Clyde CKRS 05 Скачать руководство пользователя страница 3

Dimensions and technical data

550

820

690

544

65

280

L

HO

HI

EDS801/3 page3

Dimensions

Boiler model

CKRS 05

CKRS 06

CKRS 07

CKRS 08

CKRS 09

Output

kW

75

93

110

127

145

No. sections

5

6

7

8

9

Overall length

L

mm

800

922

1044

1166

1288

Combustion chamber length

mm

550

670

790

910

1030

Combustion chamber diameter

mm

Boiler door thickness

mm

Boiler flow  connection

HO

Boiler return connection

HI

Flue spigot diameter

mm

Technical data

Nominal heat output (full load) ncv

kW

75.6

93

110.5

127.9

145.3

Nominal heat input (full load) ncv

kW

81.6

100.5

119.3

138.1

157

Efficiency at 100% load (ncv)

%

92.6

92.5

92.6

92.6

92.5

Efficiency at 30% load (ncv)

%

95.3

95.4

95.4

95.5

95.6

Boiler seasonal efficiency(1)

%

85.4

85.4

85.4

85.5

85.6

Natural gas consumption (gcv)

m³/h

8.4

10.4

12.4

14.3

16.3

Oil consumption class D (ncv)

kg/h

6.9

8.5

10.1

11.6

13.2

Dry w eight (excludes burner)

kg

289

334

381

429

474

Water volume

litres

55

65

75

85

95

Flue gas mass flow  @3% oxygen

m³/h

8.4

10.4

12.3

14.2

16.2

Chimney draught

Pa

Gas side resistance

mbar

1.65

1.82

2.05

2.3

2.55

Flue gas temperature rise @3% oxygen

Nat gas (2)

°C

166

162

159

157

154

Class D oil

°C

188

181

178

176

173

Maximum w orking temperature

°C

Maximum hydraulic w orking pressure

bar

CE-Registration number

Water flow rates and hydraulic resistances

Water flow  rate at 11°C temp. rise

l/s

1.64

2

2.39

2.77

3.15

Hydraulic resistance at 11°C temp. rise

kPa

2.52

3.1

4.45

5.5

7.27

Water flow  rate at 20°C temp. rise

l/s

0.9

1.11

1.32

1.52

1.73

Hydraulic resistance at 20°C temp. rise

kPa

0.76

1

1.56

1.9

2.23

Water flow  rate at 30°C temp. rise

l/s

0.6

0.74

0.88

1.02

1.15

Hydraulic resistance at 30°C temp. rise

kPa

0.38

0.54

0.74

0.9

1.13

Notes: (1) Calculated from the non-domestic heating and cooling compliance guide for conformance w ith

                ADL2A and ADL2B 2013 using the formula n

seasonal

 =

0.81n

30%

+ 0.19n

100%

           (2) BS 7190:1989

336

102

R2

R2

150

180

6

CE 1015BR0260

5

90

Содержание CKRS 05

Страница 1: ...tallation requirements 4 5 Boiler control wiring 6 7 Seasonal efficiency of over 84 gives compliance with ADL2B 2013 for gas fired boilers without the need for additional heating credits Compact heat...

Страница 2: ...ating pressure of 6 bar and maximum temperature of 90oC CKRS boilers may be fired by Natural gas LPG Class D or Class C oil with 1 or 2 stage control The boiler is suitable for use in either open vent...

Страница 3: ...cludes burner kg 289 334 381 429 474 Water volume litres 55 65 75 85 95 Flue gas mass flow 3 oxygen m h 8 4 10 4 12 3 14 2 16 2 Chimney draught Pa Gas side resistance mbar 1 65 1 82 2 05 2 3 2 55 Flue...

Страница 4: ...ning the layout of the boiler room allowance must be made for opening the boiler door boiler assembling boiler cleaning and maintenance The boiler door may be hinged from the right as illustrated or t...

Страница 5: ...e burner Water circulation Refer Fig 4 The flow water temperature from the boiler must reach 60 C gas firing or 50 C oil firing within 10 minutes of the boiler being brought into operation Thereafter...

Страница 6: ...n Thermostat TR is a 1 stage item with CKCR1 and a dual thermostat 1 and 2 stage with CKCR2 0 I L1 L2 Fuse STB L3 L4 TR Thermometer EDS801 3 page6 Fig 6 Boiler control panel 1 2 3 4 5 6 7 8 9 10 11 12...

Страница 7: ...eg timeclock L1 On off indicator lamp L2 Boiler high limit lock out lamp lamp is illuminated when running and goes out in lock out condition L3 Stage 1 run lamp L4 Stage 2 run lamp STB High limit ther...

Страница 8: ...803 2 November 2014 Carnot Consult Ltd This publication is issued subject to alteration or withdrawal without notice The illustrations and specifications are not binding in detail All offers and sale...

Отзывы: