036-21326-001-C-0202
Unitary Products Group
7
TABLE 1: UNIT APPLICATION DATA
Application Limitations
Minimum
Maximum
Voltage Variation (208/230-3-60) - Volts
187
253
Voltage Variation (460-3-60) - Volts
414
506
Ambient Air on Outdoor Coil (Cooling Cycle) - °F
45
115
Ambient Air on Indoor Coil (Cooling Cycle) - °F
68
86
TABLE 2: ARI RATINGS - COOLING AND SOUND
Model
Cooling Capacity
1
Cond. Unit
Sound
2
Rated Airflow
Rated ESP
Outdoor
Unit
Indoor Unit
MBH
EER
IPLV
dB
CFM
IWG
HL180
LL180
180
9.7
10.4
89.0
6000
0.35
HL240
LL240
240
9.7
10.4
90.0
8000
0.40
1. Ratings are in accordance with ARI standard 340/360.
2. Ratings are in accordance with ARI standard 370.
TABLE 3: ELECTRICAL DATA COMPRESSORS
Model
Number
Compressors
Power
Supply
System 1
System 2
RLA
LRA
RLA
LRA
HL180
208/230-3-60
25.6
190.0
25.6
190.0
HL180
460-3-60
12.8
95.0
12.8
95.0
HL240
208/230-3-60
42.0
239.0
42.0
239.0
HL240
460-3-60
19.2
125.0
19.2
125.0
TABLE 4: ELECTRICAL DATA FAN MOTORS
Model
Number
Condenser Fans
Power
Supply
Qty.
FLA
ea.
HL180
208/230-3-60
2
3.7
HL180
460-3-60
2
1.85
HL240
208/230-3-60
2
5.8
HL240
460-3-60
2
2.9
TABLE 5: ELECTRICAL DATA, OUTDOOR MCA & MAX. FUSE SIZE
Model
Number
Power
Supply
Min. Circuit
Ampacity
Max.
Fuse
Size
1
HL180
208/230-3-60
65.1
90
HL180
460-3-60
32.5
45
HL240
208/230-3-60
106.1
125
HL240
460-3-60
49.0
60
1. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Содержание HL180