ClimateMaster THW Series Скачать руководство пользователя страница 11

Tranquility THW - 50 & 60Hz R410A - ClimateMaster Geothermal Heat Pumps - Rev.: 30 June, 2008B

11

Figure 3: Typical Earth Loop Connection.  

Antifreeze may be added before, during, or after the flushing 

procedure. However, depending upon which time is chosen, 

antifreeze could be wasted when emptying the flush cart 

tank. See antifreeze section for more details. Loop static 

pressure will fluctuate with the seasons. Pressures will be 

higher in the winter months than during the cooling season. 

This fluctuation is normal and should be considered when 

charging the system initially. Run the unit in either heating 
or cooling for a number of minutes to condition the loop 
to a homogenous temperature. This is a good time for 

tool cleanup, piping insulation etc. Then final flush and 

pressurize the loop to a static pressure of 40-50 psi [275-
345 kPa] (winter) 15-20 psi [100-138 kPa] (summer). 

After pressurization, be sure to remove the plug in the 
end of the Grundfos loop pump motor(s) to allow trapped 
air to be discharged and to insure the motor housing has 

been flooded. This is not required for Taco circulators. 

Insure the loop flow center provides adequate flow 

through the unit by checking pressure drop across the 

heat exchanger and comparing it to the figures shown in 

Table 7.  

Antifreeze

In areas where minimum entering loop temperatures drop 
below 40°F [4.4°C] or where piping will be routed through 

areas subject to freezing, antifreeze is needed. Alcohols 
and glycols are commonly used as antifreezes, however 
your local territory manager should be consulted for the 
antifreeze best suited to your area. Freeze protection 
should be maintained to 15°F [-9.4°C] below the lowest 
expected entering loop temperature. For example, if 
30°F [-1.1°C] is the minimum expected entering loop 
temperature, the leaving loop temperature would be 
25-22°F [-3.9 to -5.6°C] and freeze protection should be 
at 15°F [-9.4°C] (30°F-15°F=15°F). All alcohols should 
be premixed and pumped from a reservoir outside of the 
building when possible or introduced under water level 
to prevent fuming. Initially calculate the total volume of 

fluid in the piping system using Table 3. Then use the 

percentage by volume shown in Table 4 for the amount of 
antifreeze. Antifreeze concentration should be checked 
from a well mixed sample using a hydrometer to measure 

specific gravity.  

Low Water Temperature Cut-Out Setting

When an antifreeze is selected the low temperature limit 
setpoint should be switched to the lower setting to avoid 
nuisance faults. Consult 

Low Water Temperature Cut-

Out Setting

 in the controls section for more information.

GROUND-LOOP HEAT PUMP APPLICATIONS

To/From Ground Loop

THW

Source HX

(coaxial)

Load HX

IN

OUT

NOTES:
1. P/T (pressure/temperature)  ports are internal for THW
    series units.
2. Source water piping must be insulated for closed loop
     installations.
3. Other components (additional ball valves, unions, etc.)
    may be required for ease of service. This drawing
    shows only minimum requirements. Your specific
    installation will dictate final component selections.
4. Local code supercedes any piping arrangements or
    components shown on this drawing.

Flow Controller

02Nov07

See drawings in Application manual for Load connections

P/T port

Sound absorbing pad

Содержание THW Series

Страница 1: ...Data 4 Dimensional Data 5 Installation 6 Load Plumbing Installation 7 Ground Water Heat Pump Application 8 Water Quality Standards 9 Ground Loop Heat Pump Application 10 Electrical Power Wiring 13 El...

Страница 2: ...or serious injury DANGER labels on unit access panels must be observed WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicate...

Страница 3: ...all pipes fittings and valves before installing any of the system components Remove any dirt or trash found in or on these components Pre Installation Installation Operation and Maintenance instructio...

Страница 4: ...Connection Size IPT in 1 1 1 Maximum Working Pressure Water Side Base Unit PSIG kPa 500 3445 500 3445 500 3445 DHW Option PSIG kPa 500 3445 500 3445 500 3445 Internal Source Pump w Expansion Tank PSIG...

Страница 5: ...3cm Model Overall Cabinet Water Connections Electric Access Plugs 1 2 3 4 5 6 A Depth B Width C Height D Source Outdoor Water In E Source Outdoor Water Out F Load Indoor Water In G Load Indoor Water...

Страница 6: ...erature and pressure combination This excludes PVC for most heating applications Insure load water flow in high temperature heating applications is at least 3 gpm per ton 3 2 l m per kW to improve per...

Страница 7: ...mponents additional ball valves unions etc may be required for ease of service This drawing shows only minimum requirements Your specific installation will dictate final component selections 6 Buffer...

Страница 8: ...l valve Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation Pilot operated or Taco slow closing valve s sole...

Страница 9: ...pH 6 8 O2 5 ppm check for iron bacteria Iron Fouling All 0 5 ppm of Oxygen Above this level deposition will occur Corrosion Prevention pH All 6 8 5 6 8 5 Monitor treat as needed Minimize steel pipe be...

Страница 10: ...sure an even fill Once full do not allow the water level in the flush cart tank to drop below the pump inlet line or air can be pumped back out to the earth loop Try to maintain a fluid level in the t...

Страница 11: ...ritory manager should be consulted for the antifreeze best suited to your area Freeze protection should be maintained to 15 F 9 4 C below the lowest expected entering loop temperature For example if 3...

Страница 12: ...r 240 Volt The transformers may be switched to 208V operation as illustrated on the wiring diagram By switching the Red 208V and the Orange 240V at the terminal Model Voltage Code Voltage Min Max Volt...

Страница 13: ...eothermal Heat Pumps Rev 30 June 2008B 13 Figure 5 THW 50Hz Line and Low Voltage Figure 6 THW 60Hz Line and Low Voltage Electrical Line Voltage Field Low Voltage Wiring Field Line Voltage Wiring Field...

Страница 14: ...Slow Closing valves on THW Series equipment Figure 9a wiring should be utilized The valve takes approximately 60 seconds to open very little water will flow before 45 seconds and it activates the com...

Страница 15: ...limateMaster with a 1 4 internal flare connection as part number 39B0005N01 Electrical Low Voltage CAUTION CAUTION Refrigerant pressure activated water regulating valves should never be used with Clim...

Страница 16: ...ons As the outdoor temperature decreases the heat loss of the structure increases which requires more capacity from the heating system If the water temperature is reduced as the outdoor air temperatur...

Страница 17: ...F and 68 F 20 C and 20 C the water temperature in the buffer tank is adjusted accordingly For homes that are well insulated and tightly sealed the building balance point may be 55 F 13 C or lower so t...

Страница 18: ...r unit forced air heating may be used for the shoulder seasons allowing quick heating to cooling changeover If this feature is used the consumer will easily be able to tell when WWSD is enabled becaus...

Страница 19: ...ETS PROGRAM SETTINGS DAYLIGHT SAVINGS SET MONTH DAY YR HR MIN VACATION HOLD DATE THEN TIME SECURITY LOCKOUT TEMP ADJUST LOCKOUT TOTAL KEYPAD LOCKOUT SCREEN SETTINGS PROGRAM SCREEN SERVICE INFORMATION...

Страница 20: ...ER TANK SETPOINT INPUT DEALER INFORMATION BUFFER TANK DEADBAND OUTDOOR TEMPERATURE RESET RESTORE DEFAULTS MANUAL OPERATION HOT WATER DEADBAND OUTDOOR DESIGN TEMP THW INTERFACE INSTALLER MENU MAXIMUM W...

Страница 21: ...30 June 2008B 21 Electrical Wiring diagram matrix Model Diagram Number Voltage Option THW008 96B0108N01 220 50 1 THW008 96B0108N02 220 50 1 VSFP THW010 96B0108N05 230 60 1 THW010 96B0108N06 230 60 1 V...

Страница 22: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 22 TYPICAL WIRING DIAGRAM THW 230 60 1 Units...

Страница 23: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 23 TYPICAL WIRING DIAGRAM THW 230 60 1 Units...

Страница 24: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 24 TYPICAL WIRING DIAGRAM THW 230 60 1 units with vsfp...

Страница 25: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 25 TYPICAL WIRING DIAGRAM THW 230 60 1 units with vsfp...

Страница 26: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 26 TYPICAL WIRING DIAGRAM THW 220 50 1 Units...

Страница 27: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 27 TYPICAL WIRING DIAGRAM THW 220 50 1 Units...

Страница 28: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 28 TYPICAL WIRING DIAGRAM THW 220 50 1 Units WITH VSFP...

Страница 29: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 29 TYPICAL WIRING DIAGRAM THW 220 50 1 Units WITH VSFP...

Страница 30: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 30 TYPICAL WIRING DIAGRAM THW 420 50 3 Units...

Страница 31: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 31 TYPICAL WIRING DIAGRAM THW 420 50 3 Units...

Страница 32: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 32 TYPICAL WIRING DIAGRAM THW 420 50 3 Units WITH VSFP...

Страница 33: ...Tranquility THW 50 60Hz R410A ClimateMaster Geothermal Heat Pumps Rev 30 June 2008B 33 TYPICAL WIRING DIAGRAM THW 420 50 3 Units WITH VSFP...

Страница 34: ...s to bring the building space up to occupancy temperatures 2 Voltage utilization range complies with ARI Standard 110 Determination of operating limits is dependent primarily upon three factors 1 ente...

Страница 35: ...e for proper range and also verify heating and cooling setpoints for proper operation q System pH System water pH is 7 5 8 5 Proper pH promotes longevity of hoses and fittings q System Flushing Water...

Страница 36: ...conduct the following checks a Check the voltage and current They should comply with the electrical specifications described on the unit nameplate b Look for wiring errors Check for loose terminal scr...

Страница 37: ...result of the deterioration of iron or galvanized piping or components in the system or open cooling towers requiring heavy chemical treatment and mineral buildup through water use Should periodic coi...

Страница 38: ...gn or improper application installation or use of CM s products or 13 Electricity or fuel costs or any increases or unrealized savings in same for any reason whatsoever CM is not responsible for 1 The...

Страница 39: ...rrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any fluids refrigerant or other system components or associated labor to repair or replace the...

Страница 40: ...bargain between the parties but are merely ClimateMaster s opinion or commendation of its products The management system governing the manufacture of ClimateMaster s products is ISO 9001 2000 certifi...

Отзывы: