Code
Fault
Mode
Possible Cause
Solution
98
Loop Flow w/o Loop Pump
Warning
OFF
Loop pump check valve stuck
open
Remove internal check valve and clean. System should also be
flushed using a 100 mesh strainer to remove particles from system.
99
Excessive Transition Mode
Operation
ANY
Stuck Reversing Valve
Run system in service mode to verify operation or perform magnet
test.
ANY
Bad Compressor
Check compressor operation.
100
Low Loop Pressure Warning
ANY
Low Loop Pressure
Check loop pressure
ANY
Bad Pressure (DPD) Sensor
Check sensor
ANY
Improperly installed (DPD)
sensor
Remove sensor and reinstall
Table 16: Troubleshooting (Cont.)