C.M.C. n.v. - Airmaster S1 installation guide – V1.2 – MANY0402A.00
Page 30 of 35
Connector X01: Supply
Connector type: 2-pole Combicon with 5.08mm (0.20”) pitch.
Pin Name
Function
1
SUPPLY
Supply input: AC
2
SUPPLY
Supply input: AC
Cable harness plug: Phoenix Contact type MSTB2,5/2-ST-5,08 or compatible.
Connector X02: relays (optional)
Connector type: 4-pole Combicon with 5.08mm (0.20”) pitch
Pin Name
Function
Comment
1
NO-R5
Relay 5 normal open
(Optional VDR)
2
C-R5
Relay 5 common
(Optional VDR)
3
NO-R6
Relay 6 normal open
(Optional VDR)
4
C-R6
Relay 6 common
(Optional VDR)
Cable harness plug: Phoenix Contact type MSTB2,5/4-ST-5,08 or compatible
s
Connector type: 6-pole Combicon with 5.08mm (0.20”) pitch
Pin Name
Function
Comment
Connector X03: relay
1
C-R123
Relay 1,2,3 common
With VDR
300VAC/385VDC; I<12A
2
NO-R1
Relay 1 normal open
With VDR
300VAC/385VDC
3
NO-R2
Relay 2 normal open
With VDR
300VAC/385VDC
4
NO-R3
Relay 3 normal open
With VDR
300VAC/385VDC
5
NO-R4
Relay 4 normal open
With VDR
300VAC/385VDC
6
C-R4
Relay 4 common
With VDR
300VAC/385VDC
Cable harness plug: Phoenix Contact type MSTB2,5/6-ST-5,08 or compatible