background image

Tranquility

®

 Compact 

Belt Drive (TCH/V) Series

 

Models TCH072 - 120

TCV072 - 300

60Hz - HFC-410A

Installation, Operation 

& Maintenance

97B0084N01

Revised: July 25, 2017

Table of Contents

Model Nomenclature 

3

General Information 

4

TCH Physical Data 

(includes unit w/WSE)

 

6

TCV Physical Data 

(includes unit w/WSE)

 

9

Horizontal Installation 

16

TCH Field Conversion of Air Discharge 

18

Vertical Installation 

21

TCV Field Conversion of Air Discharge 

22

TCV072-240 Field Conversion of Air Discharge 

23

TCV300 Field Conversion of Air Discharge 

26

TCV  Field  Conversion  of  Control  Box 

29               

TCV Field Conversion of Water Connections 

30

Vertical Condensate Installation 

31

Piping Installation 

32

Water-Loop Heat Pump Applications 

33

Ground-Loop Heat Pump Applications 

34

Ground-Water Heat Pump Applications 

36

Water Quality Standards 

38

Electrical - Line Voltage 

39

Electrical - Power Wiring 

41

Electrical - Power & Low Voltage Wiring 

42

Electrical - Thermostat Wiring 

44

Typical Wiring Diagram - TCH/V Units with CXM 

45

CXM Controls 

49

DXM Controls 

50

Safety Features 

52

CXM and DXM Controls 

53

Blower Adjustment 

54

Tensioning V-Belt Drives 

55

Blower Sheave Information 

56

TCH/V 072 Blower Performance 

57

TCH/V 096 Blower Performance 

58

TCH/V 120 Blower Performance 

60

Blower Performance Data – TCV160 Standard Unit 

62

Blower Performance Data – TCV192 Standard Unit 

63

Blower Performance Data – TCV240 Standard Unit 

64

Blower Performance Data – TCV240 Standard Unit 

65

Blower Performance Data – TCV300 Standard Unit 

66

Unit Starting and Operating Conditions 

67

Piping System Cleaning and Flushing 

68

Unit Starting and Operating Conditions 

69

Unit Start-Up Procedure 

70

Unit Operating Conditions 

72

Start-Up Log Sheet 

73

Preventive Maintenance 

74

Circuit Diagram with Safety Devices 

75

Functional Troubleshooting 

76

Performance Troubleshooting 

77

Warranty (U.S. & Canada) 

79

Revision History 

80

Содержание TCH072

Страница 1: ...ne Voltage 39 Electrical Power Wiring 41 Electrical Power Low Voltage Wiring 42 Electrical Thermostat Wiring 44 Typical Wiring Diagram TCH V Units with CXM 45 CXM Controls 49 DXM Controls 50 Safety Fe...

Страница 2: ...CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact Belt Drive TCH V Series Rev July 25 2017 2 ClimateMaster Water Source Heat Pumps This Page Intentionally Left Blank...

Страница 3: ...T RETURN S S DRAIN PAN BACK DISCHARGE WS RIGHT RETURN S S DRAIN PAN STRAIGHT DISCHARGE A DUAL POINT POWER V VERTICAL TCH ONLY BF BACK RETURN FRONT DISCHARGE BT BACK RETURN TOP DISCHARGE FB FRONT RETUR...

Страница 4: ...dry area Store units in an upright position at all times Unit Protection Cover units on the job site with either the original packaging or an equivalent protective covering Cap the open ends of pipes...

Страница 5: ...ity and service life Always move and store units in an upright position Tilting units on their sides may cause equipment damage CAUTION CAUTION CAUTION CAUTION CUT HAZARD Failure to follow this cautio...

Страница 6: ...kW 1 0 75 2 1 49 3 2 24 Large Motor hp kW 2 1 49 3 2 24 5 3 73 Blower No of Blowers 1 Blower Wheel Size D x W in cm 12 x 12 30 48 x 30 48 Water Connection Size FPT in mm 1 1 4 31 8 1 1 2 38 1 Coax Vo...

Страница 7: ...rvice Water inlet and water outlet connections are available on either side left or right of the unit Qty 2x MPT Plugs are shipped loose in a plastic bag tied to the water leg in front of the unit Ins...

Страница 8: ...ory supplied controller aquastat is inside unit completely wired To field adjust temperature setting remove ACP panel and push button 9 Expansion valve access panel is opposite return air side 10 WSE...

Страница 9: ...mm 1 25 4 Air Coil Data Air Coil Dimensions H x W in cm 32 x 34 81 28 x 86 36 36 x 36 91 44 x 91 44 36 x 76 91 44 x 193 04 Air Coil Total Face Area ft2 m2 7 6 0 71 9 0 0 84 19 1 77 Air Coil Tube Size...

Страница 10: ...ight of unit Drain hose and drain connection will be tied inside the unit Installer will untie the drain hose form trap and FRQQHFW WR WKH FRQGHQVDWH GUDLQ KROH RI LQVWDOOHU V FKRLFH 4 Electrical acce...

Страница 11: ...CSP ACP WSE Front View Back View Top View Rear Return Front Discharge Rear Return Front Discharge Legend BSP Blower Service Panel CSP Compressor Service Panel CAP Control Access Panel MSP Motor Servi...

