ClimateMaster THW Series Скачать руководство пользователя страница 18

Tranquility THW - 50 & 60Hz R410A - ClimateMaster Geothermal Heat Pumps - Rev.: 30 June, 2008B

18

Warm weather shutdown (WWSD):

  Radiant floor systems 

are the most comfortable type of heating available today.  
However, they do have one disadvantage – quickly 
switching from heating to cooling is not possible due to the 
mass heat storage in the slab.  For example, in the spring 
or fall, there could be times where heating is required 
at night, but cooling is required during the day.  With a 

warm floor, the cooling system has to work much harder 

to cool the space.  WWSD shuts down the water-to-water 
heat pump at a pre-determined outdoor air temperature 
(adjustable at the user interface).  When a water-to-air heat 
pump is used for space cooling, this unit can be enabled 
when WWSD is activate, allowing the water-to-air heat 
pump to heat via forced air during the shoulder seasons, 
avoiding the warm slab/cooling dilemma (see cooling 
enable, below).  A normally closed contact is provided in 
the THW unit to de-energize the heating system controls 

(e.g. radiant floor control panel) during WWSD.  WWSD 

does not affect DHW heating.  In other words, the water-to-
water unit can still operate for generating DHW, even if the 

heating distribution (e.g. radiant floor) system is disabled.  

The WWSD activation (i.e. when the WWSD feature 
is enabled) outdoor air temperature range is 40-100°F 
[4-38°C] with a default value of 70°F [21°C].  The 
WWSD deactivation (i.e. when the radiant heating 
returns to operating mode) temperature range is 35-
95°F [2-35°C] with a default value of 65°F [18°C] and a 
minimum difference between activation and deactivation 
temperatures of 5°F [3°C].  If the outdoor air temperature 
(OAT) rises above the activation temperature, the cooling 
enable signal (see below) is enabled, and the control no 
longer controls the buffer tank temperature.  If the OAT falls 
below the deactivation temperature, the control resumes 
monitoring the buffer tank temperature.

Cooling enable:  Cooling enable is tied to the WWSD 
feature.  If desired, the water-to-air unit controls can be 
wired to the THW unit controls, which will allow the water-
to-air unit to operate during WWSD, but will disable the 
water-to-air unit when the THW unit is not in WWSD mode.  
When a heat pump thermostat is connected to the water-
to-air unit, forced air heating may be used for the shoulder 
seasons, allowing quick heating to cooling changeover.  If 
this feature is used, the consumer will easily be able to 
tell when WWSD is enabled because the water-to-air unit 
thermostat will only be active during WWSD.  Otherwise, 
the water-to-air unit thermostat will be disabled, indicating 
that the consumer should utilize the hydronic heating (e.g. 

radiant floor) thermostat.

Second stage heating (backup boiler):  Optimal heat 
pump sizing may not include a water-to-water heat pump 
that can handle 100% of the heating load.  When a 
backup boiler is used to supplement the heating capacity, 
a 24VAC output from the THW unit can energize the 
boiler.  The boiler control box simply needs a relay that 
can be used to interface with the THW unit.

DHW priority:  By default, DHW heating always takes 
priority over space heating.  Normally, the hot water load 

will be satisfied quickly, and the unit can then switch back 

to space heating.  

Time schedule:  DHW temperatures may be adjusted  
during occupied/unoccupied times via the user interface 
to save energy costs. 

Vacation mode:  DHW generation may be disabled 
when the user interface is placed in vacation mode.  A 
return date and time may be set to restore normal DHW 
temperatures.  

Emergency DHW generation:  If the THW unit is locked 
out, a 24VAC signal can be sent to a contactor at the water 
heater to allow the operation of the electric elements and 
associated thermostat.

Enhanced heat pump lockouts:  Like any ClimateMaster 
unit, the CXM board locks out the compressor any 
time a lockout condition occurs.  The MPC reads the 
lockouts from the CXM, and reports the condition to the 
user interface.  The user interface changes from a blue 
backlight to a red backlight, indicating a lockout.  The 
actual lockout is reported (e.g. High Pressure) at the 
interface.  In addition to the standard CXM faults, the 
MPC checks for bad thermistors and high compressor 
discharge temperature, which are also reported at the 
user interface.

Pump control:  If the optional load and source pump(s) 
are selected, the control energizes the pumps any time 
the compressor is operating.

Variable speed floor pump (VSFP) output:

  Some radiant 

floor systems utilize a variable speed pump on the floor 

system, which changes flow based upon the number 

of zones open or closed. Since the pump has built-in 
controls, only a power supply is needed. An optional 
power terminal is available for VSFP applications. 

ELECTRICAL - CONTROLS

Содержание THW Series

Страница 1: ...Data 4 Dimensional Data 5 Installation 6 Load Plumbing Installation 7 Ground Water Heat Pump Application 8 Water Quality Standards 9 Ground Loop Heat Pump Application 10 Electrical Power Wiring 13 El...

Страница 2: ...or serious injury DANGER labels on unit access panels must be observed WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicate...

Страница 3: ...all pipes fittings and valves before installing any of the system components Remove any dirt or trash found in or on these components Pre Installation Installation Operation and Maintenance instructio...

Страница 4: ...Connection Size IPT in 1 1 1 Maximum Working Pressure Water Side Base Unit PSIG kPa 500 3445 500 3445 500 3445 DHW Option PSIG kPa 500 3445 500 3445 500 3445 Internal Source Pump w Expansion Tank PSIG...

Страница 5: ...3cm Model Overall Cabinet Water Connections Electric Access Plugs 1 2 3 4 5 6 A Depth B Width C Height D Source Outdoor Water In E Source Outdoor Water Out F Load Indoor Water In G Load Indoor Water...

Страница 6: ...erature and pressure combination This excludes PVC for most heating applications Insure load water flow in high temperature heating applications is at least 3 gpm per ton 3 2 l m per kW to improve per...

Страница 7: ...mponents additional ball valves unions etc may be required for ease of service This drawing shows only minimum requirements Your specific installation will dictate final component selections 6 Buffer...

Страница 8: ...l valve Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation Pilot operated or Taco slow closing valve s sole...

Страница 9: ...pH 6 8 O2 5 ppm check for iron bacteria Iron Fouling All 0 5 ppm of Oxygen Above this level deposition will occur Corrosion Prevention pH All 6 8 5 6 8 5 Monitor treat as needed Minimize steel pipe be...

Страница 10: ...sure an even fill Once full do not allow the water level in the flush cart tank to drop below the pump inlet line or air can be pumped back out to the earth loop Try to maintain a fluid level in the t...

Страница 11: ...ritory manager should be consulted for the antifreeze best suited to your area Freeze protection should be maintained to 15 F 9 4 C below the lowest expected entering loop temperature For example if 3...

Страница 12: ...r 240 Volt The transformers may be switched to 208V operation as illustrated on the wiring diagram By switching the Red 208V and the Orange 240V at the terminal Model Voltage Code Voltage Min Max Volt...

Страница 13: ...eothermal Heat Pumps Rev 30 June 2008B 13 Figure 5 THW 50Hz Line and Low Voltage Figure 6 THW 60Hz Line and Low Voltage Electrical Line Voltage Field Low Voltage Wiring Field Line Voltage Wiring Field...

Страница 14: ...Slow Closing valves on THW Series equipment Figure 9a wiring should be utilized The valve takes approximately 60 seconds to open very little water will flow before 45 seconds and it activates the com...

Страница 15: ...limateMaster with a 1 4 internal flare connection as part number 39B0005N01 Electrical Low Voltage CAUTION CAUTION Refrigerant pressure activated water regulating valves should never be used with Clim...

Страница 16: ...ons As the outdoor temperature decreases the heat loss of the structure increases which requires more capacity from the heating system If the water temperature is reduced as the outdoor air temperatur...

Страница 17: ...F and 68 F 20 C and 20 C the water temperature in the buffer tank is adjusted accordingly For homes that are well insulated and tightly sealed the building balance point may be 55 F 13 C or lower so t...

Страница 18: ...r unit forced air heating may be used for the shoulder seasons allowing quick heating to cooling changeover If this feature is used the consumer will easily be able to tell when WWSD is enabled becaus...

Страница 19: ...ETS PROGRAM SETTINGS DAYLIGHT SAVINGS SET MONTH DAY YR HR MIN VACATION HOLD DATE THEN TIME SECURITY LOCKOUT TEMP ADJUST LOCKOUT TOTAL KEYPAD LOCKOUT SCREEN SETTINGS PROGRAM SCREEN SERVICE INFORMATION...

Страница 20: ...ER TANK SETPOINT INPUT DEALER INFORMATION BUFFER TANK DEADBAND OUTDOOR TEMPERATURE RESET RESTORE DEFAULTS MANUAL OPERATION HOT WATER DEADBAND OUTDOOR DESIGN TEMP THW INTERFACE INSTALLER MENU MAXIMUM W...

Страница 21: ...30 June 2008B 21 Electrical Wiring diagram matrix Model Diagram Number Voltage Option THW008 96B0108N01 220 50 1 THW008 96B0108N02 220 50 1 VSFP THW010 96B0108N05 230 60 1 THW010 96B0108N06 230 60 1 V...

Страница 22: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 22 TYPICAL WIRING DIAGRAM THW 230 60 1 Units...

Страница 23: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 23 TYPICAL WIRING DIAGRAM THW 230 60 1 Units...

Страница 24: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 24 TYPICAL WIRING DIAGRAM THW 230 60 1 units with vsfp...

Страница 25: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 25 TYPICAL WIRING DIAGRAM THW 230 60 1 units with vsfp...

Страница 26: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 26 TYPICAL WIRING DIAGRAM THW 220 50 1 Units...

Страница 27: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 27 TYPICAL WIRING DIAGRAM THW 220 50 1 Units...

Страница 28: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 28 TYPICAL WIRING DIAGRAM THW 220 50 1 Units WITH VSFP...

Страница 29: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 29 TYPICAL WIRING DIAGRAM THW 220 50 1 Units WITH VSFP...

Страница 30: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 30 TYPICAL WIRING DIAGRAM THW 420 50 3 Units...

Страница 31: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 31 TYPICAL WIRING DIAGRAM THW 420 50 3 Units...

Страница 32: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 32 TYPICAL WIRING DIAGRAM THW 420 50 3 Units WITH VSFP...

Страница 33: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 33 TYPICAL WIRING DIAGRAM THW 420 50 3 Units WITH VSFP...

Страница 34: ...s to bring the building space up to occupancy temperatures 2 Voltage utilization range complies with ARI Standard 110 Determination of operating limits is dependent primarily upon three factors 1 ente...

Страница 35: ...e for proper range and also verify heating and cooling setpoints for proper operation q System pH System water pH is 7 5 8 5 Proper pH promotes longevity of hoses and fittings q System Flushing Water...

Страница 36: ...conduct the following checks a Check the voltage and current They should comply with the electrical specifications described on the unit nameplate b Look for wiring errors Check for loose terminal scr...

Страница 37: ...result of the deterioration of iron or galvanized piping or components in the system or open cooling towers requiring heavy chemical treatment and mineral buildup through water use Should periodic coi...

Страница 38: ...gn or improper application installation or use of CM s products or 13 Electricity or fuel costs or any increases or unrealized savings in same for any reason whatsoever CM is not responsible for 1 The...

Страница 39: ...rrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any fluids refrigerant or other system components or associated labor to repair or replace the...

Страница 40: ...bargain between the parties but are merely ClimateMaster s opinion or commendation of its products The management system governing the manufacture of ClimateMaster s products is ISO 9001 2000 certifi...

Отзывы: