- G E N E R AL I N F O R M AT I O N
-
7
UNIT CONFIGURATIONS
( 1 )
( 2 )
( 3 )
( 4 )
( 5 )
( 6 )
WDAT-3
S
B
FC
2.300
LN
H
CE
S
( St andard)
-
(St andard)
-
(St andard)
S T
(St andard)
H
( St andard)
C E
(St andard)
R
B
F C D
S C
C
D
LN
E N
(1) VERSION
Standard (S)
Total Recovery ( R)
made using tube bundle exchangers to recover 100% of
the condensing heat for
production of hot water. The version in question is supplied
as standard with a variable-speed
low temperature device.
The compatibility of this Version with Hydropack has to be
checked with Our Commercial
Departement.
Partial Recovery (D)
it is achieved using tube bundle exchangers, suitable for
recovering the heat from the
desuperheating zone, up to a maximum of 20% of the total
heat of the unit.
The compatibility of this Version with Hydropack has to be
checked with Our Commercial
Departement.
(2) LOW TEMPERATURE
Low water temperature (B)
this version allows unit operation in the range of water and
glycol mix temperatures
b4°C and -8°C.
Two versions are available:
- Unit only for low temperatures.
- Unit with double operation set-point.
The availability of reduction capacity steps by means of
compressor capacity control
depends on the application temperature range. Please call
our commercial dept. for details.
(3) ENERGY SAVINGS
Direct free-cooling (FCD)
Version that allows to recovery free-cooling from ambient
when tha ambient air
temperature is lower than the system outlet water
temperature.
(4) ACOUSTIC CONFIGURATION
Standard (ST)
compressors soundproofing (SC)
this configuration is obtained by inserting the compressors
in a soundproof enclosure.
Low noise (LN)
this configuration is obtained by inserting the compressors
in a soundproofed enclosure
and reducing the speed of the fans, with a larger
condensing section.
Extremely low noise (EN)
with reference to configuration LN, the speed of the fans is
reduced further with a larger
condensing section, and the Low outside temperature kit is
supplied as standard with
variable speed fans. The compressors are enclosed in a
soundproofed enclosure and fitted
on rubber antivibration mounts, with flexible suction and
discharge pipes.
(5) ENERGY EFFICIENCY
High efficiency (H)
(6) HEAT EXCHANGERS APPROVALS
C = CLIVET (Internal testing)
CE = PED (European testing)