MALFUNCTIONS AND CORRECTIVE ACTIONS

Service

MALFUNCTION

Fan does not run 

Low air flow

from fan-coil unit

Fan-coil unit noisy

Fan-coil unit

does not heat

(sufficiently)

Fan-coil unit

does not cool

(sufficiently)

Fan-coil unit leaks

in the cooling mode

Room temperature

fluctuates

POSSIBLE CAUSES

Fan coil unit not switched on

No power

Cabling not connected

The supply is stopped by the float switche

Low fan speed

Air ducting obstructed

Filter dirty

Hight fan speed

Low air discharge temperature

Air discharge system obstructed

Fan bearing defect

Filter dirty

Fan not switched on

Heating fluid not hot

Low water flow rate

Low setpoint temperature

Controller or sensor positioned near heat source

Filter dirty

Fan not switched on

Cooling fluid not cold

Low water flow rate 

High setpoint temperature

Control located in cold air (e.g. near door)

Filter dirty

Condensate tray dirty

Cold water lines not insulated

Unit not suspended horizontally

Condensate drain plugged

Condensate pump pumps no water

Condensation on air register

The control located at wrong place

(e.g. at doors or in the airdischarge area)

High heating fluid temperature

Independently controlled units connected to same

water line (e.g. radiators with thermostatic valves)

CORRECTIVE ACTION

Switch on fan-coil unit

Check fusing/mains power

Connect cabling (qualified person only)

Verify the float

Select higher fan speed

Clear air ducting, for unrestricted air flow

Replace or clean filter

Select lower fan speed

Increase temperature setting of control

Clear air discharge system

Call field service

Replace or clean filter

Switch on fan

Switch on boiler

Switch on recirculation pump

Vent heating system

Check pump throughput

Check water distribution and reset pressure losses in different

lines

Increase control setpoint temperature

Relocate the control

Replace or clean filter

Switch on fan

Switch on chiller

Switch on recirculation pump

Vent system

Check pump throughout

Check water distribution and reset pressure losses in different

lines

Lower control setpoint temperature

Relocate the control

Replace or clean filter

Clean condensate tray

Insulate cold water lines

Realign unit and suspend unit horizontally

Check condensate drain for sufficient slope, clean and refill trap

Check power supply in terminal box and at pump

Check pump for dirt in the intake area

Check pump start-up

Check float switch for correct operation

Increase water flow temperature

Increase angle between air register stats and ceiling

Use coated air register

Increase fan speed

Relocate control to place where room temperature is repre-

sentative (remote from fan-coil unit)

Add or reset maximum and minimum supply air temperature

sensors

Reset boiler control

Split water supply; if impossible use flow control valves on oth-

er units and increase system pressure

Содержание CHD U-2T 1109

Страница 1: ...ere in funzione l apparecchio GB Please read this guide carefully before switching on the appliance FR Nous vous prions de bien vouloir lire attentivement ce mode d emploi avant de mettre l appareil e...

Страница 2: ...ort CASSETTE Housing made of self extinguishing plastic Electric fan unit centrifugal fans coupled directly to the 4 speed electric motor Exchange coil consisting of copper pipes with swirl design and...

Страница 3: ...low a temperature is harmful to health as well as being a useless waste of energy Avoid direct contact with the flow of air During storms put the installation on off switch to off This instruction boo...

Страница 4: ...ged by temperatures below freezing point During installation for safety reasons observe the fol lowing precautions Always use work gloves The unit must always be handled by two people Fan coil units s...

Страница 5: ...ead and 24 dB A noise level Float for conden sate drain pump operation control and to warn of overflow obstruction Switchboard with power and control terminal block with screw terminals Set up for fre...

Страница 6: ...6 UNIT DRAWINGS General CHD U 2T 506 706 CHD U 4T 506 706 CHD U 2T 809 1209 CHD U 4T 809 1209...

Страница 7: ...er level 4 Turbo speed dB A 57 58 64 61 65 67 Max speed dB A 50 52 59 55 61 62 Med speed dB A 43 45 57 51 56 57 Min speed dB A 38 41 51 48 52 51 Technical characteritics Water content l 1 04 1 04 1 04...

Страница 8: ...n n n n n n n Min speed kW n n n n n n n n n n n n Max water flow 2 l h n n n n n n n n n n n n Max pressure drop 2 kPa n n n n n n n n n n n n Heating capacity 3 Turbo speed kW 3 69 4 62 5 31 6 52 7...

Страница 9: ...0 430 Sensible 1 0 761 0 530 0 456 CHD U 2T 606 Total 1 0 779 0 632 0 377 Sensible 1 0 773 0 623 0 414 CHD U 2T 706 Total 1 0 868 0 782 0 603 Sensible 1 0 865 0 778 0 600 CHD U 4T 506 Total 1 0 785 0...

Страница 10: ...HD 809 Model Capacity Fan speed Turbo Max Med Min CHD U 2T 809 Total 1 0 870 0 782 0 711 Sensible 1 0 853 0 755 0 673 CHD U 2T 1109 Total 1 0 854 0 750 0 652 Sensible 1 0 835 0 720 0 614 CHD U 2T 1209...

Страница 11: ...etc Determine the ceiling hole by using the paper pattern Mark the position of the hangers on ceiling by using posi tion A B C and D in the paper pattern Depending on the type of ceiling the hangers...

Страница 12: ...tallation Primary air flow connection CHD hydronic cassette units 2 pipe as 4 pipe version have primary air flow connection They are equipped with inlets for treated air on the corner of the unit This...

Страница 13: ...IONS Installation Typical water piping diagram CHD 506 706 2 Pipe 4 Pipe CHD 809 1209 2 Pipe 4 Pipe Field supply Water in Shut off valve Water out Water out Shut off valve Water in Fan coil unit 3 way...

Страница 14: ...0 mm above the unit The condensate pipe must be insulated If more than one unit is installed in the room the drain sys tem can be made as shown The control panel can be reached by opening the grille a...

Страница 15: ...CREW M4x20MM SCREW M4x20MM SCREW M4x20MM INSULATION WATER CONNECTIONS Installation Auxiliary tray installation CHD 506 706 U 2T e U 4T 1 REMOVE THE PLASTIC CAP 2 INSTALLATION AUXILIARY DRAIN PAN SCREW...

Страница 16: ...ing for the fan speed control and for the connection with the safety device The installer has to provide input connection through access provided on the sides of the unit fixing the wires and taking c...

Страница 17: ...17 ELECTRICAL CONNECTION Installation CHD 506 706 CHD 809 1209...

Страница 18: ...nections cassette unit with wall mounted control For electrical connections of CHD cassette fan coil refer to following electrical diagrams Do not refer to wiring dia grams present on instruction shee...

Страница 19: ...cassette unit with wall mounted control For electrical connections of CHD cassette fan coil refer to following electrical diagrams Do not refer to wiring dia grams present on instruction sheet of wal...

Страница 20: ...llation Multiple connection cassette fan coil with wall mounted controls For electrical connections of CHD cassette fan coil refer to following electrical diagrams Do not refer to wiring dia grams pre...

Страница 21: ...llation Multiple connection cassette fan coil with wall mounted controls For electrical connections of CHD cassette fan coil refer to following electrical diagrams Do not refer to wiring dia grams pre...

Страница 22: ...nstallation Multiple connection cassette fan coil with wall mounted controls For electrical connections of CHD cassette fan coil refer to following electrical diagrams Do not refer to wiring dia grams...

Страница 23: ...nstallation Multiple connection cassette fan coil with wall mounted controls For electrical connections of CHD cassette fan coil refer to following electrical diagrams Do not refer to wiring dia grams...

Страница 24: ...m mer winter mode of operation and to switch the fan coil on off and hot start function by minimun thermostat kit Technical data Supply voltage 230 V 10 Supply frequency 50 60 Hz Contact rating 2 5 A...

Страница 25: ...the heating mode connecting the control with Minimum Temperature Thermostat kit This function activates the fan if the water is hot enough It is not available if the heating element is installed CONF...

Страница 26: ...hot start function by minimun thermostat kit Technical data Supply voltage 230 V 10 Supply frequency 50 60 Hz Contact rating 2 5 A cos 0 85 230V Remote water sensor 10 kOhm T 25 C Storage temperature...

Страница 27: ...acti vates the fan if the water is hot enough It is not available if the heating element is installed CONFIGURATION OF THE PSW CONTROL Digital outputs YV1 Valve control max 1 5 A This is used for open...

Страница 28: ...C Storage temperature 20 C 85 C Max storage humidity 90 not condensing Working temperature 0 C 55 C Max working humidity 90 not condensing Protection rating IP 30 Case material PC ABS flame retardant...

Страница 29: ...ot enough It is not available if the heating element is installed CONFIGURATION OF THE MTW CONTROL Analog inputs Air sensor input included in MTW control analog input used for temperature control Wate...

Страница 30: ...d Medium fan speed Minimum fan speed Automatic fan speed Led Blue LED Heating Cooling plus regulator call Blue LED blinking Hot start Too Cool function active Blue LED operation in Cooling mode Blue L...

Страница 31: ...act with the copper water pipe Digital outputs YV1 Valve control max 0 1 A This is used for opening the delivery valve and the conse quent water flow into the coil as described below 2 pipe system the...

Страница 32: ...remote control with dry cloth or a vacuum cleaner If damp cloth is used remove moisture by using dry cloth afterward AT THE START OF THE SEASON Check that nothing blocks the air inlet and outlet of in...

Страница 33: ...rection as shown by the arrows see picture to diffuse cool air Close windows and doors while operating the unit to pre vent leakage of cooled air to save energy In case of ineffective ventilation open...

Страница 34: ...Connect cabling qualified person only Verify the float Select higher fan speed Clear air ducting for unrestricted air flow Replace or clean filter Select lower fan speed Increase temperature setting o...

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ...us Platz 2 59439 Holzwickede Germany Tel 49 2301 91222 0 Fax 49 2301 91222 99 info climaveneta de www climaveneta de Climaveneta Espa a Top Clima Londres 67 1 4 08036 Barcelona Spain Tel 34 934 195 60...

Отзывы: