5  Electrical connections

The characteristics of the electrical lines must be determined by qualified electrica personnel able to design electrical installations; moreover, 

the lines must be in conformity with regulations in force.
The protection devices of the unit power line must be able to stop all short circuit current, the value must be determined in accordance with 

system features.
The power cables and the protection cable section must be defined in accordance with the characteristics of the protections adopted.
All electrical operations should be performed by trained personnel having the necessary qualifications required by the regulations in force 

and being informed about the risks relevant to these activities.
Operate in compliance with safety regulations in force.

5.1  Electrical data

The serial number label reports the unit specific electrical data, included any electrical accessories.

The electrical data indicated in the technical bulletin and in the manual refer to the standard unit, accessories excluded.
The matriculation plate shows the indications foreseen by the standards, in particular:

 Voltage

 F.L.A.: full load ampere, absorbed current at maximum admitted conditions

 F.L.I.: full load input, full load power input at max. admissible condition

 Electrical wiringdiagram Nr.

5.2 Connections

1.   Refer to the unit electrical diagram (the number of the diagram is shown on the serial number label).
2.   Verify that the electrical supply has characteristics conforming to the data shown on the serial number label.
3.   Before starting work, ensure the unit is isolated, unable to be turned on and a safety sign used.
4.   Ensure correct earth connection.
5.   Ensure cables are suitably protected.
6.   Before powering up the unit, make sure that all the protections that were removed during the electrical connection work have been

restored.

5.3  Signals / data lines

Do not exceed the maximum power allowed, which varies, according to the type of signal.
Lay the cables far from power cables or cables having a different tension and that are able to emit electromagnetic disturbances.
Do not lay the cable near devices which can generate electromagnetic interferences.
Do not lay the cables parallel to other cables, cable crossings are possible, only if laid at 90°.
Connect the screen to the ground, only if there aren’t disturbances.
Guarantee the continuity of the screen during the entire extension of the cable.
Respect impendency, capacity and attenuation indications.

5.4  Power input

Fix the cables: if vacated may be subject to tearing.

The cable must not touch the compressor and the refrigerant piping (they reach high temparatures).

QS1: main isolator switch
XT1: terminal block of the customer connections

Содержание MSAT-XEE 10.2

Страница 1: ...M09G60E14 04 11 07 17 Installation and operating manual Air cooled condensing unit for outdoor installation MSAT XEE 8 2 30 2...

Страница 2: ...he installation and maintenance cost for the life cycle of the system The purpose of this manual is to provide you with information that is useful from reception of the equipment through installation...

Страница 3: ...Reception 6 3 Positioning 8 4 Refrigeranting connections 9 5 Electrical connections 12 6 Start up 14 7 Control 17 8 Maintenance 25 9 Decommissioning 28 10 Residual risks 29 11 Dimensional drawings 30...

Страница 4: ...arried out by inexperienced personnel they may cause damages to things and injuries people 1 4 Intended use Use the unit only for air conditioning Keep to the limits foreseen in the technical schedule...

Страница 5: ...n case of breakdown or malfunction Immediately deactivate the unit Contact a service centre authorized by the manufacturer The installer must train the user particularly on Start up shutdown Set point...

Страница 6: ...ceipt to supplier and the carrier Any disputes must be made within 8 days from the date of the delivery Complaints after this period are invalid 2 1 Storage Observe external packaging instructions 2 2...

Страница 7: ...EE 8 2 30 2 7 2 3 Packaging removing Be careful not to damage the unit Keep packing material out of children s reach it may be dangerous Recycle and dispose of the packaging material in conformity wit...

Страница 8: ...ll bearing points are aligned and leveled install the unit raised from the ground max distance allowed by the electrical connections Prefer places where the unit doesn t disturb the neighbours Avoid i...

Страница 9: ...nitrogen or dry air before connecting the pipes to the two units and without humidity to allow a good vacuum operation The installation of the pipes may affect the level of noise in the system instal...

Страница 10: ...riable climatic conditions for example fresh air temperature with ranges day night summer winter The receiver must have a capacity adequate to the installation and it must be positioned near the evapo...

Страница 11: ...frigerant gas tank venting the air out of the hose for connection to the gauge group Open the tap of the liquid line Open the taps of the gauge group and let liquid state refrigerant enter using an ap...

Страница 12: ...input at max admissible condition Electrical wiringdiagram Nr 5 2 Connections 1 Refer to the unit electrical diagram the number of the diagram is shown on the serial number label 2 Verify that the el...

Страница 13: ...customer ALM Cumulative fault signal max 24v AC QS1 Isolating switch XT1 Terminal block of the customer connections QG Electrical panel SA2 Compressor 1 request 5 6 RCTX Remote control For details see...

Страница 14: ...ks For details refer to the different manual sections Unit OFF power supply 1 safety access 2 functional spaces 3 refrigerant line section 4 length of the refrigerant lines 5 height difference in the...

Страница 15: ...acharge temperature WARNING BURN DANGERI 2 Condensation pressure 3 Liquid temperature 4 Dehydrator filter upstream and downstream temperature 5 Return pressure 6 Return temperature 7 Fresh air tempera...

Страница 16: ...the following data total voltages and absorptions with unit at full load absorptions of the different electric loads compressors fans pumps etc temperatures and flows of the different fluids water ai...

Страница 17: ...ssor 2 On fixed Not used 7 2 Keys Symbol Name Action Function 3 sec Up Increases the value Next voice Silenced alarm Down Decreases the value Previous voice On Standby Esc Esc WITHOUT SAVING MODIFICAT...

Страница 18: ...eset St on off CC copy card EUr alarm log reset PASS password EU alarms Alarm log 7 5 ON OFF OFF Emergency stop drive stops immediately without observing any timing Step Display Action Keys Menu Varia...

Страница 19: ...u Ai analogical inputs digital di digital inputs AO analogical outputs dO digital outputs 3 of Access diL1 4 diL1 Scroll the list Choose diL4 5 diL4 Press to see the value For digital inputs 0 input n...

Страница 20: ...r Select FnC 3 FnC Press dEF 4 dEF Select tA 5 tA Press 6 Press Back to the previous menu 7 12 Alarm log Before resetting an alarm identify and remove its cause Repeated resets can cause irreversible...

Страница 21: ...thermoregulation Thermoregulation St Stati Operating modes Operating stata CP ComPressori Compressor PI Pump Internal Primary circuit water pump FI Fan Internal Not used FE Fan External Fans external...

Страница 22: ...onday tE01 1 scheduling 1 2 scheduling 2 3 scheduling 3 5 assign the scheduling to tuesday tE02 1 scheduling 1 2 scheduling 2 3 scheduling 3 6 assign the scheduling to wednesday tE03 1 scheduling 1 2...

Страница 23: ...emperature The probe is not used to perform the ambient thermoregulation Follow these steps Step Display Action Keys Menu Variable Notes 1 Main menu Press PAr 2 PAr Press PAr 3 PAr Select Cr 4 Cr Pres...

Страница 24: ...Press Ui 5 Ui Select Ui22 6 Ui22 Confirm 0 7 0 Select 1 8 1 Confirm 1 9 Press Back to the previous menu Step Display Action Keys Menu Variable Notes 1 Main menu Press 3 sec 2 Select Air1 3 Air1 Press...

Страница 25: ...a unit booklet to take notes of the unit interventions In this way it will be easier to adequately note the various interventions and aid any troubleshooting Report on the booklet date type of interv...

Страница 26: ...l device test alarm signalling thermometers probes pressure gauges etc X European regulation 303 2008 Refer to the local regulations and ensure correct adherance Companies and technicians that effect...

Страница 27: ...27 8 9 Electric fans Check the fans and the relative protection gridsare well fixed the fan bearings evident by noise and anomalous vibrations the terminal protection covers are closed and the cable h...

Страница 28: ...vered by the legislation in question are marked with the symbol on the side With the aim of protecting the environment all of our units are produced in compliance with Directive EC on waste electrical...

Страница 29: ...Periodically check that all of the panels are correctly closed and fixed If there is a fire the temperature of the refrigerant could reach values that increase the pressure to beyond the safety valve...

Страница 30: ...d line piping d 16 mm 8 suction line piping d 28 mm 9 Main isolator switch 10 vibration mounts position 11 lifting holes position Size 8 2 10 2 12 2 A Length mm 1739 1739 1739 B Width mm 721 721 721 C...

Страница 31: ...d 16 mm 8 suction line piping d 28 mm 9 Main isolator switch 10 vibration mounts position 11 lifting holes position Size 16 2 18 2 22 2 A Length mm 1197 1197 1197 B Width mm 1143 1143 1143 C Height mm...

Страница 32: ...line piping d 16 mm 8 suction line piping d 28 mm 9 Main isolator switch 10 vibration mounts position 11 lifting holes position Size 26 2 30 2 A Length mm 2367 2367 B Width mm 1141 1141 C Height mm 15...

Страница 33: ...pressure level 1 m 3 dB A 60 60 60 64 64 65 65 65 Dimensions A Length mm 1739 1739 1739 1967 1967 1967 2367 2367 B Width mm 721 721 721 1143 1143 1143 1141 1141 C Height mm 1287 1287 1287 1599 1599 1...

Страница 34: ...2 Operating range with modulating fans 3 Operating range with option Min outdoor temperature 15 C MEN15 4 Operating range with option Min outdoor temperature 30 C MEN30 SST saturated suction temperatu...

Страница 35: ...monitor INSTALLATION AMMX Rubber antivibration mounts PGCEX Coil protection grilles outdoor air side Various MEN30 Minimum outdoor air temperature down to 30 C MEN15 Minimum outdoor air temperature do...

Страница 36: ...2 M09G60E14 04 13 1 RCTX Remote control QG Electrical panel XT1 Terminal block of the customer connections AP7 Room keypad A Max 100 mt Cable section Min 0 35 Max 1 mm2 The cable must be shielded LAN...

Страница 37: ...he function Par CF01 protocol selection 0 Disabled 1 Modbus Parameter modification Main menu Parameters CF CF01 Parameter Description Range CF30 address Modbus 1 255 CF31 BaudRate Baud Rate 0 1200 1 2...

Страница 38: ...the assembly of an LG mixer tap on the evaporator a CPCF valve on the condensing unit an additional connection pipe for the bypassed hot gas Condensing unit COND Condenser CPCF Hot gas by pass valve...

Страница 39: ...high pressure input circuit AUTO E080 Configuration error AUTO E081 Signalling of compressor operating hour exceeding Manual E090 Signalling of alarm log record exceeding Manual A AUTOMATIC reset M M...

Страница 40: ...sor 1 start dO L2 Compressor 2 start dO L3 Fan start dO L4 Not used dO L5 Not used dO L6 Cumulative alarm E1 1rE1 Not used 1rE2 Not used 1rE5 Not used 1rE6 Not used 1rE7 Not used 1SP4 Not used Sr Not...

Страница 41: ...43 Letter Seite...

Страница 42: ...Madrid Espa a Tel 34 91 6658280 Fax 34 91 6657806 info clivet es CLIVET GmbH Hydronic and Applied Division Hummelsb tteler Steindamm 84 22851 Norderstedt Germany Tel 49 0 40 32 59 57 0 Fax 49 0 40 32...

Отзывы: