3- FRESH WATER CIRCUIT

CWS Basic 121-161-201-251

When the circuit is under pressure with the antifreeze solution, purge the air as follows:
Bleed the entire circuit (manifold, fan coils and all the other purging points) starting from the lowest level
and keeping the circuit pressure at 1,5 Bars.
This purging must be done without running the pump.
Repeat all points, until no more air comes out from the bleeding valves, still keeping the pressure at 1,5
Bars.

Set to "Off" position each compressor switch.
Then check the sea-water intake is open and start the unit in "Cool" mode; both pumps will run.
Let the fresh water pump run for 30 seconds, then stops the system and bleed again all points, keeping
the pressure at 1,5 Bars.
Bleeding can be considered over when no more air is coming off the purging points and the fresh water
circulation pump runs even and quiet.
We strongly recommend that a special "air bleeding vessel" be installed in the fresh water circuit, just after
the pump outlet. This device will dramatically reduce the bleeding procedure and will also keep the system
free of air during its life. The "air bleeding vessel" is available in several sizes.

3.3- Pressurizing the fresh

The gauge set installed in the fresh water circuit is equipped with two charging ports, each (H-H1)
with a manual valve and an automatic check valve, which prevents the internal charge to come back
to the pressurized sanitary circuit in case of mistake. Use one of the two valves to charge and pres-
surize the circuit with fresh water up to 1,5 Bars, checking it with the pressure gauge. This port must
be permanently connected to the yacht sanitary water system.
Check that the circuit keeps the pressure over a certain period of time indicating that it is leak proof.
As you are sure that the circuit is leak proof, reduce the pressure to make room and add antifreeze
to the circuit.

3.4- Antifreeze solution

We suggest two methods for filling the fresh water circuit with antifreeze:

a) Calculate approximately the circuit capacity, fill it with water and add to it 20% of antifreeze, using
the second charging valve by gravity or using a pressure pump. Then connect the circuit to the sani-
tary water circuit of the vessel, pressurize up to 1,5 Bars and start purging the air. It is obvious that
if purging will be difficult, the percentage of antifreeze will decrease, as more water will be needed to
fill the circuit, therefore more antifreeze must be added to the circuit.

b) Empty the circuit from the water used for the leak test. Prepare the antifreeze solution in the quan-
tity needed to fill the circuit, made with 20% of antifreeze liquid; fill the circuit, using a pressure pump.
Then proceed with purging air and topping up the pressure using the solution.

water circuit

3.5- Air bleeding

Содержание CWS 121RC

Страница 1: ...ELS CWS BASIC 121 161 201 251 INSTALLATION OPERATION AND MAINTENANCE MANUAL S p A COMPANY WITH QUALITY SYSTEM CERTIFIED BY DNV ISO 9001 2000 Via Cantore 6 8 20034 Giussano MI ITALY Tel 39 0362 35321 fax 39 0362 852995 info veco net E mail Cod A041250 01 09 06 ...

Страница 2: ... adequate to the maximum operating load Also the sea water pump line should be done with a cable adequate to the power Supply must be connected from a suitable circuit breaker Any maintenance or inspection to the system must be performed dis connecting first the mains supply 1 1 Mains supply The connections of the other system components must be made following our schematics C312 p 2 and C650 for ...

Страница 3: ...Page 2 1 ELECTRICAL CONNECTIONS CWS Basic 121 161 201 251 ...

Страница 4: ...UD TERMOSTATO CALDO 230V A C FOR FAN COIL SUPPLY INSTALL FUSE 2A x FAN COIL PC CO THC THH EB FLOW SWITCH EXTERNAL CONTROL ALARM DELAY PUMP PUMP FUSE 5 A FOR PUMP PROTECTION Supply 400V A C S POWER 1 1 A 7 8 2 N N C C O T R N GND S R N GND T POWER La scatola elettrica contiene un dispositivo di sicurezza per impedire al compressore di girare nella direzione sbagliata Quindi dopo aver collegato l al...

Страница 5: ... position and the water outlet at top The centrifugal pump must be installed at least 0 50 m below the water line B The water intake must be scoop type oriented forward C Seacock strainer and pump intake should be connected without siphoning the piping should always rise from seacock to the pump D The intake line should be as short as possible it is very difficult to run a good circuit with an int...

Страница 6: ...er circuit Some rules are given at chapter 2 2 We can resume the following the circuit should always rise from water intake to the unit manifold After that the circuit can rise again or drop to the discharge port It is absolutely important to prevent that the circuit rises and drops making siphons which will prevent air to be drained causing an airlock during the navigation The discharge side of t...

Страница 7: ... Fresh water pump respect the layout schematic Fresh water circuit keep in mind that the easiest and shortest is the best Theorethically any high point in the circuit must have a purging valve Siphoning and up and down must be avoided as anyway they make the air purging difficult and trap air Fan coil respect the flow sense Each fan coil is equipped with a purging valve that must be acces sible bo...

Страница 8: ...H1 with a manual valve and an automatic check valve which prevents the internal charge to come back to the pressurized sanitary circuit in case of mistake Use one of the two valves to charge and pres surize the circuit with fresh water up to 1 5 Bars checking it with the pressure gauge This port must be permanently connected to the yacht sanitary water system Check that the circuit keeps the press...

Страница 9: ...Page 8 3 FRESH WATER CIRCUIT CWS Basic 121 161 201 251 ...

Страница 10: ...Page 9 3 FRESH WATER CIRCUIT CWS Basic 121 161 201 251 ...

Страница 11: ...of antifreeze lowers the freezing point of the water and adds an additional safety to the circuit Check that the fresh water circuit pressure gauge shows 1 5 bars This device stops the unit if the water flow stops below the preset minimum As explained at chapter 3 2 a safety flow switch is installed in the fresh water circuit outlet manifold It is very important to make sure that this safety devic...

Страница 12: ... heat up if the unit is in Heat mode As the fresh water temperature is approaching the set point Cool mode 12 C Heat mode 40 C the thermostat will stop the compressor The speed at which the water cools down depends from several fac tors as the number and capacity of fan coil connected the fan coil speed the room temperature etc therefore this value is not a valuable parameter 4 2 Start up 4 3 Sea ...

Страница 13: ...of the fan coils nearer to the manifold in order to let more water to reach the ones which are more distant Check that the thermostat sensor is correctly positioned in the air intake of each fan coil If the temperature control is Fan only the thermostat stops the fan when the ambient temperature reaches the set point IMPORTANT With the Fan only control the thermostat sensor must be installed on th...

Страница 14: ... system CWS Basic on the Heat or Cool The system will begin to run and also the compressor 5 3 Pumps Pumps start when the main Mode switch is turned to the Cool or Heat position IMPORTANT Both pumps keep running even when the compressor is stopped by the thermostat 5 3 Stop from the main electrical box Turn the Mode switch to the Off position ...

Страница 15: ...he fan speed control can run the fan on three different speeds The minimum speed is in the centre of the fan control switch 5 5 Fan coil in winter operation standard fan coil control panel The temperature in each cabin is controlled by a room thermostat which controls the fan motor The panel fan coil Mode switch see fig 1 must be set in red sun position Set the thermostat according to the desired ...

Страница 16: ...y of the sea water circuit inspecting the sea water strainer and evaluating or even measuring the sea water flow from the outlet We suggest keeping available a spare seal for the sea water pump and also one for the fresh water pump Clean or even replace the air filters on each fan coil A dirty air filter is dramatically reducing the fan coil efficiency as it reduces the air flow At the beginning o...

Страница 17: ...e control panel is properly set to yhe desi red Mode function Cool in summer and Heat in winter and that the thermostat is tur ned completely to 18 for summer operations and to 24 for winter operations Then check the connecting plugs If the plugs are ok then test the voltage at the plug terminals once the Max speed is selected The voltage between the black and the blue wires must be 230V If the vo...

Страница 18: ...Page 17 7 TROUBLESHOOTING CWS Basic 121 161 201 251 7 3 Cool mode the fresh water circuit doesn t cool ...

Страница 19: ...Page 18 7 TROUBLESHOOTING CWS Basic 121 161 201 251 7 4 Heat mode the fresh water circuit doesn t heat up ...

Страница 20: ...Page 19 8 TECHNICAL DATAS CWS Basic 121 161 201 251 8 1 Fan coil capacitor table Fan coil capacitor speed table for fan coil units capacitors codes Fan coil code Electrical box for models Capacitor Code ...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...Page 24 9 ELECTRICAL SCHEMATICS CWS Basic 121 161 201 251 ...

Страница 25: ...Page 25 9 ELECTRICAL SCHEMATICS CWS Basic 121 161 201 251 ...

Страница 26: ...Page 26 9 1 Codes of spare parts CWS Basic 121 161 201 251 16 CWS 121 161 201 251 ...

Страница 27: ...mostat support box Hot cycle thermostat Chilly cycle thermostat Thermometer Compressor Compressor klixon Stopper sae Needle valve Schrader High pressure switch Reversal cycle valve Valve coil Electrical box Inox steel tank Outlet rubber holder Outlet rubber holder screw Base fastener clamp 4 parts ...

Отзывы: