ELECTRICAL CONNECTION:
The unit must be connected to a single phase mains power supply network at the voltage and frequency indicated on the
characteristics plate of the extractor unit.
The electrical installation must include a bipolar phase switch with a distance between contacts of at least 3 mm.
Make the electrical connection by loosening the screw (2) until the cover (3) is free and connect the power supply cables to
the connection strip (E), the blue cable to N and the brown cable to L.
Replace the cover (3), fixing it in place with the screw (2) and finally press home the cover (A) until it is firmly held by the
clip (7) and the catch (1) (Fig. T).
The appliance must be permanently connected to a fixed electrical supply installation using twin conductor cable of at least
1 mm
2
in section and a maximum of 1.5 mm
2
.
No earth installation is required as the appliance has double insulation. (Class II).
IPX4
NOTE: TIMER and HYGRO connection
Must be carried out by following the wiring diagram for PLUS TIMER / PLUS HYGRO.
Connect the wires to the connection strip by using a pointed instrument (the tip of a screwdriver for example) to apply
pressure to (x) (x1, x2, x3) and pushing the striped wires (L, N, SL) into the holes (y) (y1, y2, y3).
Type PLUS TIMER
IPX4
Adjust the timer by turning the knob (4) in a clockwise direction to increase the operating time (3’ - 15’).
Type PLUS H
IPX4
Adjust the operating time by turning the red knob (4) in a clockwise direction.
Adjust the level of humidity by turning the blue knob (5) in a clockwise direction to increase the level.
The series PLUS fitted with a hygrometer incorporate a LED indicator. The LED is lit when the extractor is functioning either
activated by the switch fitted to the appliance itself or another, exterior switch. When the extractor is activated by the level
of humidity the LED is not lit. When the extractor is not operating the LED does not light.
Type PLUS C
IPX4
This model is fitted with a Start/stop pull-switch (6) (Fig. P).