6 Regulation
6.1
Chilled water regulation
+
To modify the working set point of the unit in Chiller mode, modify the value of parameter
2
, following the
parameter access procedure described above (chap. 2).
N° of parameters
Default value
2 Chiller set point
12 °C
4 Chiller differential
1 °C
48
∆
t
2 °C
NB: regulation is made based on the temperature reading at the evaporator inlet.
6.2
Hot water regulation
To modify the working set point of the unit in Heat Pump mode, modify the value of parameter
3
, following the parameter
access procedure described above (chap. 2).
N° of parameters
Default value
3 Heat pump Set Point
40 °C
5 Heat pump differential
1 °C
48
∆
t
2 °C
NB: regulation is made based on the temperature reading at the condenser inlet.