background image

BRA2 - BRN2  

EN

13

ELECTRICAL CONNECTIONS

I A

The BRA2 and BRN2 units leave the factory already wired,
and require the installation of an omnipolar thermal overload
switch, a lockable mains disconnecting switch for the con-
nection to the mains power supply, and the connection of
the flow switch to the corresponding terminals. All the above
operations must be carried out by qualified personnel
in compliance with the legislation in force.
For all electrical work, refer to the electrical wiring diagrams
in this manual.You are also recommended to check:
- that the characteristics of the mains electricity supply are

adequate for the absorptions indicated in the electrical
characteristics table below, also bearing in mind

Power to the unit

must be turned on only after installa-

tion work (hydraulic and electrical) has been completed.

All electrical connections

must be carried out by quali-

fied personnel in accordance with legislation in force in
the country concerned.

Respect instructions

for connecting phase, neutral and

earth conductors.
The power line should be fitted upstream with a suitable
device to protect against short-circuits and leakage to
earth, isolating the installation from other equipment.

Voltage

must be within a tolerance of ±10% of the rated

power supply voltage for the unit (for three phase units,
the unbalance between the phases must not exceed
2%). If these parameters are not respected, contact the
electricity supply company.

For electrical connections

, use double insulation cable

in conformity with current legislation in the country con-
cerned.

An omnipolar thermal overload switch and a lockable mains
disconnecting switch, in compliance with the CEI-EN stan-
dards (contact opening of at least 3mm), with adequate
switching and residual current protection capacity based on
the electrical data table shown below,must be installed as
near as possible to the appliance.

The devices

on the unit must be lockable.

An efficient

earth connection is obligatory. Failure to

earth the appliance absolves the manufacturer of all lia-
bility for damage.

In the case of three phase units

, ensure the phases

are connected correctly.

Do not use water pipes

to earth the unit.

ELECTRICAL DATA, BRA2 AND BRN2 WITHOUT HYDRONIC KIT 

F.L.I. 

Maximum power input

F.L.A. 

Maximum current input

S.A. Start-up 

current

S.A. LIM 

Peak current with peak limiter

Maximum values for sizing the protection switches and power supply cables 

Size

Power supply

Maximum values

Fuses (5x20T 250V)

(V-Ph-Hz)

FLA [A]

FLI [kW]

SA [A]

SA LIM [A]

FU1

FU2

FU3

BRA2 - BRN2 0021

230-1N-50

18,4

3,42

63,4

29,4

4A

3,15A

2A

BRA2 - BRN2 0025

230-1N-50

21,4

4,19

84,4

39,4

4A

3,15A

2A

BRA2 - BRN2 0031

230-1N-50

25,4

5,09

99,4

46,4

4A

3,15A

2A

BRA2 - BRN2 0041

230-1N-50

29,4

6,34

134,7

49,7

4A

6,3A

2A

BRA2 - BRN2 0021

400-3N-50

7,9

3,42

34,4

20,4

4A

3,15A

2A

BRA2 - BRN2 0025

400-3N-50

8,4

3,95

37,4

21,4

4A

3,15A

2A

BRA2 - BRN2 0031

400-3N-50

10,4

4,76

50,4

28,4

4A

3,15A

2A

BRA2 - BRN2 0041

400-3N-50

12,4

6,36

68,7

39,7

4A

6,3A

2A

BRA2 - BRN2 0051

400-3N-50

14,2

6,42

68,7

39,7

4A

6,3A

2A

BRA2 - BRN2 0061

400-3N-50

17,4

7,75

78,7

45,7

4A

6,3A

2A

ELECTRICAL DATA, BRA2 AND BRN2 WITH HYDRONIC KIT

F.L.I. 

Maximum power input

F.L.A. 

Maximum current input

S.A. Start-up 

current

S.A. LIM 

Peak current with peak limiter

Maximum values for sizing the protection switches and power supply cables 

Size

Power supply

Maximum values

Fuses (5x20T 250V)

(V-Ph-Hz)

FLA [A]

FLI [kW]

SA [A]

SA LIM [A]

FU1

FU2

FU3

BRA2 - BRN2 0021

230-1N-50

19,0

3,50

64,0

30,0

1,25A

1,25A

2A

BRA2 - BRN2 0025

230-1N-50

22,0

4,27

92,2

40,0

1,25A

3,15A

2A

BRA2 - BRN2 0031

230-1N-50

26,0

5,17

100,0

47,0

1,25A

3,15A

2A

BRA2 - BRN2 0041

230-1N-50

30,3

6,47

135,7

50,7

1,25A

6,3A

2A

BRA2 - BRN2 0021

400-3N-50

8,5

3,50

35,0

21,0

1,25A

1,25A

2A

BRA2 - BRN2 0025

400-3N-50

9,0

4,03

38,0

22,0

1,25A

3,15A

2A

BRA2 - BRN2 0031

400-3N-50

11,0

4,84

51,0

29,0

1,25A

3,15A

2A

BRA2 - BRN2 0041

400-3N-50

13,3

6,49

69,7

40,7

1,25A

6,3A

2A

BRA2 - BRN2 0051

400-3N-50

15,1

6,55

69,7

40,7

1,25A

6,3A

2A

BRA2 - BRN2 0061

400-3N-50

18,3

7,88

79,7

46,7

1,25A

6,3A

2A

Содержание BRA2 0021

Страница 1: ...Water chillers and air water heat pumps with centrifugal fans EN BRA2 0021 0061 BRN2 0021 0061 INSTALLATION USER AND MAINTENANCE MANUAL...

Страница 2: ...ins power supply connections 14 Installer connections 14 General technical data 16 Operating limits 18 Pressure drop and pressure head available 19 to system Fan pressure gain curves 21 Checking and s...

Страница 3: ...aid to the content shown Nonetheless Cli maveneta waives all liability deriving from the use of such document Read this document carefully All work must be performed components selected and materials...

Страница 4: ...andling the unit check the capacity of the lift equipment used respecting the instructions on the pack aging To move the unit horizontally make appropriate use of a lift truck or similar bearing in mi...

Страница 5: ...ns and weight with standard packaging Size 0021M T 0025M T 0031M T 0041M T 0051T 0061T Dimension L mm 970 970 970 970 970 970 Dimension P mm 660 660 660 660 660 710 Dimension H mm 840 1140 1140 1440 1...

Страница 6: ...te and heat loss The insu lating material must be a vapour barrier Make sure that the control and shut off devices protrude from the insulation 8 At the lowest points in the system install drain valve...

Страница 7: ...FFERENTIAL PRESSURE SWITCH 14 DRAIN CHEMICAL WASHING VALVE 15 SYSTEM VENT FACTORY CONNECTED INSTALLER CONNECTIONS UTILITY RETURN UTILITY OUTLET 12 12 9 15 8 14 14 2 10 2 4 3 5 11 6 1 15 15 7 13 System...

Страница 8: ...est points in the circuit or there are closed valves where water may stagnate It is recommended to use non toxic food grade antifreeze compliant with the standards in force in the countries where the...

Страница 9: ...may freeze Use hot wires on the condensate drain hose downstream of the unit to protect against frost C A B Safety valve D OUT IN C A B D OUT IN Safety valve BRA2 BRN2 Dimensions 0021 0025 0031 0041...

Страница 10: ...eration be repeated after the unit has been operating for a number of hours The pressure of the system should be checked regularly and if it drops below 1 bar the water content should be topped up Che...

Страница 11: ...etween the outlet and intake For the heat pump appliances the section of ducting inside the environment must be suitably insulated Use vibration damper joints on the duct fittings The outlet is suppli...

Страница 12: ...outlet collar Turn the air outlet collar 90 clockwise and fasten the four bolts that were removed previously Replace the fan holder cover P with the fan fitted and tighten the fastening screws To move...

Страница 13: ...it must be lockable An efficient earth connection is obligatory Failure to earth the appliance absolves the manufacturer of all lia bility for damage In the case of three phase units ensure the phases...

Страница 14: ...diagram enclosed with the product REMOTE ON OFF SA1 To use a remote on off device an external contactor must be connected to installer terminals 14 and 15 setting para meter CL42 to 1 CL42 1 For time...

Страница 15: ...ambient carriage temperature 50 C 100 C Measuring range 50 C 100 C Materials PA 15 GK Colour RAL 9010 1 2 20 21 BT3 REMOTE KEYPAD KIT A5 Accessory The remote keypad kit can be used to display all unit...

Страница 16: ...4 5 91 COP 1 3 51 3 55 3 13 3 37 3 62 3 62 3 39 3 39 3 57 3 50 Cooling capacity 2 kW 5 77 7 08 8 73 11 5 5 75 7 15 8 81 11 9 13 4 15 7 Power consumption 2 kW 2 16 2 61 3 52 4 26 2 11 2 47 3 24 4 41 4...

Страница 17: ...4 57 5 46 COP 1 3 08 3 02 3 08 3 03 3 08 3 16 3 18 3 04 3 24 3 15 Cooling capacity 2 kW 4 83 5 93 7 33 9 6 4 82 6 03 7 39 10 0 11 2 13 1 Power consumption 2 kW 1 92 2 34 3 19 3 76 1 88 2 22 2 91 3 88...

Страница 18: ...anufactured with operating parameters allowing water produced at the evaporator down to 5 C If needing to produce water down to 10 C contact technical service OPERATION WITH WATER GLYCOL MIX 20 25 30...

Страница 19: ...C KIT 0 10 20 30 40 50 60 70 80 90 100 0 1 2 3 4 5 Pressure drop kPa System heat exchanger pressure drop Water flow rate m3 h 0021 0025 0041 0031 0051 0061 AVAILABLE PRESSURE HEAD UNIT WITH HYDRONIC K...

Страница 20: ...ith built in inverter including water pressure transducer and micro processor to manage the following control modes adjust ment CONSTANT P the pressure differential between pump suction and discharge...

Страница 21: ...with two fans Do not operate in the dashed section of the curves Air flow rate m3 h 300 250 200 150 100 50 0 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100 3200 0011 0021 GRAPH OF FLOW RA...

Страница 22: ...rting the chiller Make sure the switch QF1 is in the OFF position Make sure the contact of the on off device SA1 see the wiring diagram is open if fea tured Close the door of the electrical panel Move...

Страница 23: ...ting Cooling Standby Defrost 1 STATUS AND OPERATING MODE LEDS Compressor Fans System pump Frost protection heater system heat exchanger 3 UTILITY LEDS Clock Degrees centigrade Pressure Bar Menu ABC 2...

Страница 24: ...anaging time bands to control specific events Follow the procedure shown below to set the hours minutes and date To enter menu CL press the set button Once having entered this menu HOUr will be shown...

Страница 25: ...BRA2 BRN2 EN 25 press the set button To exit the clock setting menu press the esc button until returning to the main display...

Страница 26: ...tE28 30 tE56 33 tE84 DHW set point tE29 50 tE57 45 tE85 Hour Minutes hours 17 tE31 17 min 00 tE32 0 hours 17 tE59 17 min 00 tE60 0 tE87 tE88 Operating mode ON Standby ON tE33 0 ON tE61 0 tE89 TIME BAN...

Страница 27: ...ally return to the main display and the Stby LED previously on will now be off and the COOL LED will be on To change the set point starting from the main display press the set button Pressing the set...

Страница 28: ...g the PASS directory from the main display press ing the esc and set buttons together esc set and scrolling to the directory with up down and setting the PASS accesses the parameters visible for the p...

Страница 29: ...ton For parameter CF00 the value displayed will be 2 To change the value of the parameter press the up or down button When having selected the value press the set button To exit the display and return...

Страница 30: ...1 CP01 Scroll using the UP and DOWN buttons until displaying if featured among the resources the operating hours for com pressor 2 CP02 and the operating hours for the pump PU02 Press the set button t...

Страница 31: ...er circuit pump Fans FE FE00 FE30 Fans Electric HI HI00 H15 System heat exchanger electric heater heater dS dS00 dS07 Dynamic set point Ad Ad00 Ad07 Adaptive AF AF00 AF03 Frost protection AL AL00 AL48...

Страница 32: ...lay indication Er 10 Fan circuit breaker tripped Manual reset if active for more than 30 seconds Check correct sequence of power supply phases versions 0071 0121 Display indication Er47 HSW15 communic...

Страница 33: ...op and start Autoreset when the minimum recovery time has elapsed Red LED Condition Action 2 flashes Undervoltage Ue 190VAC Autoreset after 5 minutes 3 flashes Overcurren 80 A for 1 sec Autoreset afte...

Страница 34: ...with pressure reading via pressure sensor controls the fan rotation speed This allows the exchange of heat to be increased and or decreased maintaining condensing or evaporation pressures essential l...

Страница 35: ...e temperature Graph with factory settings Outside air temperature Ds06 Ds02 10 C Ds06 5 C 28 C 33 C Water temperature set point Ds02 15 C Ds04 5 C Parameter Value Unit of measure Description ds00 1 En...

Страница 36: ...values which should be between 5 and 10 C and 4 and 8 C After a couple of hours operation check that the liquid indicator indicates a dry circuit dry green In the event of partial leaks the circuit mu...

Страница 37: ...eplace the component Check Check Check Protection devices trip and shut down the com pressor Excessive discharge pressure Low suction pressure Low voltage Electrical connections not sufficiently tight...

Страница 38: ...low Empty and refill Faulty operation of outside heat exchanger control pressure regulating valves Check High suction pressure greater than 20 bars High utility water inlet temperature Thermostatic ex...

Страница 39: ...n on technical assistance and obtaining spare parts contact CLIMAVENETA S P A AFTER SALES DEPARTMENT RESIDENTIAL BUSINESS Via Duca d Aosta 121 31031 Mignagola di Carbonera TV ITALY Tel 39 0424 509500...

Страница 40: ...COD C01002793C_02...

Отзывы: