background image

 

InteliATS

NT

 PWR, SW version 2.5, ©ComAp 

– May 2015 

                                             58 

IA-NT- PWR-2.5-Reference Guide.pdf 

 

H

INT

This transition can perform fastest possible changeover if 

Transfer Del

 is set to zero value. 

Overall blackout time then equals to 20 ms + breaker reaction time. 
 

H

INT

:

 

Use longer delay time to avoid problems with motor starters. (Motor starts prefer to see break of a 
few seconds so they can initialize properly). 
 

H

INT

:

 

To avoid issues with contactor mechanical interlocks use delay 0.75s or longer (mech. interlock on 
contactors takes some time to clear). If you try to close one contactor before interlock has cleared 
it can jam and you end up without supply to load). 

2. Open In-phase Transition  

Open In-phase Transition represents special kind of Open Delayed Transition where delay during 
changeover is reduced to minimal possible value and transition initiates only when both power 
sources are in sync. 

Transfer Del

 setpoint value is ignored (equals to zero). See description of 

passive synchronization for more info. 

This kind of transition is suitable for such systems where fast changeover (very short blackout) is 
required, huge inductive load (e.g. large electric motor) is involved and it is not possible to use 
Closed Transition due to some reason. 

Two or three position ATS switch or two independent breakers/contactors can be used as 
switching element. Reaction time of whole switching mechanism (including control relays) affects 
overall changeover time and in-phase transfer accuracy. 

Содержание InteliATS PWR

Страница 1: ...avata Prague Czech Republic comAp a s Kundratka 2359 17 180 00 Praha 8 Czech Republic Tel 420 246 0124 111 Fax 420 266 316 647 E mail info comap cz www comap cz Reference guide InteliATSNT PWR SW vers...

Страница 2: ...InternetBridge NT 22 Programming of IA NT controller 23 User Interface 24 Terminals 25 IA NT PWR terminals and face 25 Installation 26 Mounting 26 Dimensions 27 Recommended Wiring 28 IA NT PWR Wiring...

Страница 3: ...connection 90 Internet connection 91 IB Lite 92 IL NT GPRS 93 AirGate 96 Locate 96 Modbus protocol 97 IL NT RD Remote display software 102 General description 102 Warning 102 IL NT RD Software install...

Страница 4: ...use a damage or unproper function of the equipment if not performed correctly and may not be clear at first sight WARNING This type of paragraph indicates things procedures adjustments etc which need...

Страница 5: ...tion is needed In this case the InteliATSNT SW must be combined purchased with the IL NT AMF 25 LT HW to obtain the low temperature ATS controller NOTE Because of large variety of InteliATSNT paramete...

Страница 6: ...ode or disconnect the Binary outputs Rem Start Stop and GCB Close Open to avoid unexpected automatic start of gen set and GCB closing WARNING Dangerous voltage In no case touch the terminals for volta...

Страница 7: ...ide synch check the controller has been enhanced by the feature called passive synchronization The passive sync sync check offers possibility to synchronize mains and gen set without the need to use s...

Страница 8: ...InteliATSNT PWR SW version 2 5 ComAp May 2015 8 IA NT PWR 2 5 Reference Guide pdf Example application...

Страница 9: ...ocumentation for details NOTE You need one of communication modules to connect the controller to a PC with LiteEdit There is a special easy removable service module for cases where there is no communi...

Страница 10: ...ts into expansion slot back on the controller To insert the module you must open the cover first use screwdriver to open and then insert the module into slot Once you have inserted it the module will...

Страница 11: ...PWR SW version 2 5 ComAp May 2015 11 IA NT PWR 2 5 Reference Guide pdf 3 Remove the small cover 4 Break apart the small cover into two pieces Do not throw away the smaller part 5 Take RS 232 communica...

Страница 12: ...n module into the slot of the controller 7 Put back the small cover NOTE When you insert RS 232 communication module the boot jumper is hidden For that reason we recommend to use RS 232 communication...

Страница 13: ...ommunication module IL NT RS232 485 is optional plug in card to enable InteliATSNT the RS232 and RS485 communication This is required for computer or Modbus connection Card inserts into expansion slot...

Страница 14: ...ess via menu Controller Programming and cloning Programming Select correct firmware and confirm dialog Than follow instructions in LiteEdit Or follow video guide Boot Jumper Programming at http www co...

Страница 15: ...ollers uses standard IA NT controller with IL NT Remote display software No further programming of the display is required unit is self configurable from the main controller It is connected with the c...

Страница 16: ...rectly to a PC using cross wired UTP cable 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 CROSS WIRED UTP 10 100Mbit CABLE RJ45 RJ45 Web server for IB Lite Is a new secured way of monitoring and controlling the gen...

Страница 17: ...InteliATSNT PWR SW version 2 5 ComAp May 2015 17 IA NT PWR 2 5 Reference Guide pdf Scada window Measurement window...

Страница 18: ...SW version 2 5 ComAp May 2015 18 IA NT PWR 2 5 Reference Guide pdf Setpoints window History window HINT This feature requires IB Lite optional plug in module and visible connection of controller to Et...

Страница 19: ...le works as a standard GSM modem enabling a CSD Circuit Switch Data connection to the controller with LiteEdit or InteliMonitor and sending SMS alarms The communication module IL NT GPRS works with We...

Страница 20: ...must open the cover first use screwdriver to open and then insert the module into slot Once you have insert it the module will snap under plastic teeth It is supposed to be installed permanently Shou...

Страница 21: ...d controller can accommodate up to 8 binary inputs or outputs In LiteEdit PC configuration tool version 4 4 and higher it is possible to easily choose if particular I O will be binary input or output...

Страница 22: ...The internet connection can be enabled via the built in cellular modem supporting 2G and 3G networks or via Ethernet cable For InteliATSNT the following functions are available Direct Ethernet connect...

Страница 23: ...uide pdf Programming of IA NT controller Programming is possible only in OFF mode when the engine is not running NOTE For more information on programming see LiteEdit Reference Guide CAUTION Check the...

Страница 24: ...values see alarms or change language settings Second mode is called ENGINEER and it is dedicated for advanced users who desire to change the settings of controller monitor all values and check the his...

Страница 25: ...InteliATSNT PWR SW version 2 5 ComAp May 2015 25 IA NT PWR 2 5 Reference Guide pdf Terminals IA NT PWR terminals and face...

Страница 26: ...2 5 Reference Guide pdf Installation Mounting The controller is to be mounted onto the switchboard door Requested cutout size is 175x115mm Use the screw holders delivered with the controller to fix t...

Страница 27: ...InteliATSNT PWR SW version 2 5 ComAp May 2015 27 IA NT PWR 2 5 Reference Guide pdf Dimensions 29 58 47 185 125 110 80 168 HINT Recommended mounting cutout size is 175 x 115 mm...

Страница 28: ...erator C Mains C B GEN READY TO LOAD MAINS FAIL BLOCK REMOTE AUT GCB FEEDBACK MCB FEEDBACK REMOTE TEST REMOTE TEST ONLD AL START FAIL GCB CLOSE OPEN GEN START STOP AL MAINS FAIL ALARM READY TO AMF MCB...

Страница 29: ...ween two power supply sources mains x generator AMF using two separate breakers with feedbacks MCB and GCB G IA NT GCB 3x LOAD 3xU M 3xU G 3xI G MCB 3x T 3x MCB MCB FEEDBACK K4 MCB GCB GCB FEEDBACK 3x...

Страница 30: ...mode GCB MCB full control with feedbacks Break transfer on mains failure Break return on mains return Load reclosing Test mode set running and waiting for mains failure On Load Test load transfer to...

Страница 31: ...MCB CLOSE OPEN GCB CLOSE OPEN BO BI K3 ATS on II position LOAD ATS 3x ATS I II Specification Automatic remote gen set start when the mains fails AUT mode Two position ATS control with feedback Break...

Страница 32: ...OPEN BO BI ATS on II position LOAD ATS 3x ATS I II 0 ATS on I position K4 K3 Specification Automatic remote gen set start when the mains fails AUT mode Three position ATS control with feedbacks pass t...

Страница 33: ...I II 0 Manual Load Transfer K3 K4 K5 NEUTRAL POS Specification Automatic remote gen set start when the mains fails AUT mode Three position ATS control without feedback pass through neutral position M...

Страница 34: ...etpoint GenStart Logic has to be set to CLOSE OFF Switching of the 24V AC DC power supply is blocked when GCB is closed so the power supply is not switched to Mains if voltage on the mains bus appears...

Страница 35: ...controller should be grounded properly in order to protect against lighting strikes The maximum allowable current through the controller s negative terminal is 4A this is dependent on binary output lo...

Страница 36: ...heating element is on below 5 C Current drain of heating element exhausts LBA capacitors very fast Power supply fusing A one amp fuse should be connected in line with the battery positive terminal to...

Страница 37: ...Settings Generator currents and power measurement is suppressed if current level is bellow 1 of CT range To ensure proper function Use cables of 2 5mm2 Use transformers to 5A Connect CT according to...

Страница 38: ...nection you have to set the setpoint CT location value to Load or Gen Set Voltage measurement and generator connection types There are 4 voltage measurement ConnectionTypes setpoint ConnectionType 3Ph...

Страница 39: ...phase delta measurement 3PD 3 Phase 3 Wires DELTA Connection HI LEG wild leg red leg DELTA Connection NOTE Only L1 L2 and L3 wires should be connected In case of HI LEG DELTA connection the N neutral...

Страница 40: ...ComAp May 2015 40 IA NT PWR 2 5 Reference Guide pdf 3 ConnectionType Split Phase Single phase measurement 1PH Split Phase DOUBLE DELTA Connection ZIG ZAG DOG LEG Connection 4 ConnectionType Mono Phas...

Страница 41: ...nce Guide pdf Mono Phase MONOPHASE Connection NOTE Switchboard lighting strike protection according standard regulation is expected for all 4 connection types Binary inputs 4k7 To the microprocessor N...

Страница 42: ...room picture 1 interconnect A and B shielding connect to PE on controller side B For longer distances connection between rooms within one building picture 2 interconnect A B COM shielding connect to...

Страница 43: ...ts within one room H A L B COM 120 H A L B COM 120 Picture 2 longer distances connection between rooms within one building Picture 3 surge hazard connection out of building in case of storm etc H A L...

Страница 44: ...by LiteEdit software There is fix 1 sec delay when any binary input is configured as protection Not Used Binary input has no function Use this configuration when Binary input is not connected Alarm I...

Страница 45: ...generator without waiting for the AMF Settings EmergStart Del has elapsed In the case the transfer not succeeded the system will stay in neutral position The MainsFailBlock input performs its work nor...

Страница 46: ...EST mode When input is closed the controller automatically transfers load from the mains to the gen set Setpoint AMF Settings ReturnFromTEST must be set to MANUAL Load is automatically transferred bac...

Страница 47: ...hanged Total Stop If the input is opened Trip is immediately activated Stop signal for gen set is sent and the GCB and MCB are opened MCB Disable The input is used disable issuing the MCB closing comm...

Страница 48: ...equested and opens after the AMF Settings Prestart Time has elapsed Afterwards the GenStart Stop output is activated as a start signal for the remote gen set Pretransfer Is activated during the Presta...

Страница 49: ...e length is double of MCB Delay timer Fault Reset The output is a copy of Fault Reset button on controller and binary input FaultResButton Gen Healthy The output is a copy of generator status LED on I...

Страница 50: ...n Freq Output closes if the generator over under frequency alarm activates The output opens if alarm is not active and FAULT RESET is pressed AL Gen Freq Output closes if the generator over frequency...

Страница 51: ...ails The output opens if alarm is not active and FAULT RESET is pressed Note See setpoint Max Start Del for more information AL Overcurrent Output closes if the generator IDMT over current or current...

Страница 52: ...witches the ATS three way switch to the position II Neutral Pos output switches the ATS three way switch to the position 0 middle The resulting behavior of the ATS output differs depending on the prio...

