Manual Nitrox PDU SW-xxxx/ SM-xxxx
15 of 23
19.01.2018
5.8
Configuration - PDU
Nomination of output sockets and adjusting of Power-On delay.
Name:
Name of output socket
ON:
Adjusting of Power-On delay, per socket.
OFF:
Adjusting of Power-Off delay, per socket.
Max. delay time is 255 sec.
Consider
:
When the PDU is connected to the electric grid it will start the outputs automatically
according the preset data. Factory setting will start each output with a delay of 1
second.
If the PDU will be disconnected before finishing all operations, it will recover the last
status. Probably not started operations have to be started manually.