62
G e o t h e r m a l H e a t i n g a n d Co o l i n g
Trilogy
®
Variable
(VE) Series IOM - 60Hz HFC-410A
R e v i s i o n D a t e : 2 2 D e c e m b e r, 2 0 2 1
Code
Fault
Mode
Possible Cause
Solution
76
Low Voltage Shutdown
Mitsubishi Inverter 0930
ALL
Under voltage
Check power supply and 24Vac before and during operation
ALL
Check power supply wires
ALL
Check 24Vac transformer tap for correct power supply voltage
Carel Inverter 1860
ALL
Input power supply phase loss,
three-phase power supply
unbalance
Check the input power supply phases to the drive, reduce motor
power (speed).
ALL
Motor cable disconnected
Check the connections of the motor cable.
ALL
The drive has detected a
ground current too high
Check ground insulation of the motor and wires.
ALL
• It indicates a small earth fault
on the motor
• The current measurement
chain (sensors, op amps,
shunts, ..) is damaged
Check tightness/wiring of the inverter/compressor cables. If properly
wired, then permanent damage to the motor.
ALL
Excessive external load (e.g.
fans) connected to the DCbus
Check external loads conneted to the DCbus terminal; especially
when the external load starts.
ALL
Excessive external load (e.g.
fans) connected to the DCbus
Check external loads conneted to the DCbus terminal; especially
when the external load starts.
ALL
Incompatibility between
compressor uSafety
parameters that characterize
the inverter as a PEC and the
inverter size
Check that the compressor uSafety parameters are adequate. Check
the compressor-inverter combination. Inverter probably too small.
77
Low Leaving Air temp
ALL
Low EAT
Bring EAT into range
ALL
Check unit capacity
Run mode to check unit capacity
ALL
Bad thermistor
Check temp vs. resistance curve per calculator
ALL
Incorrect airflow
Check airflow and reduce if nessesary.
ALL
Improperly installed airflow
sensor
Check installation
78
High Leaving Air temp
ALL
High SAT
Bring SAT into range
ALL
Low airflow
Increase airflow
ALL
Bad thermistor
Check temp vs. resistance curve per calculator
ALL
Improperly installed airflow
sensor
Check installation
79
Low Subcooling
ALL
Low charge
Check unit capacity in mode check
80
ECM Blower Motor Fault
ALL
High level fault condition
See low level faults (81-86)
81
ECM Lost Rotor Fault
ALL
Check blower assembly
Blower wheel set screw loose
ALL
Check blower assembly
Blower wheel dragging
ALL
Check blower assembly
Blower wheel locked
82
ECM Current Trip Fault
ALL
Low input voltage
Check input voltage
ALL
Bad ECM
Replace motor
83
ECM temp Limit Fault
ALL
High ambient motor temp
Reduce cabinet temp
ALL
Dirty motor housing
Clean motor
84
ECM Locked Rotor Fault
ALL
Debris in blower assembly
Check blower and clean assembly
ALL
Blower wheel draging
Check blower assembly
ALL
Bad motor bearing
Replace motor
85
ECM Over Voltage Fault
ALL
High input voltage
Check input voltage
ALL
Bad ECM
If nothing is found from other solutions, replace motor