background image

R e s i d e n t i a l   Tr a n q u i l i t y

®

  2 7   S p l i t   ( T T S )   -   6 0 H z   H F C - 4 1 0 A

R e v. :   8   M a y,   2 0 1 4 C

c l i m a t e m a s t e r. c o m

41

General

If operational di

  culties are encountered, perform 

the preliminary checks below before referring to the 
troubleshooting charts.
• Verify that the unit is receiving electrical supply power.
• Make sure the fuses in the fused disconnect switches 

are intact.

After completing the preliminary checks described above, 
inspect for other obvious problems such as leaking 
connections, broken or disconnected wires, etc. If everything 
appears to be in order, but the unit still fails to operate 
properly, refer to the “CXM Troubleshooting Process 
Flowchart” or “Functional Troubleshooting Chart.”

CXM Board

CXM board troubleshooting in general is best summarized 
as simply verifying inputs and outputs. After inputs and 
outputs have been veri

fi

 ed, board operation is con

fi

 rmed and 

the problem must be elsewhere. Below are some general 
guidelines for troubleshooting the CXM control.

Field Inputs

All inputs are 24VAC from the thermostat and can be veri

fi

 ed 

using a volt meter between C and Y, G, O, W. 24VAC will be 
present at the terminal (for example, between “Y” and “C”) if 
the thermostat is sending an input to the CXM board.

Sensor Inputs

All sensor inputs are ‘paired wires’ connecting each component 
to the board. Therefore, continuity on pressure switches, for 
example can be checked at the board connector.

The thermistor resistance should be measured with the 
connector removed so that only the impedance of the 
thermistor is measured. If desired, this reading can be 
compared to the thermistor resistance chart shown in 
the CXM AOM manual. An ice bath can be used to check 
calibration of the thermistor.

Outputs

The compressor relay is 24VAC and can be veri

fi

 ed using a 

voltmeter. The fan signal is passed through the board to the 
external fan relay (units with PSC motors only). The alarm 
relay can either be 24VAC as shipped or dry contacts for use 
with DDC controls by clipping the JW1 jumper. Electric heat 
outputs are 24VDC “ground sinking” and require a volt meter 
set for DC to verify operation. The terminal marked “24VDC” 
is the 24VDC supply to the electric heat board; terminal “EH1” 
is stage 1 electric heat; terminal “EH2” is stage 2 electric heat. 
When electric heat is energized (thermostat is sending a “W” 
input to the CXM controller), there will be 24VDC between 
terminal “24VDC” and “EH1” (stage 1 electric heat) and/or 
“EH2” (stage 2 electric heat). A reading of 0VDC between 
“24VDC” and “EH1” or “EH2” will indicate that the CXM board 
is NOT sending an output signal to the electric heat board.

Test Mode

Test mode can be entered for 20 minutes by shorting the test 
pins (see Figure 29).  The CXM board will automatically exit 
test mode after 20 minutes.

CXM Troubleshooting Process Flowchart/Functional 
Troubleshooting Chart

The “CXM Troubleshooting Process Flowchart” is a quick 
overview of how to start diagnosing a suspected problem, 
using the fault recognition features of the CXM board.  The 
“Functional Troubleshooting Chart” on the following page is 
a more comprehensive method for identifying a number of 
malfunctions that may occur, and is not limited to just the 
CXM controls. Within the chart are 

fi

 ve columns:

• The “Fault” column describes the symptoms.  
• Columns 2 and 3 identify in which mode the fault is likely 

to occur, heating or cooling.

• The “Possible Cause column” identi

fi

 es the most likely 

sources of the problem.

• The “Solution” column describes what should be done to 

correct the problem. 

WARNING!

  HAZARDOUS VOLTAGE! DISCONNECT 

ALL ELECTRIC POWER INCLUDING REMOTE 
DISCONNECTS BEFORE SERVICING.
Failure to disconnect power before servicing can cause 
severe personal injury or death.

Troubleshooting

 

WARNING! 

Содержание Tranquility 27

Страница 1: ...eat Pump Applications 12 13 Water Quality Standards 14 Lineset Information 18 Refrigeration Installation 15 22 Hot Water Generator 23 25 Electrical Line Voltage 26 Power Connection 26 Electrical HWG W...

Страница 2: ...This page was intentionally left blank...

Страница 3: ...detailed information Future C 0 2 6 C G 0 1 C N N 4 5 6 7 8 9 10 11 12 13 14 026 038 049 064 Unit Size Voltage C CXM Controls C Current revision for 026 064 Revision Level Heat Exchanger Options Cabin...

Страница 4: ...practice which if not avoided could result in minor or moderate injury or product or property damage NOTICE Notification of installation operation or maintenance information which is important but whi...

Страница 5: ...s stored on the job site In areas where painting plastering and or spraying has not been completed all due precautions must be taken to avoid physical damage to the units and contamination by foreign...

Страница 6: ...plit system heat pumps are rated in the AHRI directory with a specific indoor coil match Tranquility 27 Splits are AHRI rated and listed with Tranquility TAH air handlers and TAC cased coils Other bra...

Страница 7: ...ominal tons are at AHRI ISO 13256 1 GLHP conditions Two stage units may be operated in single stage mode if desired where smaller capacity is required For example a model 026 may be used as a 1 1 2 to...

Страница 8: ...3 0 25 35 39 42 32 36 28 29 32 33 26 28 29 22 23 23 1400 80 67 54 73 59 46 64 49 38 54 39 32 43 28 27 0 27 28 43 47 35 39 43 32 36 37 28 32 32 24 26 27 750 61 49 39 55 43 33 48 37 27 41 29 20 33 21 17...

Страница 9: ...y access panel screws that would be di cult to remove after the unit is installed should be removed prior to setting the unit Refer to Figure 2 for an illustration of a typical installation Refer to P...

Страница 10: ...to insure an even fill 2 Once full the flushing process can begin Do not allow the water level in the flush cart tank to drop below the pump inlet line to avoid air being pumped back out to the earth...

Страница 11: ...Water Temperature Cutout Selection in this manual Note Low water temperature operation requires extended range equipment Table 3 Antifreeze Percentages by Volume Table 2 Approximate Fluid Volume U S g...

Страница 12: ...er type expansion tank to minimize mineral formation due to air exposure The expansion tank should be sized to provide at least one minute continuous run time of the pump using its drawdown capacity r...

Страница 13: ...to avoid freeze damage to the unit See Low Water Temperature Cutout Selection in this manual for details on the low limit setting Figure 8 Water Well Connections Ground Water Heat Pump Applications Pr...

Страница 14: ...pm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate Size and Erosion All 10 ppm of particles and a...

Страница 15: ...o minimize transmission of line set vibration to the structure Installing the Lineset at the Compressor Section Braze the line set to the service valve stubs as shown in Figure 9 Remove the schraeder...

Страница 16: ...its charged with HFC 410A refrigerant Residual mineral oil can act as an insulator on the wall of the coil tubing hindering proper heat transfer and thus reducing system e ciency and capacity Another...

Страница 17: ...existing compressor section If the unit is operational follow steps F L F First start the existing R 22 system in the cooling mode and close the liquid line valve G Completely pump all existing R 22 r...

Страница 18: ...e liquid and vapor valves Use the liquid valve on the cylinder in this case keeping the cylinder upright 14 Once the liquid refrigerant has been completely recovered switch the recovery machine to vap...

Страница 19: ...ports Add the required refrigerant so that the total charge calculated for the unit and line set is now in the system Open the service valve fully counter clockwise so that the stem will backseat and...

Страница 20: ...50 F 14 F Superheat Determining Sub Cooling 1 Measure the temperature of the liquid line on the smaller refrigerant line liquid line just outside of the cabinet This location will be adequate for meas...

Страница 21: ...ection PVC Condensate with vented trap Air pad or Extruded polystyrene Air Temperature Limit Switch Figure 11b Typical Split Add on Coil Fossil Fuel Furnace Installation Figure 11a Typical Split Air H...

Страница 22: ...system is ready for charging If the system meets the requirements in Figure 12 it is ready for charging Figure 12 Evacuation Graph Charging The System There are two methods of charging a refrigerant s...

Страница 23: ...storage from the HWG For example consider the amount of heat that can be generated by the HWG when using the 125 F set point versus the amount of heat that can be generated by the HWG when using the...

Страница 24: ...SIBLY SET BELOW 150 F THE 150 F HWG SETPOINT MUST ONLY BE USED ON SYSTEMS THAT EMPLOY AN APPROVED ANTI SCALD VALVE PART NUMBER AVAS4 AT THE HOT WATER STORAGE TANK WITH SUCH VALVE PROPERLY SET TO CONTR...

Страница 25: ...ent at the high point of the HWG piping system 2 Insulate all HWG water piping with no less than 3 8 10mm wall closed cell insulation 3 Open both shut o valves and make sure the tank drain valve is cl...

Страница 26: ...18 Consult Table 9 for correct fuse size 208 230 Volt Operation Verify transformer tap with air handler wiring diagram to insure that the transformer tap is set to the correct voltage 208V or 230V WA...

Страница 27: ...mperature Cutout Selection The CXM control allows the field selection of low water or water antifreeze solution temperature limit by clipping jumper JW3 which changes the sensing temperature associate...

Страница 28: ...R e s i d e n t i a l Tr a n q u i l i t y 27 Split TTS 60Hz HFC 410A R ev 8 May 2014C 28 Geothermal Heating and Cooling Electrical LowVoltage Wiring Figure 22b TTS Low Voltage Field Wiring...

Страница 29: ...should be designed with two parallel valves for ground water applications to limit water use during first stage operation For example at 1 5 gpm ton 2 0 l m per kW a model 049 unit requires 6 gpm 23...

Страница 30: ...plate Mark the position of the back plate mounting holes and drill holes with a 3 16 5mm bit Install supplied anchors and secure plate to the wall Thermostat wire must be 18 AWG wire Wire the appropr...

Страница 31: ...M Board Compressor Section O Y Y2 G R C L AL1 Optional Jumper Y O G R C Y1 O G R C W1 W2 W E Typical Air Handler Typical T stat CXM Board Compressor Section O G R C L AL1 Y2 Y1 Y Y2 From Compressor So...

Страница 32: ...owing field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field selection to disable the...

Страница 33: ...t is bypassed for the initial 120 seconds of a compressor run cycle FP1 is set at the factory for one try Therefore the control will go into lockout mode once the FP1 fault has occurred FP1 lockout co...

Страница 34: ...40 15 66 150 8 2 01 3 26 6 38 11 67 152 6 1 94 2 28 4 36 18 68 154 4 1 88 1 30 2 34 37 69 156 2 1 81 0 32 0 32 65 70 158 0 1 75 1 33 8 31 03 71 159 8 1 69 2 35 6 29 50 72 161 6 1 64 3 37 4 28 05 73 16...

Страница 35: ...the other two factors should be at normal levels to insure proper unit operation Extreme variations in temperature and humidity and or corrosive water or air will adversely a ect unit performance reli...

Страница 36: ...ith an HWG before completing the following steps 2 Turn the thermostat fan position to ON Blower should start 3 Balance air flow at registers 4 Adjust all valves to their full open position Turn on th...

Страница 37: ...warm air delivery within a few minutes after the unit has begun to operate d Refer to Table 15 Check the temperature of both entering and leaving water If temperature is within range proceed with the...

Страница 38: ...28 90 3 4 5 6 138 148 138 148 138 148 138 148 138 148 138 148 11 16 11 16 11 16 18 23 16 21 15 20 16 5 18 5 13 6 15 6 10 7 12 7 16 22 16 22 16 22 110 3 4 5 6 142 152 142 152 142 152 480 500 465 485 45...

Страница 39: ...2 132 124 134 339 359 341 361 344 364 27 32 27 32 27 32 3 8 3 8 3 8 13 6 15 6 10 1 12 1 6 5 8 5 25 31 25 31 25 31 90 6 9 12 132 142 130 140 129 139 419 439 396 419 374 394 15 20 15 20 15 20 15 20 12 1...

Страница 40: ...desuperheater will tend to scale even quicker than the water coil and may need more frequent inspections In areas with extremely hard water a HWG is not recommended Filters Filters must be clean to ob...

Страница 41: ...be verified using a voltmeter The fan signal is passed through the board to the external fan relay units with PSC motors only The alarm relay can either be 24VAC as shipped or dry contacts for use wi...

Страница 42: ...oubleshooting for further help Check Main power see power problems Check fault LED code on control board Yes No No No No No Yes No Yes See HP Fault See LP LOC Fault See FP1 Fault See FP2 Fault See Con...

Страница 43: ...e applications will require 30 F 1 C only X X Bad thermistor Check temp and impedance correlation per chart Condensate Fault Code 6 X X Blocked drain Check for blockage and clean drain X X Improper tr...

Страница 44: ...und moisture X Air temperature out of range in heating Bring return air temperature within design parameters X Scaling in water heat exchanger Perform scaling check and clean if necessary X X Unit ove...

Страница 45: ...68 7 21 22 1 1 6 6 2 2035 6625 6 5 68 7 21 7 1 1 6 6 36 6 7 36 6 7 5 2 48 1 7 1 3 16 21 9 9 22 1 3 16 21 9 9 5 2 48 1 7 1 3 16 21 9 9 22 1 3 16 21 9 9 36 6 7 36 6 7 5 1 5 6 7 21 2035 6625 6 7 21 5 1...

Страница 46: ...LUFXLW E XQTXDOL HG SHUVRQQHO 0ROG IXQJXV RU EDFWHULD GDPDJHV RUURVLRQ RU DEUDVLRQ RI WKH SURGXFW 3URGXFWV VXSSOLHG E RWKHUV 3URGXFWV ZKLFK KDYH EHHQ RSHUDWHG LQ D PDQQHU FRQWUDU WR 0 V SULQWHG LQVWUX...

Страница 47: ...R e s i d e n t i a l Tr a n q u i l i t y 27 Split TTS 60Hz HFC 410A Rev 8 M ay 2 0 1 4 C climatemaster com 47 Notes...

Страница 48: ...ning the manufacture of ClimateMaster s products is ISO 9001 2008 certified ClimateMaster Inc 2009 97B0047N02 Rev 08 May 2014C ISO 9001 2008 Certified Quality First Always 7300 S W 44th Street Oklahom...

Отзывы: