InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
228
13.1.5.5
Value: Reserve Stp
Group
Pwr management
Units
kX
Related FW
3.0
Description
Actual
absolute reserve
- when the reserve is higher than this value the last
started gen-set (the gen-set with the highest priority) is stopped. This value
contains the following:
#LoadResStop
plus
Nominal power
of the genset
which is first to stop. #LoadResStop is used from the currently selected
reserve set
.
13.1.5.6
Value: ActRes rel
Group
Power management
Units
%
Related FW
3.0
Description
Actual
relative reserve
. This value is active only when BTB is closed.
13.1.5.7
Value: ResStart rel
Group
Power management
Units
%
Related FW
3.0
Description
If the actual relative reserve is lower than this value the next gen-set which is
about to be started in
power managament
is started. This value is the exact
copy of setpoint
#%LdResStrt X
.
13.1.5.8
Value: ResStp rel
Group
Power management
Units
%
Relate
d FW
3.0
Descri
ption
Actual
relative reserve
- when the relative reserve is higher than this value the last started
gen-set (the gen-set with the highest priority) is stopped. This value contains the following:
Содержание IM-NT
Страница 86: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 86 APPENDIX...
Страница 326: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 326 17 User Notes...
Страница 327: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 327...
Страница 328: ...InteliMains NT SW version 3 0 InteliMains NT BTB 3 0 Reference Guide pdf ComAp June 2013 328...