background image

SIZE OF THE FIREPLACE

Once the design option has been 
determined for your fireplace, careful 
consideration should be given to the 
size best suited to the room in which 
it is located. This is important not 
only from an appearance standpoint, 
but also for it to operate efficiently.  
If it is too small for the room, for  
example, it may not produce a 
sufficient amount of heat – even if it 
functions properly. (Follow Chart I 
as a guide to the selection of the size 
best suited to your application.) Once 
the proper size has been determined, 
careful consideration should be given 
to other important areas, such as  
construction of the foundation, as 
well as the hearth, firebox, and  
smoke chamber. 

FOUNDATION

The foundation of the fireplace  
consists of concrete footings and  
masonry walls. Minimum code  
requirements must be met with 
respect to foundation and wall 
design. Unless specifically designed 
for additional loads, no other part of 
the structure or adjoining structure 
should be supported by the chimney. 
Immediately above the foundation 
wall, support for the combustion 
chamber and the extended hearth 
should be provided by a cast-in-place 
or precast concrete slab. The slab 
should include openings for outside 
combustion air vents and ash dumps. 
If a permanent form is used it must  
be non-combustible (i.e., steel, slate, 

SMOKE CHAMBER

The smoke chamber located  
directly above the firebox should be 
constructed using a choice of firebrick 
laid in with refractory mortar (ASTM 
C-199 medium duty) at a minimum 
thickness of 2 inches, a manufactured 
vitrified clay smoke chamber, or 4 
inches of solid masonry. As required 
by code, an insulating refractory  
parging product (also ASTM C-199 
medium duty) must be applied 1/2  
to 3/4 inch thick over the corbeled 
firebrick to form a smooth surface,  
allowing for an easy transfer of visible 
smoke and other gases through the 
chamber. (Refer to drawings for the 
minimum total wall thickness.)
The smoke chamber in the standard 
fireplace design should be constructed 
so that the sidewalls and front wall 
taper inward to form the support of 
the fireplace chimney. In this design, 
the chimney should be positioned so 
that it is centered on the width of the 
fireplace, and the back of the flue  
liner is aligned flush with the vertical 
rear surface of the smoke chamber. 
This configuration provides for 
smooth uninterrupted exiting of 
smoke and gases from the fireplace 
into the chimney. NOTE: The  
Rumford throat and smoke chamber 
are usually made of preformed parts. 
Follow the manufacturer’s directions 
when building a Rumford fireplace. 

CHIMNEY

The chimney is constructed directly 
on the smoke chamber. It consists of 
a flue liner and chimney wall. The 
chimney wall should have at least 
a 4 inch thickness of solid masonry 
between the flue liner and any  
exterior surface. Solid masonry 
products used in the chimney wall 
construction are those which are 
either 100 percent solid (brick, block 
or stone) or those which have cores 
or holes which do not exceed 25 
percent of the gross cross sectional 
area of any load bearing surface. The 
chimney should be separated from the 
flue liner by an air space that is not 
greater than the thickness of the clay 

our national building codes (ASTM 
C-199 medium duty). The back side 
of the firebox should be parged with 
mortar to provide added strength and 
insulation. Regular masonry mortar 
may be used here, but you may want 
to consider the specialty refractory 
products available which are designed 
for parging. The fill behind the 
firebox should be non-combustible 
rubble or solid masonry. 

PLACEMENT OF THE  

DAMPER AND LINTELS

Metal parts have a greater coefficient 
of expansion than masonry units. 
Since damper and lintels are metal, 
room for expansion or movement 
must therefore be provided. The 
damper should be laid on top of  
the firebox in a bed of refractory 
mortar only thick enough to ensure 
a level installation. A 1/8 inch to 1/4 
inch space should be left at the ends 
of the damper flanges. The damper 
should not support any masonry. Any 
fireplace lintel should be installed in 
a similar manner on a bed of mortar 
(for leveling purposes) with a 1/8 inch 
to 1/4 inch space on the sides and 
ends. This space may be filed with 
non-combustible soft material such 
as fiberglass insulation or a ceramic 
blanket. Any masonry corbeled from 
the firebox should not bear weight 
on the damper assembly. To prevent 
this, a second lintel may be installed 
with the same provisions for thermal 
expansion as the lintel installed above 
the fireplace opening. 

(e.g., by using a corbel header) to 
ensure structural integrity of the  
clay flue lining. The flue lining and 
surrounding masonry should touch 
each other only in spot locations  
(not to exceed 2 inches square each) 
to ensure proper alignment and  
support. In no circumstances should 
the clay flue liner be encased com-
pletely around its circumference in 
one location. Clay flue liners installed 
as such will have sufficient room for 
expansion and contraction during 
normal operating temperatures of 
residential  fireplaces  and  chimneys.         
When more than one flue is contained 
within the chimney, a solid masonry 
wall (wythe) separation of at least  
4 inches should be maintained  
between adjacent flues. The walls 
should be bonded to the chimney wall 
with either ties or masonry mortar. 

or corrugated metal). The concrete 
slab must not support the floor system. 

FIREBOX AND HEARTH 

All materials used to construct the 
firebox, hearth and extension must 
be made of non-combustible masonry 
materials. Brick or stone are the  
most popular. In no instance should 
combustible elements be used to  
provide support to the hearth of  
the fireplace. 

For fireplaces up to 6 sq. ft. (or an 
opening approximately 3 foot x  
2 foot) the hearth extension must 
project 16 inches in front of the 
fireplace and 8 inches beyond each 
side of the fireplace opening. For 
larger sized openings these dimensions 
increase to 20 inches in front and 
12 inches on the sides. The fireplace 
hearth and sidewalls should be  
constructed of a minimum of 2 inches 
of firebricks laid in refractory mortar. 
The firebox should be surrounded on 
three walls (front and two sides) by 
4 inch thick solid block for structural 
stability and thermal heat storage 
(refer to the drawings for minimum 
total wall thickness). Firebrick made 
to these specifications will provide 
minimal expansion and contraction 
throughout the operating temperature 
of residential fireplaces and chimneys. 
Therefore, no allowance to accommo-
date movement of firebrick is included.

All firebrick must be installed in  
refractory mortar conforming to  

flue liner. This will enable the flue 
liner to stay in alignment and permit 
expansion and contraction. 

All spaces between the chimney  
and the floor and ceilings should 
be insulated with non-combustible, 
fire-proof material. The fire proofing 
material of choice for use between 
the chimney and nearby wood joists, 
beams or headers should be galva-
nized steel that is at least 26 gauge 
and no thinner than 1/2 inch. Clay 
flue liners should be installed with 
non-water soluble refractory mortar 
bedding with close fitting joints left 
smooth on the inside and outside 
facing of the flue liner. Depending on 
the size and design of the chimney,  
the mason may choose to install an 
additional vertical section of masonry 
one unit wide (wythe) or support the 
structure by other accepted methods 

CHART I

  Fireplace Opening  Size of Room

  Width in Inches 

in Feet

 

24 to 32 

10 x 14

 

32 to 36 

12 x 16

 

36 to 40 

12 x 20

 

40 to 48 

14 x 28

 

48 to 60 

16 x 30

 

60 to 72 

20 x 26

2

3

Отзывы: