7 TROUBLESHOOTING
7.1 Alarm management
Alarms are indicated by an acoustic signal (if activated) and a message on the control panel.
In case of an alarm, shut down the boiler, eliminate the cause and restart the boiler according to the normal
procedure described in this manual.
Every alarm status causes immediate boiler shutdown.
The alarms, with causes and cures, which can appear on the control panel are listed below:
ALARMS - MESSAGES
Signalling
Fault
Possible causes
Cures
AL 1
POWER
FAILURE
-The boiler does not start.
-No power during the lighting
stage.
-Turn the boiler OFF by
pressing the button P4 and
repeat the lighting procedure.
-Other reinstatement
operations must be carried
out by a service centre.
AL 2
FUME
PROBE
-Occurs in case of a fume
temperature probe fault.
-The shutdown procedure is
activated.
-Probe fault.
-The probe is disconnected
from the board.
-Reinstatement operations
must be carried out by a
service centre.
AL 3
HOT FUMES
-Occurs if the fume probe
detects a fume temperature
above 280°C.
-The shutdown procedure is
activated.
-Too many pellets.
-Reduced heat exchange
in the system.
-Adjust the pellet flow.
-Other reinstatement
operations must be carried out
by a service centre.
AL 4
FAN FAIL
-Occurs when the fume
extraction fan is faulty.
-The shutdown procedure is
activated.
-The fume fan is blocked.
-Faulty speed control sensor.
-No power to fume fan.
-Reinstatement operations
must be carried out by a
service centre.
AL 5
NO IGNITION
-No flame in ignition stage.
-The shutdown procedure is
activated.
-The pellet hopper is empty.
-The heater is faulty, dirty or not
correctly positioned.
-Pellet load setting incorrect.
-Check pellets in hopper.
-Check the lighting
procedures.
-Other reinstatement
operations must be carried
out by a service centre.
AL 6
NO PELLETS
- Brazier not fed with pellets.
-The pellet hopper is empty.
-The pellet loading gearmotor
has to adjust.
-The gearmotor does not load
pellets.
-Check pellets in hopper.
-Adjust the pellet flow
-Other reinstatement
operations must be carried
out by a service centre.
AL 7
THERMAL
SAF
-Occurs in case of cutting in of
the auger duct temperature
safety thermostat.
-The system is stopped.
-The safety thermostat has
detected a temperature above
the setting threshold due to
overheating of the bottom part
of the hopper blocking
gearmotor operation.
-Check the cause of excessive
overheating.
-Reset the relevant safety
thermostat by pressing the
reset button.
Содержание DOMUSFIRE C17
Страница 3: ...DOMUSFIRE C17 C24 3 ...
Страница 8: ...DOMUSFIRE C17 C24 8 Dati tecnici caldaia ...
Страница 9: ...DOMUSFIRE C17 C24 9 Ingombri Caldaia a pellet mod DOMUSFIRE C17 DOMUSFIRE C24 ...
Страница 15: ...DOMUSFIRE C17 C24 15 2 7 Schema elettrico ...
Страница 36: ...DOMUSFIRE C17 C24 36 8 ALLEGATI ...
Страница 66: ...DOMUSFIRE C17 C24 66 8 ENCLOSURES ...
Страница 70: ...DOMUSFIRE C17 C24 70 Caractéristiques techniques de la chaudière ...
Страница 98: ...DOMUSFIRE C17 C24 98 8 ANNEXES ...
Страница 102: ...DOMUSFIRE C17 C24 102 Technische Daten des Kessels ...
Страница 129: ...DOMUSFIRE C17 C24 129 8 ANHÄNGE ...
Страница 133: ...DOMUSFIRE C17 C24 133 Datos técnicos de la caldera mod DOMUSFIRE C17 C24 ...
Страница 161: ...DOMUSFIRE C17 C24 161 8 ANEXOS ...