Engine Params
Prestart Time
[s]
Time of closing of the
Prestart
and/or
Pretransfer
output prior to the engine start.
Set to zero if you want to leave the output
Prestart/Pretransfer
open.
Step:
1 s
Range:
0
– 600 s
Cooling Time
[s]
Runtime of the unloaded gen-set to cool the engine before stop.
Step:
1 s
Range:
0
– 3600 s
Max Start Del
[s]
This timeout starts after closing binary output GEN START/STOP. When generator
does not reach
defined limits
Basic Settings:
Nominal Freq
) within
Max Start Del,
Trp Start Fail
alarm occurs and the
gen-set will shut down. See the table below for a description of the engine start evaluation.
If Max Start Del is longer than 600 s it means there is NO TIMEOUT.
Step:
1 s
Range:
0
– 600 s, 601 s = NO TIMEOUT