background image

259720-CTG-B-0108

Unitary Products Group

3

* ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.

NOTES: 

1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.
5. Air flows above 1800 CFM require either return from two sides or one side plus bottom.

ELECTRICAL AND PERFORMANCE DATA

Models

Input 

Max/Min

Output 

Max/Min

Blower 

Size

Blower

Max. 

Over-current 

Protect

Air Temp. Rise

Maximum Input

Air Temp. Rise

Minimum Input

MBH

MBH

In.

HP

Amps

°F

°F

FC9M060B12UP11

60/21

57/20

11 x 8

1/2

7.7

20

40 - 70

20 - 50

FC9M080B12UP11

80/28

76/26

11 x 8

1/2

7.7

20

40 - 70

20 - 50

FC9M080C16UP11

80/28

76/26

11 x 10

3/4

10.2

20

40 - 70

20 - 50

FC9M100C16UP11

100/35

95/33

11 x 10

3/4

10.2

20

40 - 70

20 - 50

FC9M100C20UP11

100/35

95/33

11 x 11

1

12.8

20

40 - 70

20 - 50

FC9M120D20UP11

120/42

115/39

11 x 11

1

12.8

20

40 - 70

20 - 50

Models

Max. Outlet 

Air Temp.

Nominal 

Airflow

Cabinet 

Width

Total 

Unit 

AFUE

Min. Wire Size

(awg) @ 75 ft. 

One Way

Approximate

Operating Weight

Power Supply

(Voltage-PH-Hz)

°F

CFM

In.

Amps

%

FC9M060B12UP11

170

1200

17-1/2

9

95.0

14

135

115-1-60

FC9M080B12UP11

170

1200

17-1/2

9

95.0

14

142

115-1-60

FC9M080C16UP11

170

1600

21

12

95.0

14

157

115-1-60

FC9M100C16UP11

170

1600

21

12

95.0

14

162

115-1-60

FC9M100C20UP11

170

2000

21

14

95.0

12

164

115-1-60

FC9M120D20UP11

170

2000

24-1/2

14

95.0

12

180

115-1-60

Содержание FC9M060B12UP11

Страница 1: ...li cations 5 year limited parts warranty FEATURES Modulating heating operation includes Modulating gas valve Modulating inducer operation Provides increased comfort level very quiet unit opera tion Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code display Low unit a...

Страница 2: ...WITH EXTERNAL FILTER FRAME LEFT SIDE FRONT RIGHT SIDE BOTTOM IMAGE RETURN END TOP IMAGE SUPPLY END 1 1 2 GAS PIPE ENTRY 7 8 JUNCTION BOX HOLE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O DIMENSIONS Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in FC9M060B12UP11 1200 B 17 1 2 16 1 4 14 1 2 8 1 2 FC9M080B12UP11 1200 B 17 1 2 16 1 4 11 8 1 2 FC9M080C16UP11 1600 C 21 19 3 4 18 8...

Страница 3: ...NCE DATA Models Input Max Min Output Max Min Blower Size Blower Max Over current Protect Air Temp Rise Maximum Input Air Temp Rise Minimum Input MBH MBH In HP Amps F F FC9M060B12UP11 60 21 57 20 11 x 8 1 2 7 7 20 40 70 20 50 FC9M080B12UP11 80 28 76 26 11 x 8 1 2 7 7 20 40 70 20 50 FC9M080C16UP11 80 28 76 26 11 x 10 3 4 10 2 20 40 70 20 50 FC9M100C16UP11 100 35 95 33 11 x 10 3 4 10 2 20 40 70 20 50...

Страница 4: ...y 155941 031 09140 1 C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor PSC MODULATING FURNACE G Fan PSC MODULATING FURNACE Y Y2 Second or Full Stage Compressor 1 W Modulating Heat HM1 Humidistat Y Full Stage Compressor G Fan PP11C70224 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary 24VAC H...

Страница 5: ... STAGE AIR CONDITIONER SINGLE STAGE AIR CONDITIONER Y Full Stage Compressor G Fan BP11C50124 BN11C01124 DP11C40124 DN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Selection of GAS ELEC switch on thermostat is not necessary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Hea...

Страница 6: ...stem Type must be set to 9 2 Heat 1 Cool Multistage Conventional Connection of the C terminal 24 volt common is optional when used with batteries Thermostat Installer Setup 1 System Type must be set to 7 2 Heat 1 Cool Multistage Conventional Thermostat Installer Setup 15 Compressor Protection must be set to 5 C 24 Volt Common R 24 Volt Hot Y First Stage Compressor Y2 Second Stage Compressor G Fan ...

Страница 7: ...on Y Compressor SINGLE STAGE AIR CONDITIONER SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE STAGE AIR CONDITIONER SINGLE STAGE AIR CONDITIONER C 24 Volt Common Y1 First Stage Compressor L Malfunction Light Y2 Second Stage Compressor G Fan PP32U71124 PP32U72124 THERMOSTAT R 24 Volt Hot W2 Second Stage Heat DHM Dehumidistat HM Humidistat O Reversing Valve Energized in Cool 24VAC Humidifi...

Страница 8: ...on C 24 Volt Common Y1 First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan DN22U00124 THERMOSTAT E Emergency Heat AUX Auxiliary Heat R 24 Volt Hot Heat XFMR R 24 Volt Hot Cool XFMR 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise 3 Part Number S1 2HU16700124 3 O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot ...

Страница 9: ... 1490 1440 1390 1315 1230 1155 1050 920 D 1325 1270 1225 1175 1105 1045 990 905 890 790 FC9M080C16UP11 FC9M100C16UP11 A 1960 1955 1925 1890 1830 1765 1695 1615 1600 1485 B 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 C 1230 1275 1285 1300 1310 1300 1280 1245 1190 1070 D 930 945 965 975 975 975 975 950 910 850 FC9M120D20UP11 A 2560 2485 2410 2320 2220 2135 2035 1920 1785 1650 B 2090 2050 1990 ...

Страница 10: ...e 0 58 0 50 0 60 0 50 0 8 4 Multiply percentage by airflow difference to obtain airflow reduction 0 8 x 110 88 5 Subract airflow reduction value to airflow 0 50 to obtain actual airflow 0 58 ESP 2288 88 2197 ACCESSORIES PROPANE LP CONVERSION KIT 1NP0680 All units This accessory conversion kit must be used to convert natu ral gas N units for propane LP operation Conversions must be made by qualifie...

Страница 11: ...259720 CTG B 0108 Unitary Products Group 11 NOTES ...

Страница 12: ...to change without notice Printed in U S A 259720 CTG B 0108 Copyright by Unitary Products Group 2008 All rights reserved Supersedes 259720 CTG A 0606 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Отзывы: