- E L E C T R I C AL C O N N E C T I O N S -
42
UNIT NETWORK – MINI NETWORK – MASTER SLAVE
The
CLIVET TALK
Local Network
system allows to connect up to 6 machines in a network which all serve the same
installation.
To interact with the network which controls the working of the system, it is necessary to have a CAN to CAN converter
code C5110692 for each machine.
Each single machine is equipped with the standard electronic devices: if necessary, it can function as an independent
unit.
SpinChiller
SpinChiller
SpinChiller
CAN 0
At use
Cavo CAN OPEN
Max. extension 200mt with a twisted and shielded pair
L max. single
derivation =20cm
L max. single
derivation =20cm
L max. single
derivation =20cm
Unit #3
Unit #2
Unit #1
Water Reset
Temp. Ext
UR% Ext
Mode remoto
PE1W0009
(C5110692)
Master #1
PE1W0009
(C5110692)
Slave #2
PE1W0009
(C5110692)
Slave #3
Unit MASTER
CAN 1
CAN 0
CAN 1
CAN 0
CAN 1
CONNECTION CABLE :
Section (nominal)
0.34mm2
Heater 70m
Ω
/meter
Impedance 120m
Ω
/meter
Propagation delay 5nS/metrer
Length MAX
200meters
DATALOGGER
cod PE1W0006
CONNECTIONS : make reference to the electrical panel and to SIGNALS/DATA LINES paragraph
LONWORKS
cod PE1W0014 / 25