5.3 REFRIGERATION COMPRESSOR 

The refrigeration compressor is the pump of the system where the gas coming from the evaporator (low pressure side) is compressed up 
to the condensation pressure (high pressure side). The compressors utilized are manufactured by primary companies and are designed 
for applications where high compression ratios and wide temperature changes are present. 
The fully sealed construction is perfectly gas tight, so ensuring high-energy efficiency and long useful life. Dumping springs supports the 
pumping unit, in order to consistently reduce the acoustic emission and the vibration diffusion. 
The electric motor is cooled by the aspirated refrigerating gas, which goes through the coils before reaching the compression cylinders. 
The thermal protection protects the compressor from over heating and over currents. The protection is automatically restored as soon as 
the nominal temperature conditions are reached. 
 

5.4 CONDENSER UNIT

 

The condenser is the element in which the gas coming from the compressor is cooled down and condensed becoming a liquid. 
Mechanically, a copper tubing circuit (with the gas flowing inside) forms it immersed in an aluminum fin package. The cooling operation 
occurs via a high efficiency fan, which, in applying pressure on the air contained within the dryer, forces it into the fin package. It’s 
mandatory that the temperature of the ambient air will not exceed the nominal values. It is also important 

TO KEEP THE UNIT FREE 

FORM DUST AND OTHER IMPURITIES

 

5.5 FILTER DRIER 

  

Traces of humidity and slag can accumulate inside the refrigeration circuit, or long periods of use can produce sludge, could limit the 
lubrication of the compressor and clog the expansion valve or capillary tube. 
The function of the filter drier, located before the capillary tubing, is to stop the impurities, avoiding their circulation within the system. 
 

5.6 CAPILLARY TUBE

 

It consists of a piece of reduced cross section copper tubing located between the condenser and the evaporator and acts as a metering 
device to reduce the pressure of the refrigerant. Reduction of pressure is a function of the temperature to be reached within the 
evaporator: the smaller the capillary tube outlet pressure, the lower the evaporation temperature. 
  
The length and interior diameter of the capillary tubing is accurately sized with the performance to be reached by the dryer; no 
maintenance or adjustment is necessary. 

 

5.7 EVAPORATOR 

Also called an air-refrigerant exchanger. The liquid refrigerant formed in the condenser is evaporated in this part of the circuit. In the 
evaporation phase the refrigerant side of the evaporator tends to absorb heat from the compressed air present in the other side of the 
exchanger. The evaporator is immersed in the cabinet base of the dryer and insulated with non-CFC expanded insulating foam. The part 
is entirely constructed in copper and the cooler goes in the opposite direction to the air, thus contributing to limited pressure loss and to 
provide efficient thermal exchange. 
 

5.8 HOT GAS BY-PASS SOLENOID VALVE 

This valve is located between the pressure side of the compressor and the terminal side of the evaporator. 
Its purpose is to avoid conditions of low thermal charge in the dryer (low air flow or relatively cold air)  
The temperature inside the evaporators will drop below 32ºF. Temperature below 32ºF would eventually allow the formation of ice inside 
the evaporator, with the consequent blockage of air flow and, in the worst of the cases, the rupture of the evaporator itself. The DMC11 
Controller activates the coil of the solenoid valve. 

5.9 AIR-TO-AIR EXCHANGER 

The purpose of this exchanger is the transmission of the heat of the incoming air to the exiting cold air. The benefits of this solution are 
basically twofold: the incoming air is partially cooled down. Therefore the chilling system can be sized for a lower thermal drop, thus 
allowing a 40-50% energy saving; moreover, cool air will never reach the compressed air circuit and condensate will not form on the 
external surface of the piping. 

Содержание CNCM10

Страница 1: ...CNCM18 CNCMIOM 01 02 Rev REL Model Number Serial Number FILL IN COMPLETELY AT INSTALLATION Coaire Technologies Corporation 12226 Coast Drive Whittier CA 90601 TEL 562 463 3935 562 463 4928 website www coaire com e mail sales coaire com support coaire com Printed in U S A FORM CM AD03 FEB 2002 ...

Страница 2: ... authorization Said authorization may be obtained through our refrigerated dryer service department All refrigerated dryers parts materials must be returned freight prepaid to the Manufacturer s factory within 30 days of return authorization date Any shipment returned to the factory collect will be refused If an item is found to be warrantable the repaired item or replacement will be returned norm...

Страница 3: ...IFICATIONS 4 1 Technical Specifications CNCM10 CNCM18 115 1 60 4 2 Technical Specifications CNCM10 CNCM18 230 1 60 5 TECHNICAL DESCRIPTION 5 1 Operation 5 2 Flow diagram 5 3 Refrigeration Compressor 5 4 Condenser 5 5 Filter Drier 5 6 Capillary Tube 5 7 Evaporator 5 8 Hot Gas By pass Solenoid Valve 5 9 Air to Air Exchanger 5 10 Condensate separator 5 11 DMC5 Air Dryer Controller 5 12 Electric Schem...

Страница 4: ... equipment with panels removed Maintenance or control operation to be performed by qualified personnel only 1 ARIA AIR LUFT AIR Compressed air inlet connection point ARIA AIR LUFT AIR Compressed air outlet connection point Condensate drain connection point Operations that can be performed by the operator of the machine if qualified 1 NOTE Text that specifies items of note to be taken into account ...

Страница 5: ...tained in compressed air Any other use has to be considered improper The Manufacturer will not be responsible for any problem arising from improper use the user will responsible for any resulting damage Moreover the correct use requires the adherence to the installation instructions specifically Voltage and frequency of the main power Pressure temperature and flow rate of the inlet air Ambient tem...

Страница 6: ...le to hold the weight of the dryer Minimum ambient temperatures 34 F see the data plate for maximum temperature Allow at least 16 inches of clearance on each side of the dryer for proper ventilation and to facilitate maintenance operations The dryer doesn t require to be fixed to the supporting surface Locks will be required for special installations on brackets hanging etc 2 3 INSTALLATION LAYOUT...

Страница 7: ...s are supplied with a standard North American power cord and plug assembly two poles and a ground Be sure to provide the proper fuses or breakers based on the data tag information located on the back of the unit The main power receptacle must be protected with a thermal overload relay I n 0 03A rated to the power consumption of the dryer refer to data nameplate for nominal values The power supply ...

Страница 8: ...in system If a by pass is installed around the dryer close the inlet and outlet isolation valves open the by pass valve Verify that the manual valve mounted on condensate drain circuit is open Remove all packaging and other material that could obstruct the area around the dryer Turn on the main power to the unit Move the rocker ON OFF switch to the ON position in the on position the switch should ...

Страница 9: ... pressure drop p psi bar 4 4 0 3 Inlet outlet air connection Copper pipe OD 3 8 in 9 52 mm Refrigerant type R134 a HFC CH2F CF3 Refrigerant charging oz g 6 1 8 175 12 3 8 350 Cooling air capacity cfm m3 h 120 200 200 340 Power supply Phase V Hz 115 1 60 Nominal electric consumption A 2 2 3 0 Max electric consumption A 2 9 4 2 Compressor power HP 1 8 1 5 Weight lbs kg 62 28 68 31 Max noise level 70...

Страница 10: ... pressure drop p psi bar 4 4 0 3 Inlet outlet air connection Copper pipe OD 3 8 in 9 52 mm Refrigerant type R134 a HFC CH2F CF3 Refrigerant charging oz g 6 1 8 175 12 3 8 350 Cooling air capacity cfm m3 h 120 200 200 340 Power supply Phase V Hz 230 1 60 Nominal electric consumption A 1 1 1 4 Max electric consumption A 1 5 1 7 Compressor power HP 1 8 1 5 Weight lbs kg 62 28 68 31 Max noise level 70...

Страница 11: ...e capillary tube where the resulting pressure drop allows the refrigerant to boil off at a predetermined temperature Low pressure liquid refrigerant enters the heat exchanger where heat from the incoming air is transferred causing the refrigerant to boil the resulting phase change produces a low pressure low temperature gas The low pressure gas is returned to the compressor where it is re compress...

Страница 12: ...ed cross section copper tubing located between the condenser and the evaporator and acts as a metering device to reduce the pressure of the refrigerant Reduction of pressure is a function of the temperature to be reached within the evaporator the smaller the capillary tube outlet pressure the lower the evaporation temperature The length and interior diameter of the capillary tubing is accurately s...

Страница 13: ...ion for Set Point is 37 4 to 39 2 F 3 to 4 C with a fix hysteresis t equal to 0 9 F 0 5 ºC The hot gas by pass solenoid valve is activated when the temperature falls below 37 4 to 39 2 F 3 to 4 C and deactivated when the temperature rises over 38 3 to 40 1 F 3 5 to 4 5 C To adjust the Set Point perform the following steps Put a thermometer in the vacant copper well near the similar copper well tha...

Страница 14: ... temperature conditions exist during operation of system Avoid contact until system or component has dissipated heat DAILY Verify that the DewPoint displayed on the DMC11 is correct Check the proper operation of the condensate drain system Inspect the condenser for cleanliness EVERY 200 HOURS OR MONTHLY Blow entire unit out with compressed air Max 30 psig 2 barg Blow condenser coils out with compr...

Страница 15: ...e or service be sure that Ensure that the power is off and the unit is at atmospheric pressure Main power circuit breaker is in the off position per lock out tag out procedures Ensure that maintenance personnel have read and understand the safety and operations instructions in this manual High temperature conditions exist during operation of system Avoid contact until system or component has dissi...

Страница 16: ...ler doesn t work replace it Î The hot gas solenoid valve is blocked contact a certified refrigeration technician Î Excessive pressure drop within the dryer Î The DewPoint is too low the condensate is frozen and blocks air flow see specific point Î Check for throttling the flexible connection hoses Î The condensate is not draining Î Verify the electric wiring Î The condensate drain mechanical filte...

Страница 17: ...ion compressor 10 Cabinet Rear panel 3 Condenser unit 11 Cabinet Cover panel 4 Condenser unit fan 12 Cabinet Lateral panel 5 Solid filter dryer 13 Inlet Outlet connections 6 Hot gas by pass solenoid valve 14 Rocker switch Illuminated 7 Condensate drain valve strainer 15 DMC5 Air Dryer Controller 8 Condensate drain solenoid valve 16 DewPoint copper tube immersion well 11 1 13 10 2 5 15 6 3 4 9 14 1...

Страница 18: ...UTED BY COAIRE Technologies reverse the right to make changes at any time without notice as a result of our commitment to continuous improvement Coaire Technologies Corporation 12226 Coast Drive Whittier CA 90601 TEL 562 463 3935 562 463 4928 website www coaire com e mail sales coaire com support coaire com ...

Отзывы: