background image

8

1.  Please read 

Indoor Unit Installation Requirements

 on page 7 to properly 

identify the best location for wall-mounted installation of the indoor 

unit. While choosing a location for indoor unit, be aware that you 

should leave ample room for a wall hole for the refrigerant piping to 

connect the indoor and outdoor units. Make sure to use a stud finder to 

locate the best place on the wall for mounting. 

2.  Remove mounting plate from the indoor unit and position it on the wall 

so that the screw holes will line up with the studs. Use a level to make 

sure the plate is kept in a horizontal position. 

3.  Secure the mounting plate to the wall by putting at least one screw in 

each corner of the mount. Make sure the mount is level, a slanted wall-

mounting plate might jeopardize the discharge of condensed water. 

4.  Choose location of hole for line set. The recommended position for 

all piping is the right side of the indoor unit (see   in figure 2 below). 

However, the unit can accommodate piping to both the left and right. 

See figure 2 below for different ways piping can be fixed. Figure 3 

provides measurements for hole placement for Rear Outlet and Left 

Rear Outlet configurations. Make sure to use minimum 2.75" hole saw.

 

 

Figure 3: Rear and left rear hole placement measurements

Indoor wall mount

2.5"

2.5"

1.5"

1.5"

2.75"

2.75"

Rear outlet 

(Recommended)

Left Rear 

outlet

Figure 2: Optional line set configurations

(Recommended)

Note: The unit comes with 

knockout side pieces if you 

decide to run the lines out 

the side of the unit.

 

 

 

 

 

2

3

1

 

WARNING: 

Read all safety instructions on page 3 before installing indoor unit. 

Read all indoor installation requirements. It is recommended that 

two people be used for the following installation steps. 

 - Stud Finder

 - Pencil  

 - Drill with Drill Bits

 - Tape Measure 

 - 6 – 2” Wood Screws

 - Step Ladder 

 - Level

 - 2-3/4 hole saw

 -

Wall clamps (optional)

 -

Teflon tape

TOOLS YOU WILL NEED

INSTALLATION OF INDOOR UNIT

 CAUTION 

•  No matter what layout you select make 

sure lines are running downward along the 

entirety of the line set.

•  When drilling hole in the wall for the line 

set, make sure you are not drilling through 

electrical wires or pipes in the wall. 

Содержание easyair CR12000SACH

Страница 1: ...ORE ASSEMBLY AND USE Read and follow all safety rules and instructions before operating this equipment THIS PRODUCT IS INTENDED FOR HOUSEHOLD USE ONLY Please keep this manual for future reference OWNER S MANUAL INSTALLATION GUIDE Install without the need for an HVAC technician Do it y urself easyair ...

Страница 2: ...EMA 5 15 Control Panel Temperature Display Only operates with remote Remote Control Infrared Remote Compressor Rotary Thermostat Digital Refrigerant R410a 800g Line Set is Pre charged Filter Included washable Noise Interior Unit 42 dB Exterior Unit 53 dB Capacity Cooling BTU 12 000 Dehumidification pts hour 1 25 Heating BTU 14 000 heat pump Approximate Max Enclosure Size 500 550 sq ft Well insulat...

Страница 3: ...he plug for this unit is polarized with one blade wider than the other Do not force the plug into an electrical outlet Do not alter the plug in any way If the plug does not fit into the outlet reverse the plug If it still does not fit contact a qualified technician to install a proper outlet Do not use if the power cord is damaged or the connection to the wall outlet is loose Operate product only ...

Страница 4: ... in the affected room It can cool and dehumidify the air completely automatically and also provide heat using a heat pump Air pulled by the fan enters through the grill of the front panel and passes through the filter which traps dust inside Air is then sent to the heat exchanger and is cooled dehumidified or re heated by the heat exchanger Heat removed from the air is then sent outside When the c...

Страница 5: ...nction in SLEEP mode which will automatically adjust the temperature to maximize comfort during night time sleep To put the air conditioner into SLEEP mode press the SLEEP button on the remote until the symbol is pointing to SLEEP on the remote s display If the system is set to run using the cooling or dry modes the set temperature will automatically be raised by 1 degree every 60 minutes for a to...

Страница 6: ...6 REMOTE CONTROLLER BUTTON DIAGRAM Turns off digital display on indoor unit LAMP button Indicates the selected air rate It works on three dimensional air flow model ...

Страница 7: ...it by inserting attaching vibration proof pads between the unit and fittings Avoid leaving items near the outlet and inlet of the outdoor unit These can cause malfunction or increase operation noise Contact ClimateRight Customer Service if you hear irregular sounds during operation Only use a soft dry cloth to wipe the unit clean If the unit is especially dirty you can use a cloth soaked in warm w...

Страница 8: ...ommodate piping to both the left and right See figure 2 below for different ways piping can be fixed Figure 3 provides measurements for hole placement for Rear Outlet and Left Rear Outlet configurations Make sure to use minimum 2 75 hole saw Figure 3 Rear and left rear hole placement measurements Indoor wall mount 2 5 2 5 1 5 1 5 2 75 2 75 Rear outlet Recommended Left Rear outlet Figure 2 Optional...

Страница 9: ...extension to the end of drain hose before operating Wrap the extension connection point firmly with Teflon tape to ensure a good seal and to prevent leaks INCORRECT CORRECT Figure 5 Installation of drain hose 7 Carefully bend the line set downward routing them to either the left or right as needed to connect to the condenser portion of the unit outside 8 Click the 2 round plastic housings around t...

Страница 10: ...e more secure and assist with keeping the unit level EXTREME WEATHER CONSIDERATIONS If the unit is exposed to heavy wind Install unit so that air outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds If the unit is frequently exposed to heavy rain or snow Build a shelter above the unit it to protect it from ...

Страница 11: ...d Gravel or sand under the base can keep the base more secure and assist with keeping the unit level Unit must be 12 away from the wall for proper airflow and servicing 10 WARNING Read all safety instructions on page 3 before installing outdoor unit Read all outdoor installation requirements DO NOT DO NOT install near an obstacle that will block air inlets and outlets DO NOT install near a public ...

Страница 12: ... unit current 6 If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1 8in 3mm must be incorporated in the fixed wiring Use an approved circuit breaker or switch 7 Only connect the unit to an individual branch circuit outlet Do no connect another appliance to that outlet 8 Make sure to properly ground the air conditione...

Страница 13: ...lide the spade connector on the end of the black L1 wire into the L1 terminal and tighten Then slide the spade connector on the end of the white L2 wire into the L2 terminal and tighten 16 Route utility power cord and line set power cord through the strain relief and tighten with screw removed in Step 18 17 Reinstall panel on unit and tighten screw FINISH INSTALLATION 18 Once the condenser is secu...

Страница 14: ...m remote controller 5 Cover both indoor and outdoor units to prevent dust buildup PRE SEASON INSPECTION 1 Check for damaged wires 2 Clean air filters 3 Check for leaks 4 Replace batteries in the remote controller 5 Make sure nothing is blocking all air inlets and outlets TROUBLESHOOTING WARNING If ANY of the following conditions occurs turn off your unit immediately The power cord is damaged or ab...

Страница 15: ...nd during operation This is normal and is caused by refrigerant gas flowing through both indoor and outdoor units Low hissing sound when the system starts has just stopped running or is defrosting This noise is normal and is caused by the refrigerant gas stopping or changing direction Squeaking sound Normal expansion and contraction of plastic and metal parts caused by temperature changes during o...

Страница 16: ...ods winds fires lightning accidents corrosive environments rust etc or other conditions beyond the control of the Company 6 Parts not supplied or designated by Company or damages resulting from their use 7 Products installed outside USA and Canada 8 Electricity or fuel costs or increases in electricity or fuel costs from any reason whatsoever including additional or unusual use of supplemental ele...

Страница 17: ..._________________________________________ Date of Purchase___________________________________ Date of Installation__________________________________ Owners Name______________________________________ Address of Installation_______________________________ _______________________________ Installing Contractor_________________________________ Address_________________________________________ Phone No E...

Отзывы: