TECHNICAL MANUAL  

CVM 2 

C 5001 CV/04-99 GB

 

  

11

 

4   Alarm signals 

Code 

ALARM 

Reset type 

Cause 

E00 

Remote off 

Automatic 

Check the connection between 

terminals 8 and 9. 

E01 

Circuit 1 high pressure 

Manual 

Check the power supply to the 

fans; 

Check if the condensing coils 

are clean (Chiller); 

Check the water flow rate to 

the evaporator (Heat pump). 

E02 

Circuit 1 low pressure 

Automatic 

Check the flow rate to the 

evaporator (Chiller); 

Check if the condensing coils 

are clean (Heat pump). 

E03 

Compressor 1 thermal 
protection 

Manual 

Possible compressor motor 

malfunction 

E04 

Circuit 1 fan thermal 
protection 

Manual 

Possible electric fan motor 

malfunction 

E05 

Circuit 1 antifreeze 

Manual 

Check the water flow rate to 

the evaporator; 

Check the operation of the 

water pump; 

Verify if cold set point is 

correct (parameters: 2, 58, 59). 

E06 

ST2 probe malfunction 

Automatic 

Check the connections to 

board terminals 3 and 4; 

Probe malfunction. 

E07  

ST5 probe malfunction 

Automatic 

Check the connections to 

board terminals 7 and 8; 

Probe malfunction. 

E21 

Circuit 2 high pressure 

Manual 

Check the power supply to the 

fans; 

Check if the condensing coils 

are clean (Chiller); 

Check the water flow rate to 

the evaporator (Heat pump). 

Содержание CVM 2

Страница 1: ...UPPLY 8 2 SETUP 8 2 1 ACCESS TO PROGRAMMING 8 3 SOFTWARE 9 3 1 DESCRIPTION OF USER INTERFACE 9 3 2 UNIT STARTUP 9 3 3 UNIT SHUTDOWN 10 3 4 ALARMS 10 3 4 1 Circuit and or compressor alarms 10 3 4 2 Gen...

Страница 2: ...ated inside the electrical panel and of a keyboard Enclosures fig 1 The boards for the continuous adjustment of the fan speed are connected to the main board The keyboard communicates with the main bo...

Страница 3: ...HNICAL MANUAL CVM 2 C 5001 CV 04 99 GB 3 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 Figure 1 1 MAIN BO...

Страница 4: ...r temperature Temperature C 55 50 40 30 20 Resistance 485 510 562 617 677 Temperature C 10 0 10 20 25 Resistance 740 807 877 951 990 Temperature C 30 40 50 60 70 Resistance 1029 1111 1196 1286 1378 Te...

Страница 5: ...0 15 5 Current mA 11 43 10 69 10 96 11 23 11 49 11 76 12 03 12 30 Pressure Bar 16 0 16 5 17 0 17 5 18 0 18 5 19 0 19 5 Current mA 12 56 12 83 13 10 13 37 13 63 13 90 14 17 14 44 Pressure Bar 20 0 20 5...

Страница 6: ...Circuit 1 compressor thermal protection 14 AT6 Circuit 2 compressor thermal protection 19 AT7 Circuit 1 fans thermal protection 13 AT8 Circuit 2 fans thermal protection 20 AT9 Water differential press...

Страница 7: ...1 1 KEYBOARD CONNECTION 1 7 Remote keyboard Figure 1 2 REMOTE KEYBOARD CONNECTION NB The supplementary transformer is the 230 12 Vac transformer supplied with the remote keyboard kit The maximum leng...

Страница 8: ...gh the parameter list using the arrow up and arrow down keys to visualise the required parameter Press the SET key the value of the parameter on the left hand side of the display will start flashing M...

Страница 9: ...and stand by condition required by the timer Then they become steady indicating operational readiness first of COMPRESSOR 1 and then of COMPRESSOR 2 If the unit is a HEAT PUMP the HEATING LED comes o...

Страница 10: ...ssor alarms are visualised with the corresponding flashing code on the DISPLAY while the ALARM LED comes on The related compressor is simultaneously shut down Alarm reset Press the ON OFF RESET key th...

Страница 11: ...l protection Manual Possible compressor motor malfunction E04 Circuit 1 fan thermal protection Manual Possible electric fan motor malfunction E05 Circuit 1 antifreeze Manual Check the water flow rate...

Страница 12: ...to the evaporator Check the operation of the water pump Verify if cold set point is correct parameters 2 58 59 E26 ST3 probe malfunction Automatic Check the connections to board terminals 5 and 6 Pro...

Страница 13: ...urs Operating hours since last operating hours reset 03 Circuit 1 fans 01 operating 02 off for defrosting 06 fans off 04 Circuit 1 defrosting not present 01 defrosting 02 compressor 1 safety count 03...

Страница 14: ...resent value in C 10 ERR probe error 44 Condensing water inlet temperature reading for unit with reversing cycle on water side ST5 or condensing pressure reading for unit with fans speed regulation SP...

Страница 15: ...et point 12 C 4 Chiller differential 1 C 48 t 2 C NB regulation is made based on the temperature reading at the evaporator inlet 6 2 Hot water regulation To modify the working set point of the unit in...

Страница 16: ...hiller 1 Water water chiller 3 Water air heat pump 5 Water water heat pump with reversing cycle on liquid side Table 7 1 UNIT TYPE 2 M COLD SET POINT COOLING p 58 p 59 120 C 10 3 M WARM SET POINT HEAT...

Страница 17: ...11 M CIRCUIT No 2 FAN OPERATING MODE 0 MODULATING OUTPUT 1 ON OFF 2 DISABLED 0 num 12 M MODULATING OUTPUT LOWER LIMIT 0 100 30 13 M MODULATING OUTPUT UPPER LIMIT 0 100 100 14 M SUMMER CUT OFF SET POIN...

Страница 18: ...23 M MAXIMUM DEFROST TIME 0 126 5 min 24 M DELAY BETWEEN FIRST CIRCUIT END OF DEFROST AND SECOND CIRCUIT START DEFROST 0 126 2 min 25 M FORCED VENTILATION PRESSURE DURING DEFROST 0 30 16 Bar CHILLER...

Страница 19: ...SOR START DELAY AFTER PUMP START 0 126 60 sec 41 M PUMP SHUTDOWN DELAY AFTER COMPRESSOR SHUTDOWN 0 126 60 sec 42 M DIFFERENTIAL PRESSURE SWITCH AND EXTERNAL FLOW SWITCH ALARM BY PASS E41 UPON PUMP STA...

Страница 20: ...2 CIRCUIT CONFIGURATION 58 M SUMMER SET POINT LOWER LIMIT CHILLER 20 p 2 10 C 59 M SUMMER SET POINT UPPER LIMIT CHILLER p 2 50 20 C 60 M WINTER SET POINT LOWER LIMIT HEAT PUMP 10 p 3 30 C 61 M WINTER...

Страница 21: ...P5 PROBE OFFSET 100 100 Bar 10 83 M SP6 PROBE OFFSET 100 100 Bar 10 84 CI DEFROST CYCLES 0 NOT ENABLED 1 ENABLED 1 flag 85 CI ANTIFREEZE HEATER 0 ABSENT 1 PRESENT flag 86 CI OPERATION OF ANTIFREEZE HE...

Страница 22: ...0 E p 68 2 2 PRESENT ONLY FOR ON OFF Table 7 5 REMOTE CONTROL CONFIGURATION WARNING If the unit is switched off using the keyboard s ON OFF key the antifreeze resistance control will also go off This...

Страница 23: ...TECHNICAL MANUAL CVM 2 C 5001 CV 04 99 GB 23 8 Enclosures...

Отзывы: