General technical data
Sound levels
Standard Mode
Size
Sound power level
Sound
pressure
level
Sound
power
level
Octave band (Hz)
63
125
250
500
1000 2000 4000 8000
dB(A)
dB(A)
18.2
62
67
68
72
79
72
64
52
65
83
20.2
68
79
76
73
76
67
59
52
65
83
25.2
65
66
69
73
80
73
65
51
66
84
30.2
59
67
69
72
80
73
65
51
67
85
35.2
87
77
76
76
79
68
60
53
67
85
Silenced Mode
Size
Sound power level
Sound
pressure
level
Sound
power
level
Octave band (Hz)
63
125
250
500
1000 2000 4000 8000
dB(A)
dB(A)
18.2
54
57
62
67
66
64
57
46
56
74
20.2
73
65
70
69
65
62
55
49
56
74
25.2
66
57
60
68
67
65
56
43
58
76
30.2
61
55
59
67
66
63
55
41
58
76
35.2
86
67
69
70
63
58
54
47
58
76
Super Silenced Mode
Size
Sound power level
Sound
pressure
level
Sound
power
level
Octave band (Hz)
63
125
250
500
1000 2000 4000 8000
dB(A)
dB(A)
18.2
48
51
57
62
58
61
56
44
52
70
20.2
68
64
70
64
59
62
54
48
53
71
25.2
69
58
59
66
62
59
51
40
53
71
30.2
61
49
56
64
61
59
52
39
53
71
35.2
86
63
58
68
60
56
54
48
55
73
At maximum conditions data
Sound levels refer to units with nominal test
conditions.
The sound pressure level refers to a distance of 1
meter from the outer surface of the unit operating in
open field.
Noise levels are determined using the tensiometric
method (UNI EN ISO 9614-2)
Data referred to the following conditions in heating:
- internal exchanger water = 30/35°C
- ambient temperature 7/6 °C
Data referred to the following conditions in cooling:
- internal exchanger water = 12/7°C
- ambient temperature 35°C
Sound levels refer to units with nominal test
conditions.
The sound pressure level refers to a distance of 1
meter from the outer surface of the unit operating
in open field.
Noise levels are determined using the tensiometric
method (UNI EN ISO 9614-2)
Data referred to the following conditions in heating:
- internal exchanger water = 30/35°C
- ambient temperature 7/6 °C
Data referred to the following conditions in cooling:
- internal exchanger water = 12/7°C
- ambient temperature 35°C
Sound levels refer to units with nominal test
conditions.
The sound pressure level refers to a distance of 1
meter from the outer surface of the unit operating
in open field.
Noise levels are determined using the tensiometric
method (UNI EN ISO 9614-2)
Data referred to the following conditions in heating:
- internal exchanger water = 30/35°C
- ambient temperature 7/6 °C
Data referred to the following conditions in cooling:
- internal exchanger water = 12/7°C
- ambient temperature 35°C
Silenced mode can be set from the user interface terminal
Super Silenced mode can be set from the user interface terminal
Size
Sound power level
Sound
pressure
level
Sound
power
level
Octave band (Hz)
63
125
250
500
1000 2000 4000 8000
dB(A)
dB(A)
18.2
55
65
67
72
77
70
61
50
67
83
20.2
55
65
67
72
77
70
61
50
67
83
25.2
57
67
69
73
79
72
64
51
69
85
30.2
57
67
69
73
79
72
64
51
69
85
35.2
57
67
69
73
79
72
64
51
69
85
Sound levels refer to units with maximum test
conditions. The sound pressure level refers to a
distance of 1 meter from the outer surface of
the unit operating in open field. Noise levels are
determined using the tensiometric method (UNI
EN ISO 9614-2)
63
Содержание WSAN-YES 18.2
Страница 1: ...MANUAL FOR INSTALLATION USE AND MAINTENANCE WSAN YES 18 2 35 2 ...
Страница 7: ...7 WSAN YES 18 2 35 2 M0ST10N19 00 2 RECEPTION ...
Страница 10: ...10 WSAN YES 18 2 35 2 M0ST10N19 00 Protection grilles Option PESM00007 PESM00008 3 POSITIONING ...
Страница 19: ...19 WSAN YES 18 2 35 2 M0ST10N19 00 Connections by the Customer 5 ELECTRICAL CONNECTIONS ...
Страница 22: ...22 WSAN YES 18 2 35 2 M0ST10N19 00 5 ELECTRICAL CONNECTION Modular configuration Controller wiring ...
Страница 65: ......