InteliDrive DCU Industrial 3.4.0 Global Guide
171
Related FW
3.4.0
Related applications
AS, SS
Comm object
927
Description
If the input is activated, engine shutdown is immediately performed. However, the controller behavior is
slightly different compared to other shutdown alarms:
and
are deactivated as well.
This input cannot be overriden with the input Sd override.
Note:
Because of safety reasons it is recommended to configure this input as Normally closed and use a
NC switch.
IMPORTANT: This is a software function only. It can be extended by a "hard wired"
emergency stop function, which means disconnecting power supply from the controller
outputs.
EmergencyStop1
Related FW
3.4.0
Related applications
AS, SS
Comm object
928
Description
If the input is activated, engine shutdown is immediately performed. However, the controller behavior is
slightly different compared to other shutdown alarms:
and
are deactivated as well.
This input cannot be overriden with the input Sd override.
Note:
Because of safety reasons it is recommended to configure this input as Normally closed and use a
NC switch.
IMPORTANT: This is a software function only. It can be extended by a "hard wired"
emergency stop function, which means disconnecting power supply from the controller
outputs.
EmergencyStop2
Related FW
3.4.0
Related applications
AS, SS
Comm object
156
Description
External “edge sensitive” request for engine start. Binary input is active in all
AUX, EME, HRB
and
PRP
modes and inactive in LOC (Local) mode. There is only one start attempt, use
or
Blackout Start
(
AUX
,
EME
and
HRB
) binary input for repetitive starting procedure using
and
until the engine does not start. Unsuccessful
start is recorded to Alarm list and History. The second edge on Binary input
Remote Start
skips the Idle time
when engine is running in Idle state.
Binary input
Remote Start
signal is equivalent to ID-DCU Industrial front panel
Start
button.
Remote Start
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...