InteliDrive DCU Industrial 3.4.0 Global Guide
117
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
0 .. 600 [s]
Default value
2
Force value
Alternative config
Step
1
Comm object
8394
Related applications
AS, SS
Description
Time the binary output Prestart is active prior to engine start (Start request sending to ECU). Set to zero if
you want to start immediately after Start button is pressed (the Prestart output stays opened). RPM must be
zero during
Prestart time
otherwise the Starting procedure is not activated.
Prestart Time
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
1 .. 200 [s]
Default value
8
Force value
Alternative config
Step
1
Comm object
8234
Related applications
AS, SS
Description
Amount of time the controller will crank the engine in an attempt to start.
MaxCrank Time
Setpoint group
Engine params
Related FW
3.4.0
Range [units]
CMB, EME: 3 ..200 [s], AUX, PRP: 0 .. 200 [-]
Default value
8
Force value
Alternative config
Step
1
Comm object
8257
Related applications
AS, SS
Description
Pause between cranking attempts.
CrankFailPause
Содержание InteliDrive DCU Industrial
Страница 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Страница 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Страница 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Страница 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Страница 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...
Страница 281: ...InteliDrive DCU Industrial 3 4 0 Global Guide 281 6 back to Appendix 6 back to Table of contents...
Страница 294: ...InteliDrive DCU Industrial 3 4 0 Global Guide 294 Dimensions Note Unit is 35 mm DIN rail mounted Terminals...
Страница 306: ...InteliDrive DCU Industrial 3 4 0 Global Guide 306 Dimensions Note Unit is 35 mm DIN rail mounted...
Страница 314: ...InteliDrive DCU Industrial 3 4 0 Global Guide 314 Dimensions Unit is 35 mm DIN rail mounted Terminals...
Страница 350: ...InteliDrive DCU Industrial 3 4 0 Global Guide 350 6 back to Theory of binary inputs and outputs...