CLIVET WSH-EE 101 Скачать руководство пользователя страница 14

 

M03Q40G6-03 30/07/08 

pag 

14 

 

WATER CONNECTIONS

 

 

GENERAL 

Piping must be designed with the least possible number of 
bends and head variations. If the pressure chute of the 
installation is above the useful prevalence of the pump, the 
water delivery capacity is reduced as well as, as a 
consequence, the thermal exchange and the yield.  

INTERCEPTING VALVES 

Install on the input and output of the user parts 
(exchangers, coils, humidifiers, etc) So that it will be 
possible to carry out all the service operations and possible 
substitutions without emptying the installation. 

PRESSURE AND TEMPERATURE INDICATOR 

Install on the input and output of the user parts 
(exchangers, coils, humidifiers, etc) So that it will be 
possible to carry out all the service operations. 

AUTOMATIC OR MANUAL ESCAPE VALVES 

Install the highest points of tubes in a way that the air can 
escape form the circuit.  

BLEEDING COCK 

Install them at the lowest points of the circuit, so as to allow 
emptying. 

LEAKAGE TESTS 

Before performing the insulation of the tubes, carry out a 
leakage test. 

TUBE INSULATION  

All tubes of water must be insulated so that to avoid the 
formation of condensation and thermal dispersions along 
the tubes themselves. Verify that the insulation is the 
vapour coil type. The connections for the air escape and for 
the emptying must be out of the insulating thickness to 
assure the accessibilità. 

CONNECTIONS SUPPORTS 

The weight of the hydraulic connections must be supported 
in the exterior of the unit so as not to stress the connections 
of user devices (exchangers, coils, humidifiers, etc ) . 

ANTI-VIBRATION DEVICES 

In case of units with anti-vibration devices, it is necessary to 
assemble elastic joints, even on water connections. 

RISK OF FREEZE 

If the unit and the relevant water connections are subject to 
temperatures near 0°C:  

• 

mix the water of the system with glycol 

• 

protect the tubes with heating cables under the tubes 
insulation 

• 

empty the system by verifying that: 

no taps are closed so they can not trap the water, 
even after emptying 

there are no low points where the water can 
stagnate even after emptying; blow if necessary 

INTALLATION EMPTYING  

The refilling of the water present in the installation increase 
the oxidation phenomena and lime deposits.  
If necessary empty only the interested system section and 
anyway empty or refill the installation if necessary .  

EXPANSION TANK 

The installation must be kept at the right pressure by both 
an expansion tank and a combined valve of pressure 
reduction and discharge; if the components are present on 
the unit, they must be installed on the installation. The 
expansion tank must be dimensioned in function of the 
water in the installation. 

 

EXCHANGER USE SIDE 

 

FILTER 

It is very important for the water to be free of impurities. If it 
is not, the efficiency of thermal exchange is diminished. In 
worst cases, the exchanger can be irreparably damaged. If 
the filter is not present on the machine, it must be 
immediately installed upstream from the unit, in a position 
which can be easily reached for cleaning 

FLOW SWITCH 

The flow switch must be present as a component of the 
system, so as to ensure shutdown of the unit if water is not 
circulating. It must be installed in a straight tract of the 
tubes, not near the elbows, which can generate harmful 
turbulence  

UNFREEZABLE LIQUIDS 

If the unit is used when the water temperature is lower than 
+ 4°C, avoid the formation of ice by using unfreezable 
liquids (ex. Ethilenic Glycol) in the necessary percentage. 
The use must also be determined for room temperatures 
near 0°C . 

ANTIFREEZE HEATERS  

If the unit is equipped with antifreeze heaters on the 
exchanger side (standard or optional according to the 
models), verify that they are electrically fed during periods 
that the machine is stopped (night, weekends, long stops) 

WASHING THE SYSTEM 

Carefully wash the system by using clean water and 
discharge it before connecting the unit. 

 

Содержание WSH-EE 101

Страница 1: ...WSH EE WSHH EE 17 21 31 41 51 61 71 81 91 101 121 WATER COOLED WATER CHILLER FOR INDOOR INSTALLATION Installation and Use Manual M03Q40G6 03 21 11 07...

Страница 2: ......

Страница 3: ...8 CONNECTION TO THE MAINS 19 SYSTEM COMPOSITION 19 FUNCTIONAL CONNECTIONS 20 S T A R T U P 2 8 PRELIMINARY CHECKS 28 REFRIGERANT SYSTEM 28 WATER SYSTEM 28 ELECTRICAL SYSTEM 28 VERIFy tensions absorpti...

Страница 4: ...AL NUMBER This provides unique identification of the machine It makes it possible to trace the specific features of the unit and to identify the components installed in it Without this number it is no...

Страница 5: ...ases 8 in the utility side exchanger the refrigerant evaporates and absorbs heat from the water that returns from the equipment underfloor piping fan coil cooling it 9 the refrigerant at gaseous statu...

Страница 6: ...ining the system at a safety temperature in WINTER MAINTENANCE function Put the unit in OFF parameter 45 must be 1 yellow led is flashing Minimize the consumptions maintaining the system at a safety t...

