M04J40H14-00 MDE-SL3
120.1-290.1
31
10 Alarms - Status
10.1 Alarms
The alarm code identifies the concerned circuit:
Example:
ee 1 01:TimeOutModCirc = circuit 1
ee 2 01:TimeOutModCirc = circuit 2
The number of refrigerant circuits depends on series and size of the unit.
t.i. input type:
DI = digital input
AI = analogic input
Module:
687 = main module
985 = circuit module
94U = thermostatic driver module
Input:
Connector number:
T1, T2, T3.....
PIN code:
X1, X2, Q13, DO1.....
t.a. alarm type:
A automatic reset
M manual reset
A/M automatic reset, (after N alarm interventions becomes manual reset)
code
detailed description
t.i.
module
input
t.a.
eE001
Phase monitor
DI
687 central
T13 DL1
A/M
EE003
Pump 1 overload
DI
687 central
T13 DL2
M
EE004
Pump 2 overload
DI
687 central
T4 D1
M
EE005
Pump 3 overload
DI
687 central
T13 DL2
M
ee010
Master Offline - Master Slave network enabled
A
ee011
Unit 2 in alarm - Master Slave network enabled
A
ee012
Unit 2 OffLine - Master Slave network enabled
A
ee013
Unit 3 in alarm - Master Slave network enabled
A
ee014
Unit 3 OffLine - Master Slave network enabled
A
ee015
Unit 4 in alarm - Master Slave network enabled
A
ee016
Unit 4 OffLine - Master Slave network enabled
A
ee017
Unit 5 in alarm - Master Slave network enabled
A
ee018
Unit 5 OffLine - Master Slave network enabled
A
ee019
Unit 6 in alarm - Master Slave network enabled
A
ee020
Unit 6 OffLine - Master Slave network enabled
A
ee021
Unit 7 in alarm - Master Slave network enabled
A
ee022
Unit 7 OffLine - Master Slave network enabled
A
EE023
Pump 1 thermal protection
DI
965 hydronic
T1 X4
M
EE024
Pump 2 thermal protection
DI
965 hydronic
T1 X5
M
EE025
Pump 3 thermal protection
DI
965 hydronic
T1 X6
A
EE026
Inverter thermal protection
DI
965 hydronic
T5 DL1
A
ee027
Water inlet temperature probe faulty
AI
687 central
T1 B1
A
ee028
Water outlet temperature probe faulty
AI
687 central
T1 B2
A
ee029
External air temperature probe faulty
AI
687 central
T1 B3
A
ee030
Signal logoff or short circuit
AI
687 central
T2 X1
A
ee031
Signal logoff or short circuit
AI
687 central
T2 X2
A
ee032:
External Humidity probe faulty
AI
687 central
T2 X3
A
ee033:
Cabinet temperature probe faulty
AI
687 central
T2 X4
A