EXCELLENCE VERSION
General technical data
Size
21
31
41
51
71
81
91
101
121
131
141
151
161
171
Radiant panels
Cooling
Cooling capacity
1
kW
4,25
6,33
8,06
10,3
13,0
15,9
18,7
20,9
26,5
33,0
39,8
40,5
47,6
52,9
Total power input
2
kW
1,07
1,68
2,10
2,72
3,42
3,87
4,84
5,74
6,27
8,34
9,88
10,3
12,0
13,9
EER (EN 14511:2013)
3
3,97
3,77
3,85
3,80
3,81
4,12
3,86
3,65
4,23
3,96
4,03
3,92
3,97
3,80
ESEER
4
5,86
5,43
5,95
5,09
6,04
6,62
6,86
6,61
7,71
5,77
5,77
5,30
4,98
4,89
Water flow-rate
1
l/s
0,20
0,30
0,39
0,49
0,62
0,76
0,89
1,00
1,27
1,58
1,90
1,94
2,27
2,53
Useful pump discharge head
1
kPa
58
51
43
45
46
64
59
55
69
100
103
101
84
67
ELFORoom and ELFOSpace terminal units
Cooling
Cooling capacity
5
kW
4,40
5,65
8,00
10,2
13,1
15,5
17,4
19,6
25,3
26,8
32,4
36,4
43,2
48,1
Total power input
2
kW
1,58
2,04
2,91
3,78
5,12
5,18
6,26
7,83
8,69
8,56
10,2
12,2
14,4
16,4
EER (EN 14511:2013)
3
2,79
2,77
2,75
2,69
2,55
2,99
2,78
2,50
2,91
3,13
3,18
2,99
3,00
2,93
ESEER
6
4,42
4,09
4,43
4,28
4,76
5,18
5,13
4,90
5,71
4,18
4,27
3,88
3,80
3,75
Water flow-rate
5
l/s
0,21
0,27
0,38
0,49
0,63
0,74
0,83
0,94
1,21
1,28
1,55
1,74
2,06
2,30
Useful pump discharge head
5
kPa
57
53
43
45
45
64
62
58
72
124
122
112
98
83
Compressor
Type of compressors
Rotary inverter dc
Scroll inverter DC
Refrigerant
R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
No. of compressors
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Oil charge
0,35
0,35
0,87
1,70
1,70
1,90
1,90
1,90
1,90
1,90
3,30
3,30
3,60
3,60
Refrigeration circuits
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Refrigerant Charge
2,1
1,9
2,1
3,3
4,4
4,7
4,7
4,7
6,8
6,8
6,8
10
10
10
User side exchanger
Type of internal exchanger
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
PHE
No. of exchangers
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Water content
0,56
0,64
0,64
1,14
1,80
2,37
2,37
2,37
3,13
3,13
3,13
3,13
4,27
4,27
External Section Fans
Type of fans
AX
AX
AX
AX
AX
EC
EC
EC
EC
EC
EC
EC
EC
EC
No. of fans
1
1
1
2
2
1
1
1
2
1
1
1
1
1
Standard airflow
653
1028
1028
2081
1996
2222
2306
2444
2778
4694
4694
5139
5649
5833
Installed unit power
0,12
0,15
0,15
0,15
0,15
0,19
0,23
0,27
0,20
0,63
0,63
1,03
1,02
1,36
Water circuit
Maximum water side pressure
550
550
550
550
550
550
550
550
550
550
550
550
550
550
Safety valve calibration
600
600
600
600
600
600
600
600
600
600
600
600
600
600
Min. installation water contents
17
20
25
33
40
50
53
57
63
68
87
99
113
117
Power supply
Standard power supply
230/1/50
230/1/50
230/1/50
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
400/3/50+N
1. Entering/leaving water temperature user side 23/18°C, external exchanger entering air 35°C
2. The overall power absorbed is calculated by adding the power absorbed by the comp the power absorbed by the fan - the percentage value of the fan to overcome external pressure drop + the power absorbed by the pump - the percentage value of the pump to
overcome pressure drop o the power absorbed by the auxiliary electrical circuit
3. EER (EN 14511:2013) cooling performance coefficient. Ratio between delivered cooling capacity and power input in compliance with EN 14511:2013
4. ESEER calculated by Clivet for radiant systems with water produced at 18°C by taking into account the load conditions and source water temperature as defined by EUROVENT for water at 7°C
5. User side entering/leaving water temperature 12/7 °C, external exchanger entering air 35°C
6. ESEER calculated by EUROVENT, for systems featuring terminal units with water produced at 7°C
7. PHE = plate exchanger
8. AX = axial-flow fan, EC = axial-flow fan + EC
The heads are intended as available at the unit connections
The pressure drops of the steel mesh strainer, supplied with the unit, have been already taken into consideration