Coleman FC9T-UP Скачать руководство пользователя страница 5

246739-CTG-C-0407

Unitary Products Group

5

FILTER PERFORMANCE

The airflow capacity data published in the “Blower Perfor-
mance” table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the “Filter
Performance” table shown below.

NOTE: 

The filter pressure drop values in the “Filter Perfor-

mance” table shown below are typical values for the type of 
filter listed and should only be used as a guideline. Actual 
pressure drop ratings for each filter type vary between filter 
manufacturer.

NOTES: 

1. Air velocity through throwaway type filters may not exceed 300 
feet per minute. All velocities over this require the use of high 
velocity filters.
2. Air flows above 1800 CFM require either return from two sides or 
one side plus bottom.

RECOMMENDED FILTER SIZES

Input/Output

BTU/H

CFM

Cabinet 

Size

Side Return 

Filter in.

Bottom Return 

Filter in.

40/38

1200

A

16 x 25

14 x 25

60/56

1200

B

16 x 25

16 x 25

80/75

1200

B

16 x 25

16 x 25

80/75

1600

C

16 x 25

20 x 25

100/93

1600

C

16 x 25

20 x 25

100/93

2000

C

16 x 25

20 x 25

120/112

2000

D

(2) 16 x 25

22 x 25

FILTER PERFORMANCE - PRESSURE DROP INCHES W.C. AND (KPA)

Airflow Range

Minimum 

Opening Size

Filter Type

Disposable

Washable Fiber

Pleated

CFM

 in

2

   

In W.C.

In W.C.

In W.C.

0 - 750

230

0.01

0.01

0.15

751 - 1000

330

0.05

0.05

0.20

1001 - 1250

330

0.10

0.10

0.20

1251 - 1500

330

0.10

0.10

0.25

1501 - 1750

380

0.15

0.14

0.30

1751 - 2000

380

0.19

0.18

0.30

2001 & Above

463

0.19

0.18

0.30

UNIT CLEARANCES TO COMBUSTIBLES

Application

Top

Front

Rear

Left Side

Right Side

Flue

Floor/ 

Bottom

Closet 

Alcove

Attic

In.

In.

In.

In.

In.

In.

Upflow

1

3

0

0

0

0

Combustible

Yes

Yes

Содержание FC9T-UP

Страница 1: ...operation includes Two stage gas valve Two stage inducer operation Provides increased comfort level very quiet unit opera tion Adjustable delay timer allows two stage operation with single stage therm...

Страница 2: ...P IMAGE SUPPLY END 1 1 2 GAS PIPE ENTRY 7 8 JUNCTION BOX HOLE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O A 40 FRONT CABINET AND DUCT DIMENSIONS Models Nominal CFM Cabinet Size Cabinet Dimension A...

Страница 3: ...MANCE DATA Models Input High Low Output High Low Nominal Airflow Cabinet Width Total Unit AFUE Air Temp Rise MBH MBH CFM In Amps F FC9T040A12UP11 40 26 38 24 1200 14 1 2 9 94 0 35 65 FC9T060B12UP11 60...

Страница 4: ...d High 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 Med Low 1230 1275 1285 1300 1310 1300 1280 1245 1190 1070 Low 930 945 965 975 975 975 975 950 910 850 FC9T100C20UP11 High 2300 2210 2120 2020 1...

Страница 5: ...of high velocity filters 2 Air flows above 1800 CFM require either return from two sides or one side plus bottom RECOMMENDED FILTER SIZES Input Output BTU H CFM Cabinet Size Side Return Filter in Bot...

Страница 6: ...nction Light E W1 First Stage Heat G Fan G Fan Connection of the C Termainal 24 Volt Common is optional when used with batteries Thermostat Installer Setup Number 1 System Type must be set to 6 2 Heat...

Страница 7: ...SG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor W2 Second Stage Auxiliary Heat W2 Second Stage Auxiliary Heat AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Hea...

Страница 8: ...w reduction value to airflow 0 50 to obtain actual airflow 0 58 ESP 2288 88 2197 ACCESSORIES CONCENTRIC VENT TERMINATION 1CT0302 2 1CT0303 3 For use through rooftop sidewall Allows combustion air to e...