Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
AC8B060F1
INDOOR COIL MODEL NO.
FC62D + MV20D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1750
1850
1950
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
57.1 61.0 60.6 66.2 71.1 58.0 61.4 61.2 66.8 72.2 58.8 61.6 61.8 67.3 73.3
S.C.
58.1 53.7 44.6 44.7 36.4 59.0 54.7 46.2 45.8 36.6 59.8 55.6 47.7 46.8 36.8
K.W.
3.20 3.25 3.26 3.32 3.36 3.27 3.32 3.31 3.39 3.44 3.36 3.40 3.38 3.47 3.53
75
T.C.
55.3 58.5 58.0 63.4 68.2 56.0 58.8 58.4 63.9 68.9 56.7 59.1 58.7 64.3 69.5
S.C.
56.3 52.5 43.9 43.6 34.8 57.0 53.5 44.9 44.6 34.9 57.7 54.5 45.8 45.6 34.9
K.W.
3.69 3.74 3.74 3.80 3.86 3.77 3.80 3.79 3.87 3.93 3.85 3.88 3.86 3.95 4.01
85
T.C.
53.6 55.9 55.4 60.6 65.3 54.1 56.2 55.5 60.9 65.5 54.6 56.5 55.6 61.2 65.8
S.C.
54.5 51.3 43.2 42.5 33.1 55.1 52.4 43.6 43.5 33.1 55.6 53.4 44.0 44.4 33.0
K.W.
4.19 4.23 4.22 4.29 4.35 4.26 4.29 4.28 4.35 4.41 4.34 4.36 4.35 4.43 4.49
95
T.C.
51.8 53.3 52.8 57.8 62.4 52.2 53.6 52.7 58.0 62.2 52.6 53.9 52.5 58.2 62.0
S.C.
52.7 50.1 42.5 41.5 31.5 53.1 51.3 42.4 42.3 31.4 53.5 52.4 42.1 43.2 31.2
K.W.
4.69 4.71 4.70 4.77 4.84 4.76 4.77 4.76 4.83 4.90 4.83 4.85 4.83 4.91 4.97
105
T.C.
48.6 49.8 49.3 53.9 58.3 49.1 50.1 49.3 54.1 58.2 49.5 50.4 49.2 54.2 58.1
S.C.
49.5 47.7 40.5 39.8 30.1 50.0 48.7 40.7 40.6 30.1 50.4 49.6 40.8 41.3 30.1
K.W.
5.39 5.40 5.38 5.46 5.54 5.46 5.47 5.44 5.53 5.60 5.54 5.55 5.52 5.60 5.67
115
T.C.
45.6 46.3 46.0 50.2 54.3 46.1 46.7 46.0 50.3 54.3 46.5 47.1 46.0 50.4 54.2
S.C.
46.4 45.4 38.6 38.2 28.7 46.9 46.2 39.0 38.9 29.0 47.4 46.9 39.4 39.6 29.1
K.W.
6.06 6.07 6.04 6.13 6.22 6.14 6.14 6.11 6.20 6.28 6.23 6.22 6.19 6.28 6.36
125
T.C.
42.6 42.8 42.6 46.4 50.3 43.1 43.3 42.7 46.5 50.4 43.5 43.7 42.7 46.5 50.4
S.C.
43.4 43.2 36.6 36.6 27.4 43.9 43.7 37.4 37.2 27.8 44.3 44.1 38.1 37.8 28.2
K.W.
6.74 6.75 6.71 6.80 6.89 6.82 6.82 6.78 6.87 6.96 6.91 6.90 6.86 6.96 7.04
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
AV/SV60D
–
0.96 0.96 0.99
F4FV060
–
0.96 0.96 0.99
MV20D
FC/MC/PC60D
0.96 0.96 0.99
MV20D
UC60D
0.96 0.96 0.99
MV20D
FC/MC62D
1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
(F,L)C8V*C20
FC/PC60C
0.95 0.95 1.00
(F,L)C8V*C20
FC/MC/PC60D
0.95 0.95 1.00
(F,L)C8V*C20
UC60D
0.95 0.95 1.00
(F,L)C9(C,V)*C20
FC/PC60C
0.93 0.93 0.99
(F,L)C9(C,V)*C20
FC/MC/PC60D
0.93 0.93 0.99
(F,L)C9(C,V)*C20
UC60D
0.93 0.93 0.99
(F,L)C9(C,V)*D20
FC/MC/PC60D
0.93 0.93 0.98
(F,L)C9(C,V)*D20
UC60D
0.93 0.93 0.98
(F,L)C8V*C20
FC/MC62D
0.98 0.98 1.01
(F,L)C9(C,V)*C20
FC/MC62D
0.97 0.97 1.00
(F,L)C9(C,V)*D20
FC/MC62D
0.97 0.97 0.99
(F,L)C9(C,V)*D20
HC60D
0.94 0.94 0.98
C*9C*D20
FC/MC62D
0.97 0.94 1.02
C*(8,L)C*C20 FC/PC60C
0.96 0.93 1.00
C*9C*C20
FC/PC60C
0.96 0.93 1.02
C*9C*D20
HC60
0.94 0.90 1.01
C*(8,L)C*C20 HD60
0.97 0.93 1.00
C*9C*C20
HD60
0.97 0.94 1.03
C*9C*D20
HD60
0.96 0.92 1.02
C*(8,L)C*C20 UC60C
0.94 0.89 1.00
C*9C*C20
UC60C
0.93 0.89 1.02
C*9C*D20
UC60D
0.94 0.89 1.01
G*9V*D20
FC/MC62D
0.97 0.94 1.02
G*9V*C20
FC/PC60C
0.96 0.93 1.02
G*9V*D20
HC60
0.94 0.90 1.01
G*9V*C20
HD60
0.97 0.94 1.03
G*9V*D20
HD60
0.96 0.92 1.02
G*9V*C20
UC60C
0.93 0.89 1.02
G*9V*D20
UC60D
0.94 0.89 1.01
Variable Speed
Furnace
Coil
T.C.
S.C.
KW