Страница 53: ...he system is running in short time parallel with mains closed transition and the time of the parallel run is longer than 300ms It is a kind of protection against long time parallel run with mains when...

Страница 54: ...n and means maximal continuous generator current See Gener Protect Amps IDMT Del Short Crct Trip setpoints Nominal Current can be different from generator rated current value Step 1 A Range 1 10000 A...

Страница 55: ...0 1 500 0 V V Vm PT Ratio 1 Mains potential transformers ratio Step 0 1 V V Range 0 1 500 0 V V NomVolts Ph N V Nominal generator voltage phase to neutral Step 1 V Range 80 20000 V NOTE Phase sequence...

Страница 56: ...r measurement are connected to controller values are just shown on measuring screen More info can be found in chapter Source evaluation or in description of binary input MainsReadyToLoad NOTE When bin...

Страница 57: ...ide Open In phase Transition and Closed Transition short time parallel Controller provides below described types of changeover between Mains and Gen set power sources depending on following setpoint v...

Страница 58: ...supply to load 2 Open In phase Transition Open In phase Transition represents special kind of Open Delayed Transition where delay during changeover is reduced to minimal possible value and transition...

Страница 59: ...s during changeover however mechanical interlock can still be useful Two or three position ATS switches ensure this by its nature HINT It is necessary to use fast breakers with known closing opening t...

Страница 60: ...akers contactors are required as switching elements Reaction time of whole switching mechanism including control relays affects overall changeover time It is required to use as fast switches as possib...

Страница 61: ...ue of breaker switching time MUST contain all the parts of breaker delay i e breaker switching time plus switching time of relay used for breaker control The more exact value is given the more exact i...

Страница 62: ...been assigned by the DHCP server A gateway is a device which connects the respective segment with the other segments and or Internet IBLite DHCP ENABLED DISABLED The setpoint is used to select the me...

Страница 63: ...to enter the user name for the SMTP server SMTP User Pass Use this setpoint to enter the password for the SMTP server SMTP Server IP This setpoint is used for entering the domain name e g smtp yourpro...

Страница 64: ...d or Pretransfer output prior to the engine start Set to zero if you want to leave the output Prestart Pretransfer open Step 1 s Range 0 600 s Cooling Time s Runtime of the unloaded gen set to cool th...

Страница 65: ...state means GenReadyToLoad signal is deactivated or generator voltages disappeared If the engine is still running after the stop time expires the Wrn Stop Fail alarm is announced Stop Fail starts coun...

Страница 66: ...IA NT PWR 2 5 Reference Guide pdf PowerSwitch ON kW Threshold level for switching the binary output Power Switch on Step 1 Range 0 32000 kW PowerSwitchOFF kW Threshold level for switching the binary...

Страница 67: ...ort Crct Trp Trip occurs when generator current reaches Short Crct Trp limit Step 1 of Nominal current Range 100 500 Short Crct Del s Delay for generator shortcurrent alarm Step 0 01 s Range 0 00 10 0...

Страница 68: ...1 200 of Nominal current Amps Unbal Del s Delay for generator current unbalance Step 0 1 s Range 0 0 600 0 s Gen V Trp Threshold for generator overvoltage All three phases are checked Maximum out of...

Страница 69: ...l s Delay for generator under frequency and over frequency alarm Step 0 1 s Range 0 0 600 0 s Programmable delay on alarms Possibility to set programmable delay on alarms configured for binary input 6...

Страница 70: ...he controller closes GCB Close Open output straight away 100 ms after the MCB feedback input deactivates If some delay between MCB feedback deactivation and closing of GCB Close Open output is require...

Страница 71: ...100 Mains V Mains V Del s Delay for mains under voltage and overvoltage Step 0 1 s Range 0 600 0 s Mains V Unbal Threshold for mains voltage unbalance Step 1 of Nominal voltage Range 1 150 Mains VUnb...

Страница 72: ...he gen set remains running loaded 4 To stop the gen set select AUTO Mode 5 In AUT Mode a After the MainsReturnDel InteliATSNT opens the GCB b After the Transfer Del delay InteliATSNT closes the MCB c...

Страница 73: ...MCB close open this timer starts After the timer elapses the state of BI MCB feedback is evaluated If the setting of the MCB feedback del setpoint is longer than 60 0 s it means there is NO TIMEOUT S...

Страница 74: ...ng in AUT mode No Func There is no any other function but binary output Timer1 2 activation TEST When this option is chosen then the Timer output is also internally connected to the Remote TEST binary...

Страница 75: ...tect which communication terminal is connected to the network and send the email SMS via the active one InternetBridge NT is preferred terminal if more possibilities are detected NOTE An internet modu...

Страница 76: ...he telephone number and active SMS is sent NOTE For GSM numbers use either national format i e like number you will dial if you want to make a local call or full international format with character fo...

Страница 77: ...ctivity Setpoint ActivityAtOff DISABLED The controller opens all binary outputs and Fault reset is active all the time Output controlling MCB remains unchanged Standard activity Setpoint ActivityAtOff...

Страница 78: ...active Controller waits for gen set parameters are OK means GenReadyToLoad signal is activated or generator voltages are in allowed limits and then GCB is reclosed For ensuring GCB Open Close output...

Страница 79: ...ller is put to TEST mode and will remain running unloaded If a mains failure occurs the gen set will take the load The load can be transferred to the gen set also manually If the MCB button is pressed...

Страница 80: ...red mains electrical limits voltage frequency are still in limits the controller switches MCB ON again EmergStart Del Mains fail MCB opened Mains V Del or Mains Freq Del or Mains VUnb Del genset start...

Страница 81: ...nput for mains State of source can be evaluated in these ways Binary input only Measured values only Binary input and measured values Binary input only In this case the binary input GenReadyToLoad or...

Страница 82: ...nteliATSNT opens outputs GCB CLOSE OPEN GENSTART STOP and PRESTART to stop the engine immediately Alarm outputs and common shutdown output are closed Active or not reset protection disables start Poss...

Страница 83: ...PWR 2 5 Reference Guide pdf AMF time chart genset OK AMF time chart genset not started properly NOTE For more details please see the AMF Settings Min Stab Time Max Start Del setpoint description AMF S...

Страница 84: ...t time delays for CB fail detection see following diagrams When is BO GCB close open MCB Close Open in steady state and GCB feedback MCB feedback is changed the GCB fail is detected immediately no del...

Страница 85: ...ery is flat Trp BatteryFlat TRP YES If the controller switches off during starting sequence due to bad battery condition it doesn t try to start again and activates this protection Trp Start Fail TRP...

Страница 86: ...eout when the system waits for both sources to get synchronized is exceeeded Warningis activated and either changeover is interrupted or continues as open delayed transition Wrn Shunt Trip WRN YES GCB...

Страница 87: ...ge L3 Ig1 Generator current L1 Ig2 Generator current L2 Ig3 Generator current L3 Vm1 Mains voltage L1 Vm2 Mains voltage L2 Vm3 Mains voltage L3 Mfrq Mains frequency UBat Battery voltage BIN Binary inp...

Страница 88: ...this screen is possible to switch between languages configured in controller User Interface screen InteliATSNT controller enables to choose the user interface as customer prefers There are two choices...

Страница 89: ...t located on the rear side of the controller Find more information about installation of the modules in a separate chapter A RS232 USB or RS485 interface can be used for direct cable connection to a P...

Страница 90: ...y 240 20V is ground free GND terminal is not connected 5 GND 2 RxD 3 TxD PC 5 GND 2 RxD 3 TxD RS232 RS232 230 VAC 0 VDC CONTROLLER Battery Required the same voltage potential between GND s RS 232 Mode...

Страница 91: ...track M1306B Fastrack M1206B is not recommended Falcom A2D Modem setup procedure Analog modems obviously do not require any setup The only case in which setup could be necessary is if the modem has be...

Страница 92: ...use any web browser for basic monitoring and adjustment of the controller Direct your web browser to the IP address of the module e g http 192 168 1 254 and then enter the access code IB Lite HINT Se...

Страница 93: ...for proper IP settings 8 Consult your e mail provider for proper e mail settings Note that also most public SMTP servers require authentication and e mails must be sent from an existing address 9 If y...

Страница 94: ...gs as every setpoint group are accessible by PAGE button from any measurement screen on controller Setpoints can be set on controller s front panel keyboard or by LiteEdit 4 5 and higher 6 Switch off...

Страница 95: ...We will create free account for you Details at http www comap cz products detail WebSupervisor Communication is now ready for use HINT To reduce the data traffic over GPRS network you can set in setp...

Страница 96: ...essful registration to CDMA network 23 Controller couldn t detect IL NT GPRS module communication speed 255 Only running communication is needed to indicate AirGate Diag Diagnostic Code for AirGate co...

Страница 97: ...y in the controller memory and identified by the unique 16 bit communication object number The register according to Modbus communication protocol represents a two byte data and in communication funct...

Страница 98: ...o 9836 0 01 60 Unsigned 16 Basic Settings MCB Delay 0 05 s No 9056 0 01 60 Unsigned 16 Comms Settings ControllerAddr 1 Yes 24537 1 32 Unsigned 8 Comms Settings COM1 Mode DIRECT Yes 24522 String list C...

Страница 99: ...Unsigned 16 AMF Settings MCB Close Del 1 s No 8389 0 60 Unsigned 16 AMF Settings Mains V 110 No 8305 60 150 Unsigned 16 AMF Settings Mains V 60 No 8307 50 110 Unsigned 16 AMF Settings Mains V Del 2 s...

Страница 100: ...ad Load kVA L3 51 kVA 8532 Integer 16 Load Load PF 1 8204 Integer 8 Load Load Char R 8395 Char Load Load PF L1 1 8533 Integer 8 Load Load Char L1 R 8626 Char Load Load PF L2 1 8534 Integer 8 Load Load...

Страница 101: ...IA Info Timer Text Basic Settings 8954 Unsigned 16 IA Info Timer Value 0 s 8955 Unsigned 16 IA Info FW Version 24 8393 Unsigned 8 IA Info Application 19 8480 Unsigned 8 IA Info FW Branch 10 8707 Unsi...

Страница 102: ...highly recommended to use the same type and model of controller for master and remote display Only in such case is assured the proper function of all buttons LED diodes and display Another combinatio...

Страница 103: ...e master controller from one remote display at the time Connection process Remote display after power on automatically starts to search for any master controller connected It starts to search on COM1...

Страница 104: ...485 IA NT IL NT ID Lite Remote Display Master controller RS 232 COM1 OR IA NT IL NT ID Lite IL NT RS232 485 IL NT RS232 485 IA NT IL NT ID Lite Remote Display Master controller RS 485 COM2 OR IA NT IL...

Страница 105: ...s and view history records All IL NT RD screens Init Measure Setpoints and History display the same data like in the master controller Master device is always able to work without connected Remote dis...

Страница 106: ...After the next power switch on with flat battery already controller Stays in the INIT state not possible to run genset All History records disappear except of System log SetpointCS err record Time and...

Страница 107: ...Guide pdf 5 Put the rear cover back Use slight pressure to lock the snaps into the housing Pay attention that the cover is in correct position and not upside down 6 Plug the modules back into the slo...

Страница 108: ...V Battery voltage measurement tolerance 2 at 24V NOTE For the supply voltage less than 7V the backlight of the display is switched off Short term voltage drops e g during the engine cranking do not af...

Страница 109: ...voltage Uimp 4 kV Binary inputs and outputs Binary inputs Not electrically separated Number of inputs 7 Input resistance 4 2 k Input range 0 36 VDC Switching voltage level for close contact indicatio...

Страница 110: ...Speed Up to 57 6 kBd DIRECT 38 4kBd Analog modem 9 6 kBd digital modem 57 6 kBd MODBUS Use only shielded A B USB cables up to 5m length Recommend USB cable USB LINK CABLE 1 8M ComAp A B USB cable IB...

Страница 111: ...binary inputs or outputs Binary inputs Number of inputs 8 Input resistance 4 7 k Input range 0 36 VDC Voltage level for close contact indication Logical 1 0 8 VDC Voltage level for open contact indica...

Отзывы: