Unitary Products Group

APPLYING FILTER PRESSURE DROP TO 
DETERMINE SYSTEM AIRFLOW

To determine the approximate airflow of the unit with a filter in
place, follow the steps below:

1.

Select the filter type.

2.

Select the number of return air openings or calculate the 
return opening size in square inches to determine the 
proper filter pressure drop.

3.

Determine the External System Static Pressure (ESP) 
without the filter.

4.

Select a filter pressure drop from the table based upon 
the number of return air openings or return air opening 
size and add to the ESP from Step 3 to determine the 
total system static.

5.

If total system static matches a ESP value in the airflow 
table (i.e. 0.20, 0.60, etc,) the system airflow corre-
sponds to the intersection of the ESP column and Model/
Blower Speed row.

6.

If the total system static falls between ESP values in the 
table (i.e. 0.58, 0.75, etc.), the static pressure may be 
rounded to the nearest value in the table determining the 
airflow using Step 5 or calculate the airflow by using the 
following example.

Example:

  For a 120,000 Btuh furnace with 2 return openings

and operating on high speed blower, it is found that total sys-
tem static is 0.58" w.c.  To determine the system airflow, com-
plete the following steps:

1.

Obtain the airflow values at 0.50" & 0.60" ESP.

Airflow @ 0.50":  2285 CFM

Airflow @ 0.60":  2175 CFM

2.

Subtract the airflow @ 0.50" from the airflow @ 0.60" to 
obtain airflow difference.

2175 - 2285 = -110 CFM

3.

Subtract the total system static from 0.50" and divide this 
difference by the difference in ESP values in the table, 
0.60" - 0.50", to obtain a percentage.

(0.58 - 0.50) / (0.60 - 0.50) = 0.8

4.

Multiply percentage by airflow difference to obtain airflow 
reduction.

(0.8) x (-110) = -88

5.

Subract airflow reduction value to airflow @ 0.50" to 
obtain actual airflow @ 0.58" ESP.

2288 - 88 = 2197

ACCESSORIES

PROPANE (LP) CONVERSION KIT - 

1NP0680 - All units

This accessory conversion kit must be used to convert natu-
ral gas (N) units for propane (LP) operation. Conversions
must be made by qualified distributor or dealer personnel.

CONCENTRIC VENT TERMINATION -

 

1CT0302 (2")

1CT0303 (3")

For use through rooftop, sidewall. Allows combustion air to
enter and exhaust to exit through single common hole.

CONDENSATE NEUTRALIZER KIT - 1NK0301

Neutralizer cartidge has a 1/2" plastic tube fittings for installa-
tion in the drain line. Calcium carbonate refill media is also
avaiable from the Source 1 Parts (p/n 026-30228-000).

SIDEWALL VENT TERMINATION -

 

1HT0901 (3")
1HT0902 (2")

For use on sidewall, two-pipe installations only. Provide a
more attractive termination for locations where the terminal is
visable on the side of the home.

SIDE RETURN FILTER - 

1SR0402 - All Models

1SR0200 - All Models

BOTTOM RETURN FILTER - 

1BR0117 or 1BR0217 - For 17-1/2” cabinets

1BR0121 or 1BR0221 - For 21” cabinets

1BR0124 or 1BR0224 - For 24-1/2” cabinets

ROOM THERMOSTATS 

- A wide selection of compatible

thermosets are available to provide optimum performance
and features for any installation.

1H/1C, manual change-over electronic non-programmable 
thermostat.

1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.

1H/1C, auto/manual changeover, electronic programmable.

* For the most current accessory information, refer to the
price book or consult factory.

UNIT CLEARANCES TO COMBUSTIBLES

APPLICATION

TOP

FRONT

REAR

LEFT SIDE

RIGHT SIDE

FLUE

FLOOR/ 

BOTTOM

CLOSET 

ALCOVE

ATTIC

In.

In.

In.

In.

In.

In.

UPFLOW

1

3

0

0

0

0

COMBUSTIBLE

YES

YES

Содержание FC9M060B12UP11

Страница 1: ...li cations 5 year limited parts warranty FEATURES Modulating heating operation includes Modulating gas valve Modulating inducer operation Provides increased comfort level very quiet unit opera tion Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code display Low unit a...

Страница 2: ...WITH EXTERNAL FILTER FRAME LEFT SIDE FRONT RIGHT SIDE BOTTOM IMAGE RETURN END TOP IMAGE SUPPLY END 1 1 2 GAS PIPE ENTRY 7 8 JUNCTION BOX HOLE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O DIMENSIONS Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in FC9M060B12UP11 1200 B 17 1 2 16 1 4 14 1 2 8 1 2 FC9M080B12UP11 1200 B 17 1 2 16 1 4 11 8 1 2 FC9M080C16UP11 1600 C 21 19 3 4 18 8...

Страница 3: ...NCE DATA Models Input Max Min Output Max Min Blower Size Blower Max Over current Protect Air Temp Rise Maximum Input Air Temp Rise Minimum Input MBH MBH In HP Amps F F FC9M060B12UP11 60 21 57 20 11 x 8 1 2 7 7 20 40 70 20 50 FC9M080B12UP11 80 28 76 26 11 x 8 1 2 7 7 20 40 70 20 50 FC9M080C16UP11 80 28 76 26 11 x 10 3 4 10 2 20 40 70 20 50 FC9M100C16UP11 100 35 95 33 11 x 10 3 4 10 2 20 40 70 20 50...

Страница 4: ...y 155941 031 09140 1 C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor PSC MODULATING FURNACE G Fan PSC MODULATING FURNACE Y Y2 Second or Full Stage Compressor 1 W Modulating Heat HM1 Humidistat Y Full Stage Compressor G Fan PP11C70224 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Clipping Jumper W914 for electric heat on thermostat is not necessary 24VAC H...

Страница 5: ... STAGE AIR CONDITIONER SINGLE STAGE AIR CONDITIONER Y Full Stage Compressor G Fan BP11C50124 BN11C01124 DP11C40124 DN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Heat Selection of GAS ELEC switch on thermostat is not necessary C 24 Volt Common Y Full Stage Compressor G Fan BN11C00124 THERMOSTAT RH 24 Volt Hot Heat XFMR RC 24 Volt Hot Cool XFMR W Full Stage Hea...

Страница 6: ...stem Type must be set to 9 2 Heat 1 Cool Multistage Conventional Connection of the C terminal 24 volt common is optional when used with batteries Thermostat Installer Setup 1 System Type must be set to 7 2 Heat 1 Cool Multistage Conventional Thermostat Installer Setup 15 Compressor Protection must be set to 5 C 24 Volt Common R 24 Volt Hot Y First Stage Compressor Y2 Second Stage Compressor G Fan ...

Страница 7: ...on Y Compressor SINGLE STAGE AIR CONDITIONER SINGLE STAGE AIR CONDITIONER Y Compressor Contactor SINGLE STAGE AIR CONDITIONER SINGLE STAGE AIR CONDITIONER C 24 Volt Common Y1 First Stage Compressor L Malfunction Light Y2 Second Stage Compressor G Fan PP32U71124 PP32U72124 THERMOSTAT R 24 Volt Hot W2 Second Stage Heat DHM Dehumidistat HM Humidistat O Reversing Valve Energized in Cool 24VAC Humidifi...

Страница 8: ...on C 24 Volt Common Y1 First Stage Compressor O B Reversing Valve L Malfunction Light Y2 Second Stage Compressor G Fan DN22U00124 THERMOSTAT E Emergency Heat AUX Auxiliary Heat R 24 Volt Hot Heat XFMR R 24 Volt Hot Cool XFMR 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise 3 Part Number S1 2HU16700124 3 O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot ...

Страница 9: ... 1490 1440 1390 1315 1230 1155 1050 920 D 1325 1270 1225 1175 1105 1045 990 905 890 790 FC9M080C16UP11 FC9M100C16UP11 A 1960 1955 1925 1890 1830 1765 1695 1615 1600 1485 B 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 C 1230 1275 1285 1300 1310 1300 1280 1245 1190 1070 D 930 945 965 975 975 975 975 950 910 850 FC9M120D20UP11 A 2560 2485 2410 2320 2220 2135 2035 1920 1785 1650 B 2090 2050 1990 ...

Страница 10: ...e 0 58 0 50 0 60 0 50 0 8 4 Multiply percentage by airflow difference to obtain airflow reduction 0 8 x 110 88 5 Subract airflow reduction value to airflow 0 50 to obtain actual airflow 0 58 ESP 2288 88 2197 ACCESSORIES PROPANE LP CONVERSION KIT 1NP0680 All units This accessory conversion kit must be used to convert natu ral gas N units for propane LP operation Conversions must be made by qualifie...

Страница 11: ...259720 CTG B 0108 Unitary Products Group 11 NOTES ...

Страница 12: ...to change without notice Printed in U S A 259720 CTG B 0108 Copyright by Unitary Products Group 2008 All rights reserved Supersedes 259720 CTG A 0606 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Отзывы: