USER MANUAL : 

 

DOCUMENT NAME

The interface on the  logger needs to be told what the parameters are for the type of sensor attached, as well as, wh

sensor is measuring. This is done through the Loop Low Value, Loop High Value and Loop Units parameters. The Loop Low 
Value would be the lowest reading for that sensor (i.e. 4mA reading), the Loop High Value, the highest reading (i.e. 20mA 
reading) and the Loop Units, the unit of measure.
An example of a submersible 4-20mA level pressure sensor that reads up to 10 metres.
 

Loop Low Value = 0 

Loop High Value = 10 
Loop Units = metres 

Next  are the  'General Setup'  parameters.  These  are parameters that  a
applications of the logger. 

 

 
Very important here is the 'Vendor Code'. The 
server will automatically populate the database that is associated with a specific 
Vendor Code  assigned to it. Data is matched between these systems using that

communications between different vendors, preventing the cross accessing of 
Code is assigned to the relevant subsystem by the a

The description is a simple string of data that is stored by the  logger and used to identify that logger in simple terms. He

it is best to use wording that might explain something about where this logger has been applied.

Application types are explained in detail earlier in this document. To select an application type, simply click the dropdown 
arrow on the right of the entry field and select the application type you wish to apply.
When using a simcard to connect to a GSM network, the

need  from  you in  order to  connect  to their  network.  These  are  sometimes not  necessary  as the card  will  automatically 
connect but most will require them. The parameters are the APN Name, User

Networks generally require you to enter the APN Name but the Username and Password are not necessary. These details 
are obtained directly from your GSM service provider and most are published on their websites.

Cloudworks devices are also designed to allow 
the APN details here will result in the device connecting to your private network.
address which will be shown in the 'Local IP' field in the 'General Details' box.

All  Cloudworks  devices  connect  to  a    server  with  a  static  IP  or  domain  name.  They  usually  use  UDP/IP  protocols  and 
connect, by default, on port 13000. If you are running your own server, the Server Name or 

MANUAL : CDS541 CUMULUS PULSE LOGGER 

NAME 

CLASSIFICATION 

DATE 

PAGE

The interface on the  logger needs to be told what the parameters are for the type of sensor attached, as well as, wh

sensor is measuring. This is done through the Loop Low Value, Loop High Value and Loop Units parameters. The Loop Low 
Value would be the lowest reading for that sensor (i.e. 4mA reading), the Loop High Value, the highest reading (i.e. 20mA 

and the Loop Units, the unit of measure. 

20mA level pressure sensor that reads up to 10 metres. 

Next  are the  'General Setup'  parameters.  These are parameters that are used for the  communications, descriptions and 

 

Very important here is the 'Vendor Code'. The Cloudworks System supports multiple databases. What this means is that the 
server will  automatically populate the database that is associated with  a specific logger. Each database and 
Vendor Code assigned to it. Data is matched between these systems using that code. This code is also used to separate 

communications between different vendors, preventing the cross accessing of loggers by unauthorised users. The Vendor 

subsystem by the administrator during the creation of the database on the server.

The description is a simple string of data that is stored by the  logger and used to identify that logger in simple terms. He

it is best to use wording that might explain something about where this logger has been applied.

 

types are explained in detail earlier in this document. To select an application type, simply click the dropdown 

arrow on the right of the entry field and select the application type you wish to apply. 
When using a simcard to connect to a GSM network, there are a couple of parameters that your GSM service provider will 

need  from  you  in  order  to  connect  to their network.  These  are  sometimes  not  necessary  as  the card  will  automatically 
connect but most will require them. The parameters are the APN Name, Username and Password.  

Networks generally require you to enter the APN Name but the Username and Password are not necessary. These details 
are obtained directly from your GSM service provider and most are published on their websites. 

so designed to allow for the connection to custom private APN's for purposes of security. Entering 

the APN details here will result in the device connecting to your private network. These networks normally issue a static IP 

he 'Local IP' field in the 'General Details' box. 

All  Cloudworks  devices  connect  to  a    server  with  a  static  IP  or  domain  name.  They  usually  use  UDP/IP  protocols  and 
connect, by default, on port 13000. If you are running your own server, the Server Name or IP address as well as Server Port 

 

PAGE 

The interface on the  logger needs to be told what the parameters are for the type of sensor attached, as well as, what that 

sensor is measuring. This is done through the Loop Low Value, Loop High Value and Loop Units parameters. The Loop Low 
Value would be the lowest reading for that sensor (i.e. 4mA reading), the Loop High Value, the highest reading (i.e. 20mA 

re used  for the communications,  descriptions and 

supports multiple databases. What this means is that the 

. Each database and logger has a 

code. This code is also used to separate 

s by unauthorised users. The Vendor 

ase on the server. 

The description is a simple string of data that is stored by the  logger and used to identify that logger in simple terms. Here, 

types are explained in detail earlier in this document. To select an application type, simply click the dropdown 

re are a couple of parameters that your GSM service provider will 

need  from  you in  order  to  connect  to  their  network.  These are sometimes  not necessary  as  the  card will  automatically 

Networks generally require you to enter the APN Name but the Username and Password are not necessary. These details 

the connection to custom private APN's for purposes of security. Entering 

These networks normally issue a static IP 

All  Cloudworks  devices  connect  to  a    server  with  a  static  IP  or  domain  name.  They  usually  use  UDP/IP  protocols  and 

IP address as well as Server Port 

Содержание CDS541

Страница 1: ...se Logger User Manual User 28 February 2018 V2 0 Draft Confidential CDS541 Cumulus Pulse Logger User Manual docx This document contains information relating to the rights of Cape Digital Solutions The...

Страница 2: ...021 MANUAL CDS541 CUMULUS PULSE LOGGER NAME CLASSIFICATION DATE PAGE AMENDMENT HISTORY Amendment Details Amended By Compile document Alex Romanov Updated modem technology specs Alex Romanov New config...

Страница 3: ...0mA loop input and 24V loop power generator 1 8 5 Using the Pulse Input with echo output 1 8 6 Using the ECO interface 2 Logger Setup 2 1 Setup via Bluetooth Configure 2 2 Setup via Remote Configure 2...

Страница 4: ...r easy installation and setup without the need for a complicated server infrastructure Setup and management software CloudWorks is supplied free of charge to allow clients to manage their own networks...

Страница 5: ...of 30mA allowing for the powering of an external piece of equipment or current loop device eliminating the need option will also function under battery operation 2 x Pulse inputs with echo output Puls...

Страница 6: ...NAME CLASSIFICATION DATE PAGE or Bluetooth Interface Central Processor GPS Satellite Receiver Input Output Interface 3 x Alkaline Batteries External 12V Power Supply Power Management 2 wire Isolated 4...

Страница 7: ...usly connected to the server allowing for the streaming Cumulus Pulse logger uses standard D Cell alkaline batteries that will last several years In this mode the logger will wakeup adjustable normall...

Страница 8: ...und 13 Pulse 2 input 14 Ground for Pulse 2 input 15 Ground for Pulse 2 output pulse splitter output 16 Pulse 2 pulse splitter output switch to ground 17 Digital input 18 Ground for digital input 19 EC...

Страница 9: ...also populating the logger with alkaline batteries means that the logger can be put e is solar power available the logger will remain online with the server Should the solar power fail the logger wil...

Страница 10: ...igned to connect to a volt free mechanical or electronic switch The logger has Example for connecting to a volt free contact Example for connecting to an Open Collector electronic switch note that pin...

Страница 11: ...has been designed to supply a maximum of 30mA Please note using the 24V power generator to power a loop device uses a substantial amo he loop should only be powered each time the device needs to be re...

Страница 12: ...nfiguration of MANUAL CDS541 CUMULUS PULSE LOGGER NAME CLASSIFICATION DATE PAGE Example configuration of water meter with electronic interface Please note the polarity of the interface Ground connecti...

Страница 13: ...umulus Pulse logger has an onboard Bluetooth interface which allows for the device There are two different places in the software to activate the Bluetooth connection The first option is from the log...

Страница 14: ...r the Refresh button to start the search again Please remember that battery operated devices will need the Bluetooth interface activated before it will be found by the Bluetooth Server This is normall...

Страница 15: ...Firstly it will stream diagnostic information is operating This will be information like the GSM signal strength next wakeup time is initiating a connection to the server ommand Mode which allows the...

Страница 16: ...ed into Command Mode and the current setup data retrieved and displayed on the right hand screen nt to the device only after the parameter setup field has been left What this means is that while adjus...

Страница 17: ...an be cleared by right clicking in this box and before any of the settings changes or other instructions are accepted command in Diagnostic Mode will cause the logger to switch to Command Mode but tha...

Страница 18: ...attery or Mains Digital input status 20mA loop current reading in milliamps 20mA current loop reading with its calibration data implemented including the unit The I O Parameter block is the data used...

Страница 19: ...pulate the database that is associated with a specific logger Each database and Vendor Code assigned to it Data is matched between these systems using that code This code is also used to separate comm...

Страница 20: ...number is normally not required as your network will default this value This can be customised using the SMS Serv Centre field If you are using a foreign simcard on a network the logger will need to b...

Страница 21: ...gle chance to wake up fails it will return to sleep and a only reconnect at the next wakeup period At the start of a wake up the Max Start Time timer will be started Should the connection to the serve...

Страница 22: ...V 30mA power generator The Cumulus Pulse Logger can generate a stable 24V allowing for the powering of an external piece of equipment or current loop device the need for a secondary power supply This...

Страница 23: ...for a couple of minutes typically 5 minutes set in the server software in order to get a fix If this takes too long the remote device will be put back to sleep without updating the position This is do...

Страница 24: ...ent Upgrading firmware on the logger can be done through the Bluetooth interface Newer versions of the software for each into the Cloudworks software so will not need an internet connection to collect...

Страница 25: ...is complete the following message will be displayed Please power cycle the logger and then reconnect the Bluetooth interface if you wish to carry out further configurations when a logger is in battery...

Страница 26: ...when you configure via the Bluetooth setup option Again d commands are sent to the device only after the parameter setup field has been left What this means is that while adjusting a parameter in its...

Страница 27: ...enting you from making any further changes The Remote Configure screen has one further tool available in its arsenal and that is the Send Test SMS function The purpose of this function is to not only...

Страница 28: ...n which are picked up As you can see the parameters are the same as when you configure via the Bluetooth setup option with one or two minor All the parameter fields are empty at this point To create a...

Страница 29: ...ts that are still present in the database Each command has associated with it a status those that still need to be executed Listed also is the response to each command for diagnostic purposes You can...

Отзывы: