The applications are too varied to describe in this 
document, however some basic guidelines will be 
presented. All plumbing should conform to local codes 
and consider the following:

Wide temperature variation applications such as 
heating/cooling coils 
-  Employ piping materials that are rated for the 

maximum temperature and pressure combination.  
This excludes PVC for most heating applications.

-  Insure load water fl ow in high temperature heating 

applications is at least 3.2 l/m per kW to improve 
performance and reduce nuisance high pressure 
faults.

-  DO NOT employ plastic to metal threaded joints
-  Utilize a pressure tank and air separator vent system 

to equalize pressure and remove air.

Swimming Pool Hot Tub Applications

-  Recommended application includes a brazed plate 

heat exchanger to isolate pool water from the unit 
heat exchanger. 

Potable Water Applications

-  Insure load water fl ow in high temperature heating 

applications is at least 3.2 l/m per kW to improve 
performance and reduce nuisance high pressure 
faults.

-   A secondary heat exchanger must always be used 

between the water-to-water heat pump and potable 
water tank. Either an indirect water heat or brazed 
plate heat exchanger (with a secondary pump) will 
isolate the potable water from the heating water. 

Load Plumbing Installation

Installation

THW Unit Location

These units are not designed for outdoor installation.  
Locate the unit in an INDOOR area that allows 
enough space for service personnel to perform typical 
maintenance or repairs.

The installation of water source heat pump units and all 
associated components, parts and accessories which 
make up the installation shall be in accordance with 
the regulations of ALL authorities having jurisdiction 
and MUST conform to all applicable codes. It is the 
responsibility of the Installing Contractor to determine 
and comply with ALL applicable codes and regulations.
Locate the unit in an indoor area that allows easy 
removal of access panels, and has enough space for 
service personnel to perform maintenance or repair. 
Provide suffi cient room to make water and electrical 
connections. Any access panel screws that would be 
diffi cult to remove after the unit is installed should be 
removed prior to setting the unit. These units are not 
approved for outdoor installation and, therefore, must 
be installed inside the structure being conditioned. 
Do not locate in areas where ambient conditions are 
not maintained within 4-38°C and up to 75% relative 
humidity.

/RDG+;
EU]SOW

,1

287

287
+7*

'+:

0

'+:

,1

+7*

7R

'+:

6WRUDJH

7DQN

Load Piping Connections

Load piping connections are designated ‘Load Water In 
and Out’ for the radiant heating system piping, and ‘DHW 
Water In and Out’ (optional) for connection to the domestic 
hot water piping.  Any unused piping connections on the 
load side of the THW unit will allow spillage of the load 
circuit fl uid, as the radiant and DHW circuits are connected 
internally.

If a unit is ordered with the DHW option and is not being 
connected to a radiant heating system, the ‘Load Water 
In and Out’ (radiant heating circuit) connections must be 
connected to the ‘DHW In and Out’ piping using tees as 
shown in Figure 1a.  Failure to do so will lead to nuisance 
high-pressure faults.

THW Unit Load Plumbing

Figure 1a: THW DHW Only Piping

Содержание Tranquility THW Series

Страница 1: ...Load Plumbing Installation 7 Ground Water Heat Pump Application 9 Water Quality Standards 10 Ground Loop Heat Pump Application 11 Electrical Line Voltage 13 Electrical Low Voltage 15 Electrical Contro...

Страница 2: ...CLIMATEMAS TE R WATE R S OURCE H E A T P UMP S 2 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 This Page Intentionally Left Blank...

Страница 3: ...requirements WARNING All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION Technicians must follow industry accepted guidelines and all local state and federal statutes for th...

Страница 4: ...an up Examine all pipes fittings and valves before installing any of the system components Remove any dirt or trash found in or on these components Pre Installation Installation Operation and Maintena...

Страница 5: ...utdoor Source Water Connection Size FPT in 1 1 1 Domestic Hot Water Connection Size FPT in 1 1 1 Weight Operating kg 207 207 234 Weight Packaged kg 214 214 241 Dual isolation compressor mounting Balan...

Страница 6: ...should take care to comply with all building codes and allow adequate clearance for future field service Model Overall Cabinet Water Connections Electric Access Plugs 1 2 3 4 5 6 A Depth B Width C He...

Страница 7: ...r service personnel to perform typical maintenance or repairs The installation of water source heat pump units and all associated components parts and accessories which make up the installation shall...

Страница 8: ...U 7 XQLWV RQ ORDG DQG VRXUFH FRQQHFWLRQV 2WKHU FRPSRQHQWV DGGLWLRQDO EDOO YDOYHV XQLRQV HWF PD EH UHTXLUHG IRU HDVH RI VHUYLFH 7KLV GUDZLQJ VKRZV RQO PLQLPXP UHTXLUHPHQWV RXU VSHFLILF LQVWDOODWLRQ ZLO...

Страница 9: ...codes i e recharge well storm sewer drain field adjacent stream or pond etc Most local codes forbid the use of sanitary sewer for disposal Consult your local building and zoning department to assure c...

Страница 10: ...tered for maximum 841 micron 0 84 mm 20 mesh size Any particulate that is not removed can potentially clog components Notes Rev 3 22 2012 15 Application not recommended 1R GHVLJQ 0D LPXP ORVHG 5HFLUFX...

Страница 11: ...rom a garden hose through flush cart before using flush cart pump to ensure an even fill Once full do not allow the water level in the flush cart tank to drop below the pump inlet line or air can be p...

Страница 12: ...your area Freeze protection should be maintained to 9 4 C below the lowest expected entering loop temperature All alcohols should be premixed and pumped from a reservoir outside of the building when...

Страница 13: ...al Line Voltage WARNING To avoid possible injury or death due to electrical shock open the power supply disconnect switch and secure it in an open position during installation Model Voltage Code Volta...

Страница 14: ...A T P UMP S 14 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Electrical Line Voltage Field Low Voltage Wiring Field Line Voltage Wiring Figu...

Страница 15: ...iagram for details Low Water Temperature Cutout FP1 The CXM DXM control allows the field selection of source fluid low temperature cutout points The factory setting of FP1 is set for water 1 1 C In co...

Страница 16: ...boards Remove the yellow wire from the CXM board and connect it to terminal 2 on the valve Add a new wire from terminal 3 to the Y terminal at the CXM board and a jumper wire from terminal 1 to termi...

Страница 17: ...ble controller as outlined above is the ability to integrate complex decision making tasks with the standard heat pump CXM controls and communicate with a user interface Below is a list of standard fe...

Страница 18: ...OAT at which maximum setpoint MaxBT reduction will occur The valid range for building balance point is 10 21 C with a default value of 16 C The minimum design water temperature is the minimum desired...

Страница 19: ...t is connected to the water to air unit forced air heating may be used for the shoulder seasons allowing quick heating to cooling changeover If this feature is used the consumer will easily be able to...

Страница 20: ...TEMPERATURE OFFSETS PROGRAM SETTINGS DAYLIGHT SAVINGS SET MONTH DAY YR HR MIN VACATION HOLD DATE THEN TIME SECURITY LOCKOUT TEMP ADJUST LOCKOUT TOTAL KEYPAD LOCKOUT SCREEN SETTINGS PROGRAM SCREEN SERV...

Страница 21: ...vised 02 Ja nuary 20 13 INSTALLER MENU BUFFER TANK SETPOINT INPUT DEALER INFORMATION BUFFER TANK DEADBAND OUTDOOR TEMPERATURE RESET RESTORE DEFAULTS MANUAL OPERATION HOT WATER DEADBAND OUTDOOR DESIGN...

Страница 22: ...umps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Electrical Wiring Diagram Matrix Model Diagram Number Voltage Option THW008 010 96B0108N01 220 50 1 THW008 010 96B0108N02 220 50...

Страница 23: ...TH E S MAR T SOLU T I ON FOR E N E RG Y E FFI CIENCY 23 climatemaster com Tra nquil it y Wa ter t o Wa ter T HW Series Revised 02 Ja nuary 20 13 Typical Wiring Diagram THW 220 50 1 Units...

Страница 24: ...CLIMATEMAS TE R WATE R S OURCE H E A T P UMP S 24 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Typical Wiring Diagram THW 220 50 1 Units...

Страница 25: ...TH E S MAR T SOLU T I ON FOR E N E RG Y E FFI CIENCY 25 climatemaster com Tra nquil it y Wa ter t o Wa ter T HW Series Revised 02 Ja nuary 20 13 Typical Wiring Diagram THW 220 50 1 Units with VSFP...

Страница 26: ...MATEMAS TE R WATE R S OURCE H E A T P UMP S 26 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Typical Wiring Diagram THW 220 50 1 Units with V...

Страница 27: ...TH E S MAR T SOLU T I ON FOR E N E RG Y E FFI CIENCY 27 climatemaster com Tra nquil it y Wa ter t o Wa ter T HW Series Revised 02 Ja nuary 20 13 Typical Wiring Diagram THW 220 50 3 Units...

Страница 28: ...CLIMATEMAS TE R WATE R S OURCE H E A T P UMP S 28 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Typical Wiring Diagram THW 220 50 3 Units...

Страница 29: ...TH E S MAR T SOLU T I ON FOR E N E RG Y E FFI CIENCY 29 climatemaster com Tra nquil it y Wa ter t o Wa ter T HW Series Revised 02 Ja nuary 20 13 Typical Wiring Diagram THW 220 50 3 Units...

Страница 30: ...CLIMATEMAS TE R WATE R S OURCE H E A T P UMP S 30 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Typical Wiring Diagram THW 220 50 3 Units...

Страница 31: ...he control is attempting a retry of a fault the status LED will slow flash slow flash one flash every 2 seconds to indicate the control is in the process of retrying Field Configuration Options Note I...

Страница 32: ...he low pressure switch input is bypassed for the initial 120 seconds of a compressor run cycle Low pressure lockout code 3 Water coil low temperature FP1 The FP1 thermistor temperature must be below t...

Страница 33: ...mperature range and with flow rates of between 1 6 to 3 2 L M Per kW however usually no more than one of these factors may be at a minimum or maximum level at a time The commissioning table indicates...

Страница 34: ...oper range and also verify heating and cooling setpoints for proper operation System pH System water pH is 6 8 5 Proper pH promotes longevity of hoses and fittings System Flushing Water used in the sy...

Страница 35: ...r without satisfying the Y input call then the control will go to Lockout mode The last fault causing the lockout will be stored in memory and can be viewed by going into test mode Consult the CXM AOM...

Страница 36: ...y These dirty installations are a result of the deterioration of iron or galvanized piping or components in the system or open cooling towers requiring heavy chemical treatment and mineral buildup thr...

Страница 37: ...cts damage or insuf cient performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any incr...

Страница 38: ...r information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products ClimateMas...

Отзывы: