3- FRESH WATER CIRCUIT
CWS Basic 121-161-201-251
Follow the installation schematic, with particular regard to the sense and position of components.
Keep in mind the accessibility of components for the following steps of installation and also for
maintenance. Respect the flow sense marked on the unit.
Keep accessible the purging valve installed on the fresh water return. Respect the nominal diame-
ters of the manifold.
Manifold: install it in an accessible position, if possible with a certain heel (purging valve higher).
Check that each calibrating valve (if installed) of the manifold is fully open.
Expansion tank: respect the schematic. Connecting port must be upwards to drain out of it.
Fresh water pump: respect the layout schematic.
Fresh water circuit: keep in mind that the easiest and shortest is the best.
Theorethically any "high" point in the circuit must have a purging valve. Siphoning and "up-and-
down" must be avoided as anyway they make the air purging difficult and trap air.
Fan coil: respect the flow sense. Each fan coil is equipped with a purging valve that must be acces-
sible both at installation and also for maintenance.
This item must be installed on the fresh water
manifold. It must be accessible for maintenan-
ce and calibration.
The flow switch is needed as a safety device
which cuts out the compressor if the fresh
water circulation stops or is not enough.
The flow must be electrically connected to the
electrical box (two wires cables and ground
connection), as specified in the electrical
schematic.
3.1- 1Fresh water circuit connections
3.2- Flow switch (option)
Содержание CWS 121RC
Страница 3: ...Page 2 1 ELECTRICAL CONNECTIONS CWS Basic 121 161 201 251 ...
Страница 9: ...Page 8 3 FRESH WATER CIRCUIT CWS Basic 121 161 201 251 ...
Страница 10: ...Page 9 3 FRESH WATER CIRCUIT CWS Basic 121 161 201 251 ...
Страница 18: ...Page 17 7 TROUBLESHOOTING CWS Basic 121 161 201 251 7 3 Cool mode the fresh water circuit doesn t cool ...
Страница 19: ...Page 18 7 TROUBLESHOOTING CWS Basic 121 161 201 251 7 4 Heat mode the fresh water circuit doesn t heat up ...
Страница 21: ......
Страница 22: ......
Страница 23: ......
Страница 24: ...Page 24 9 ELECTRICAL SCHEMATICS CWS Basic 121 161 201 251 ...
Страница 25: ...Page 25 9 ELECTRICAL SCHEMATICS CWS Basic 121 161 201 251 ...
Страница 26: ...Page 26 9 1 Codes of spare parts CWS Basic 121 161 201 251 16 CWS 121 161 201 251 ...