4 Alarm signals
Code
ALARM
Reset type
Cause
E00
Remote off
Automatic
%
Check the connection between
terminals 8 and 9.
E01
Circuit 1 high pressure
Manual
%
Check the power supply to the
fans;
%
Check if the condensing coils
are clean (Chiller);
%
Check the water flow rate to
the evaporator (Heat pump).
E02
Circuit 1 low pressure
Automatic
%
Check the flow rate to the
evaporator (Chiller);
%
Check if the condensing coils
are clean (Heat pump).
E03
Compressor 1 thermal
protection
Manual
%
Possible compressor motor
malfunction
E04
Circuit 1 fan thermal
protection
Manual
%
Possible electric fan motor
malfunction
E05
Circuit 1 antifreeze
Manual
%
Check the water flow rate to
the evaporator;
%
Check the operation of the
water pump;
%
Verify if cold set point is
correct (parameters: 2, 58, 59).
E06
ST2 probe malfunction
Automatic
%
Check the connections to
board terminals 3 and 4;
%
Probe malfunction.
E07
ST5 probe malfunction
Automatic
%
Check the connections to
board terminals 7 and 8;
%
Probe malfunction.
E21
Circuit 2 high pressure
Manual
%
Check the power supply to the
fans;
%
Check if the condensing coils
are clean (Chiller);
%
Check the water flow rate to
the evaporator (Heat pump).