M0M140L15-01 WSAN-XIN
18.2-45.2
23
6.12 Water reset
Menu accessible only after having entered the password.
Access reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
The water reset correction affects the setpoint defined by the Climate curve TExt (actual setpoint).
The setpoint is shown at status S0052: ActualUtSetp
Only if P0003: En WaterReset ≠ 0
Path: Main menu / Unit parameters / Water reset config
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Password
Set
Password
3
Press
4
Main menu
Select
Unit parameters
5
Unit parameters
Select
Water reset
6
Water reset
Select
Parameter
7
Set
8
Confirm
9
Press 3 sec.
10
Select
Local connections
Path: Main Menu / Unit parameters / Water reset
Parameters
Short description
Description
P0616
MaxCWRC
Maximum correction to be applied to the setpoint Cooling
P0617
SWRMaxC
Value of the WR control signal corresponding to the correction of the set Cool equal to P0616
P0618
SWRMinC
Value of the WR control signal corresponding to the correction of the set COOL equal to 0
P0615
MaxCWRH
Maximum correction to be applied to the setpoint Heating
P0619
SWRMaxH
Value of the WR control signal corresponding to the correction of the set Heating equal to P0615
P0620
SWRMinH
Value of the WR control signal corresponding to the correction of the set Heating equal to 0
P0616 / P0618: Cooling
P0615, P0619, P0620: Heating