28 WSAN-XIN
18.2-45.2
M0M140L15-01
7.4 Change unit state
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Main menu
Select
Cmd Local state
3
Set
OFF - ECO - ON - Pump On
*
4
Confirm
6
Exit
* Local state
ECO: recurrent pump ON-OFF; compressors keep water system at setpoint ECO
Pmp ON: pump ON, compressor OFF
7.5 Change the mode
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Main menu
Select
Cmd Local mode
3
Set
Cool: water cooling
Heat: HEATING
4
Confirm
5
Exit
7.6 Modify
setpoint
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press
2
Main menu
Select
Unit parameters
3
Unit parameters
Confirm
Set Point
4
Select
Set Point
5
Set
Set Point
6
Confirm
7
Exit
Parameters
Short description
Description
P0583
SetPointCooling
Setpoint Cool
P0584
2SetPointCooling
2° Setpoint Cool
Enable by remote switch
P0855
SetPointECOCooling
Economic summer SetPoint
P0577
SetPointHeating
Setpoint Heat
P0578
2SetPointHeating
2° Setpoint Heat
P0579
SetPointECOHeating
Economic winter SetPoint
P0640
SetPointRecover
Recovery Set Point
P0580
ACSSetPoint
domestic hot water set point