11.3 KG4UP - Management kit up to 4 units in parallel by the two set point available for each
unit
Max 4 units
Automatic unit rotation
Connect PE1P0008 with SA3 unit 1, SA3 units 2, etc..
enable SA3 on unit 1, unit 2, etc.. (main menu Par CL CL45 = 22)
Set Tr15 on unit 1, unit 2, etc.. (main menu Par Tr Tr15)
example of Summer set point
2 units
3 units
4 units
unit 1
unit 2
unit 1
unit 2
unit 3
unit 1
unit 2
unit 3
unit 4
Summer set point (SPCool)
7
7,5
7
7,5
8
7
7,5
8
8,5
Tr15
0,5
-0,5
1
-0,5
-0,5
1,5
0,5
-0,5
-1,5
2° Summer set point (2°SPCool)
7,5
7
8
7
7,5
8,5
8
7,5
7
SCHEDULING EXAMPLE
monday: KA = OFF Enabled set summer, tuesday KA = ON 2° Enabled set summer, wednesday KA = OFF Enabled set summer
example summer scheduling
Monday
Tuesday
Wednesday
unit 1
7 (SPCool)
8,5 (2°SPCool)
7 (SPCool)
unit 2
7,5 (SPCool)
8 (2°SPCool)
7,5 (SPCool)
unit 3
8 (SPCool)
7,5 (2°SPCool)
8 (SPCool)
unit 4
8,5 (SPCool)
7 (2°SPCool)
8,5 (SPCool)