6
2
General technical data
Performance
SIZE
18.2
20.2
25.2
30.2
35.2
Radiant panels
Cooling
Cooling capacity (EN 14511:2018)
kW 1/4
61,7
72,1
88,1
94,5
108
EER (EN 14511:2018)
2
4,30
3,96
4,44
4,28
4,02
Water flow-rate
l/s
1
2,95
3,44
4,21
4,51
5,14
User side exchanger pressure drops
kPa 1
33,4
44,7
65,2
74,4
95,1
Terminal unit
Cooling
Cooling capacity (EN 14511:2018)
kW 3
53,1
59,2
72,2
77,5
85,1
EER (EN 14511:2018)
2
3,10
3,00
3,21
3,20
3,10
SEER (EN 14511:2018)
5
4,85
4,84
4,89
4,81
4,74
Water flow-rate
l/s 5
2,54
2,83
3,45
3,70
4,07
User side exchanger pressure drops
kPa 3
25,2
30,9
31,3
35,8
42,8
Dati AHRI
Cooling capacity (AHRI 550/590)
kW 6
61,3
69,1
80,7
88,1
95,5
Total power input (AHRI 550/590)
kW 6
12,9
14,3
16,2
18,3
20,4
COP
R
6
4,75
4,83
4,98
4,81
4,68
IPLV
6
5,24
5,23
5,20
5,12
5,04
The Product is compliant with the ErP (Energy Related Products) European Directive. It includes the Commission delegated Regulation (EU) No 811/2013 (rated heat output ≤ 70 kW at
specified reference conditions) and the Commission delegated Regulation (EU) No 813/2013 (rated heat output ≤ 400 kW at specified reference conditions).
Contains fluorinated greenhouse gases’(GWP 675).
1. Entering/leaving water temperature user side 23/18 °C, Entering external exchanger air temperature 35 °C.
2. EER (EN 14511:2018) cooling performance coefficient. Ratio between delivered coolimg capacitu and power input in compliance with EN 14511:2018.
3. User side entering/leaving water temperature 12/7 °C, external exchanger entering air 35 °C.
4. Data referred to unit operation with inverter frequency optimized for this application..
5. Data calculated according to the EN 14825:2016 Regulation.
6. Data compliant to Standard AHRI 550/590 referred to the following conditions: internal exchanger water temperature = 6,7 °C. Water flow-rate 0,043 l/s per kW. Entering external
exchanger air temperature 35°C. Evaporator fouling factor = 0.18 x 10^(-4) m
2
K/W.
Содержание WSAT-YES 18.2
Страница 1: ...R32 M0SF00004 02 07 2021...
Страница 3: ......
Страница 12: ...Protection grilles Option PESM00007 PESM00008...
Страница 22: ...Connections performed by costumer...
Страница 24: ...Modular configuration Controller wiring...
Страница 58: ...Exchanger replacement Pump replacement Compressor replacement...