System Configuration (Cont.)
Loop Configuration
Configures the internal vFlow device to the application. The vFlow device will adjust the flow to maintain the selected
temperature difference (Delta T) between the entering and leaving water for the active operating mode.
System Setting
Description
Range/Options
Default
Loop Configuration
Selects the type of internal flow device.
None,
Variable Speed Pump,
Modulating Valve
Variable Speed
Pump
Loop Option
Configures the application for the loop.
Single system (one
unit, one loop),
Parallel system
(multiple units, one
common loop, parallel
pumping)
Single system
Heating Delta T
Sets the source water flow rate for the heating mode. The variable speed pump
or motorized valve will adjust the source water flow to maintain the selected
temperature difference between the entering and leaving source water during
the heating mode.
5.0°F to 12.0°F
6.0°F
Cooling Delta T
Sets the source water flow rate for the cooling mode. The variable speed pump
or motorized valve will adjust the source water flow to maintain the selected
temperature difference between the entering and leaving source water during
the cooling mode.
9.0°F to 20.0°F
10.0°F
Option Configuration
System Setting
Description
Range/Options
Default
Compressor ASCD
(Anti-Short Cycle Delay)
Configures the minimum amount of time the compressor will remain off
between cycles.
5 to 8 minutes
5 minutes
Over/Under Voltage
Detection
Configure the over/under voltage detection.
Enabled, Disabled
Enabled
Source Antifreeze
(if applicable)
Configures the low temperature protection setting for the source water heat
exchanger.
No - 30°F,
Yes - 10°F
No - 30°F
Over/Under Voltage condition exists when the control voltage is outside the range of 18VAC to 31.5VAC.