Страница 7: ...dify the water temp in MAINTENANCE heating Control parameter parametro 43 Modify the water temp in MAINTENANCE cooling Control parameter 42 Only by SERVICE keypad A L A R M S T A T U S S E T only WSHH...

Страница 8: ...ct the instructions given in this manual will cause the warranty to lapse INTENDED USE The unit must only be used for the specific purpose it was designed L unit destinata al raffreddamento riscaldame...

Страница 9: ...zed entry GENERAL RISKS A smell of burning smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself I...

Страница 10: ...er Chart No FRIG 8 Product R 410A Identification of the supplier See heading or bottom of page No of emergency telephone See heading or bottom of page 02 Composition information on ingredients Substan...

Страница 11: ...ed from the driver compartment Verify that the driver is informed on the potential risk of the load and that he knows what to do in case of an accident or emergency Before starting the transport verif...

Страница 12: ...ressure of the circuits can assume values which activate the safety valves HANDLING The operation of handling the unit must be carried out respecting the instructions of the safety norms in force Legi...

Страница 13: ...accessible only to qualified and authorized personnel 2 SAFETY VALVE only if present on the unit the installer is responsible for evaluating the opportunity of installing drain tubes in conformity wi...

Страница 14: ...tect the tubes with heating cables under the tubes insulation empty the system by verifying that o no taps are closed so they can not trap the water even after emptying o there are no low points where...

Страница 15: ...essure switch 13 Discharge cock 14 inertial storage tank The accumulation tank is necessary in the event of the following the water in the system is very low the unit will not be used in a private hou...

Страница 16: ...s also required when geothermal probes are used WASHING THE SYSTEM Carefully wash the system by using clean water and discharge it before connecting the unit CONTROL OF FLOW RATE This makes it possibl...

Страница 17: ...n double temperature underfloor heating manages the elements of a mixed system with underfloor piping fan coil radiators circulator mixer valve outlet probe see details in the ELECTRICAL CONNECTIONS s...

Страница 18: ...ose value should be determined according to the plant features The section of supply cables and protection cable must be seized according to the characteristics of the protections used SIGNALS DATA LI...

Страница 19: ...TERMINAL Permits setting the unit function modes cooling heating ECO and to display the alarms ELECTRIC REFRIGERATOR WATER This is standard on certain types of unit L N 91 92 STA TUS SET ALA RM 2 1 RE...

Страница 20: ...he bridge should not be removed 2 CHANGING FROM SUMMER TO WINTER USING THE REMOTE CONTROL This function is activated with the 163 remmode 1 parameter Selection switch open unit in heating mode selecti...

Страница 21: ...p 1 0 IN REPLACEMENT OF THE COMPRESSOR the heaters operate only when the compressor is disabled due to an external temp lower than par 180 1 1 MAIN ADJUSTMENT UNIT IN HEATING MODE in heat pump mode th...

Страница 22: ...oiler in case of unit shutdown MAINTENANCE With the unit coupled to a boiler the maintenance function if enabled activates the boiler instead of the heat pump if necessary The diagram on the side is i...

Страница 23: ...d the sanitary hot water boiler thermostat must be set to the same value as the sanitary hot water set point of the machine If remote control will also be used for the SECOND SET POINT it is necessary...

Страница 24: ...ven near its operation limits curve B in the graph the compensation must be enabled during start up PARAMETERS INDICATIVE VALUES T EXT P 12 P 13 SET POINT 40 C 37 C P 175 P 74 P 160 A B T EXT 15 C 7 C...

Страница 25: ...water set point at the radiant panels can be managed in three ways 1 the valve is managed to maintain the outlet temperature at par 192 value independently of the unit operating mode COOLING or HEATIN...

Страница 26: ...VE IN HEATING mA P 23 P 24 COMP MAX P22 COMP 0 SET POINT mA P 21 P 20 COMP MAX P19 COMP 0 SET POINT 10 SET POINT COMPENSATION ON THE TEMPERATURE OR EXTERNAL ENTHALPY Optimises unit energy efficiency b...

Страница 27: ...e of conductors twisted and shielded Section of conductor 0 22mm 2 0 35mm 2 Nominal capacity between conductors 50 pF m nominal impedance 120 Recommended cable BELDEN 3105 A TYPE OF NETWORK The serial...

Страница 28: ...osition Check that there is no air in the circuit If required bleed it using the vent valves in the system When using antifreeze solutions make sure the glycol percentage is suitable for the type of u...

Страница 29: ...x flow rate L h The cooling power is shown in the TABLE ON GENERAL TECHNICAL DATA included in this manual referred to specific air water conditions or in the tables on cooling PERFORMANCE IN THE TECH...

Страница 30: ...ION The thermoregulation is based on the OUTLET temperature The unit is dimensioned for a determined TOTAL HEAD between input and output water temperature Usually the project step is 5 C if the value...

Страница 31: ...point visible at status 1 static set point The static set point can so be modified in a dynamic way by two CORRECTIONS based on as many unit external factors correction based on the ext temp enthalpy...

Страница 32: ...r on STANDBY for example during the weekend or the night time Periodically the system activates the circulation pump measures the water temperature and activates the compressor if required to take the...

Страница 33: ...ANCE The operating mode leds remain alight even when the machine is in the maintenance status The maintenance set points if activated control the water temperature when the unit is OFF or on STANDBY T...

Страница 34: ...arme serial faulty Allarme serial faulty Allarme serial faulty FUNCTIONING TEST The Test key allows the verification of the proper functioning of the all six signalisation LEDs When it is pressed all...

Страница 35: ...5 A L A R M S T A T U S S E T SET to esc VISIBLE STATUS FROM REMOTE KEYBOARD OR SERVICE KEYBOARD UNIT STATA MENU INDICE DESCRIPTION VALUE 1 Current Set Point C 2 Temperature drop in degrees centigrade...

Страница 36: ...dangerous situation for machine safety Before resetting the alarm discover and remove the cause repeated resetting could cause irreversible damage To avoid this the unit can only be reset MANUALLY fr...

Страница 37: ...17 Pump flow Auto E 18 System charged with water MANUAL E 19 Phase monitor Auto E 20 Antifreeze alarm MANUAL C 21 Antifreeze PREAlarm Auto C 22 High pressure PreAlarm Auto C 24 Pump change Auto E 25 f...

Страница 38: ...e unit where this problem may occur Check that the panelling is fastened correctly Poor fastening may give rise to malfunctions and abnormal noise and vibration MAINTENANCE INSPECTIONS Foresee inspect...

Страница 39: ...ter break for cooling units or when seasonal switching should be performed When restarting refer to the SWITCHING ON section Schedule technical assistance in advance to avoid hitches and be able to us...

Страница 40: ...7 7 79 1 70 8 69 16 0 44 28 60 46 43 78 38 84 26 01 5 2 6 92 22 65 8 79 2 73 7 73 16 2 44 77 60 95 44 24 39 32 26 46 5 4 7 96 23 70 9 77 3 73 6 79 16 4 45 26 61 44 44 69 39 79 26 90 5 6 8 97 24 73 10...

Страница 41: ...2 63 76 59 85 45 47 37 6 82 67 98 58 78 62 76 01 60 26 26 8 66 37 82 56 64 07 60 18 45 77 37 8 82 94 98 84 78 86 76 27 60 50 27 0 66 71 82 90 64 38 60 51 46 08 38 0 83 20 99 09 79 09 76 53 60 73 27 2...

Страница 42: ...are excluded or included other uses are isolated etc 4 Dirt water filter valves open air bubbles in the plant 5 dirty exchanger 6 Manostat transducer loose electric contacts terminals wiring cables i...

Страница 43: ...value in Ohms Temperature Heater Temperature Heater Temperature Heater Temperature Heater C C C C 20 0 67732 1 0 26094 22 5 11013 43 5 5146 19 5 66149 1 5 25543 23 0 10805 44 0 5063 19 0 64604 2 0 250...

Страница 44: ...must be stored in special containers When recovering the substances present in the unit all measures must be taken to avoid damaging persons and things and polluting the surrounding area Awaiting dism...

Страница 45: ...8 143 5 112 1 Water content l 0 6 0 6 0 8 0 8 0 9 1 1 2 2 2 5 2 9 2 9 3 2 Exsternal exchanger type of external exchanger 4 PHE No of exsternal exchangers 1 Water flow rate 1 l s 0 36 0 39 0 47 0 62 0...

Страница 46: ...5 0 57 0 78 1 02 1 26 1 48 1 68 1 88 2 31 2 65 pressure drop kPa 18 20 18 31 31 36 42 38 38 49 53 4 Connections Water fittings 5 1 GAS F Hydraulic circuit Max water side pressure kPa 550 Safety valve...

Страница 47: ...43 57 31 79 67 57 51 49 41 41 35 44 57 41 78 70 59 50 47 43 38 34 44 58 51 77 69 61 54 49 41 39 36 45 58 61 78 67 62 55 54 46 43 38 46 60 71 77 72 65 62 53 47 44 38 49 63 81 78 73 66 63 54 48 45 39 50...

Страница 48: ...0 21 21 22 27 W3 kg 20 19 21 22 24 W4 kg 22 23 23 24 29 Operating weight kg 80 81 85 88 102 Shipping weight kg 78 79 83 85 99 1 COMPRESSOR 2 INTERNAL EXCHANGER UTILITY SIDE EXCHANGER 3 EXTERNAL EXCHAN...

Страница 49: ...23 27 W4 kg 35 32 26 29 29 28 Operating weight kg 114 128 143 157 159 164 Shipping weight kg 111 125 140 153 155 160 1 COMPRESSOR 2 INTERNAL EXCHANGER UTILITY SIDE EXCHANGER 3 EXTERNAL EXCHANGER SOURC...

Страница 50: ......

Страница 51: ......

Страница 52: ...24 info clivet nl CLIVET TFAIRSYSTEMS P LTD Malur INDIA Tel 91 8151 232683 5 Fax 91 8151 232684 info clivettfa com CLIVET SPA BUREAUDE LIAISON EN FRANCE Verrier s le Buisson FRANCE Tel 33 0 1 69 20 25...

Отзывы: