alarm configurable on the
input of the controller.
Wrn AIO
WRN
YES
Warning alarm configurable on the
input of plug-in.
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...