Страница 12: ...QGHQVDWH GUDLQ KROH RI LQVWDOOHU V FKRLFH 4 Electrical access is available on either side left or right of unit and is also available in the front on the left or right side of the unit 5 Overall width...

Страница 13: ...AP CSP BSP ACP UPA and MSP 3 Factory supplied controller aquastat is inside unit completely wired To field adjust temperature setting remove ACP panel and push button 4 Internally trapped externally v...

Страница 14: ...ection will be tied inside the unit Installer will untie the drain hose form trap and FRQQHFW WR WKH FRQGHQVDWH GUDLQ KROH RI LQVWDOOHU V FKRLFH 4 Electrical access is available on either side left or...

Страница 15: ...erature setting remove ACP panel and push button 4 Internally trapped externally vented 5 For top discharge units BSP is on front For front discharge units BSP is on top allow 3 feet above unit for se...

Страница 16: ...ns 2 DO NOT obstruct the space beneath the unit with piping electrical cables and other items that prohibit future removal of components or the unit itself 3 Use a manual portable jack lift to lift an...

Страница 17: ...with integral J swivel Building Loop Water In Ball valve with optional integral P T plug Unit Power CAP CAP EAP BSP CBP LEGEND CAP Compressor Access Panel CBP Control Box Panel BSP Blower Service Pane...

Страница 18: ...Adjust motor downward to tighten belt Raise or lower motor slide assembly with adjusting bolt and retighten 2 slide nuts Check for correct tension See Tensioning V Belt Drives page Rewire motor at con...

Страница 19: ...tate entire blower housing assembly to rest at back end of the unit Locate housing holes and bolt down using previous 1 4 20 UNC bolts 3x ea side Motor motor motor sheave blower sheave and belt Step 7...

Страница 20: ...e included in the supply duct to reduce air noise If air noise or excessive air flow is a problem the blower speed can be changed For airflow charts consult submittal data for the series and model of...

Страница 21: ...e following application guidelines must be used when installing TC units Failure to follow these guide lines could result in unsatisfactory unit performance and or premature failure of some unit compo...

Страница 22: ...its can be field converted between top and straight side and back end discharge using the instructions below Preparation Place in a well lighted area Conversion should only be attempted by qualified s...

Страница 23: ...ly 25 2017 23 climatemaster com TCV072 240 Field Conversion of Air Discharge Figure 8 TCV072 120 and TCV160 240 Pictorally Shown Top Discharge Steps to Convert to Straight Discharge Step 1 For TCV072...

Страница 24: ...4 ClimateMaster Water Source Heat Pumps TCV072 240 Field Conversion of Air Discharge Step 2 Remove motor and then unscrew and remove motor mount assembly Put motor mount assembly back in lower mount p...

Страница 25: ...ter com TCV072 240 Field Conversion of Air Discharge Step 4 Rotate blower assembly 90 degrees Reattach blower assembly to front of unit as shown Put belt on and retighten Step 5 Replace panels and mis...

Страница 26: ...mpact Belt Drive TCH V Series Rev July 25 2017 26 ClimateMaster Water Source Heat Pumps TCV300 Field Conversion of Air Discharge Step 1 Remove 5 panels dividers and panel mount brackets Figure 8 TCV30...

Страница 27: ...aster com TCV300 Field Conversion of Air Discharge Note Unlike the 160 240 the TCV300 only has 1 location for the motor mount assembly Do not remove Step 2 Unattach and lift entire 3 blower sub assemb...

Страница 28: ...ld Conversion of Air Discharge Step 5 Rotate the blower assembly 90 degrees counter clockwise The belly of the blowers should be facing upward Step 4 Attach middle divider Step 6 Reattach blower assem...

Страница 29: ...els Note Must provide 3 feet or code requirement service access for new control box location TCV Field Conversion of Control Box Step 1 Remove control box access panel and panel box will be relocated...

Страница 30: ...qualified service technician Side to Back Discharge Conversion Step 1 Remove panels needed for access to water connections Step 2 Remove screws from side panels Loosen 4x screws in slots but do not r...

Страница 31: ...e line is pitched toward drain 1 4 per foot 10mm per 46cm of run Vertical Condensate Installation All fittings and tubing outside of the unit are field supplied Condensate Pan 1 IPT 2 Screws Open Vent...

Страница 32: ...tion is required if loop water temperature drops below the dew point insulation is required for ground loop applications in most climates Pipe joint compound is not necessary when Teflon thread tape i...

Страница 33: ...ng system Depending upon selection hose kits may include shut off valves P T plugs for performance measurement high pressure stainless steel braided hose Y type strainer with blow down valve and or J...

Страница 34: ...thylene fusion only for in ground sections of the loop Galvanized or steel fittings should not be used at any time due to their tendency to corrode All plastic to metal threaded fittings should be avo...

Страница 35: ...Wiring Insulated supply duct with at least one 90 deg elbow to reduce air noise Return Air Supply Air Unit Hanger 3 8 10mm threaded rods Flexible Duct Connector Optional Balancing Valve Water Out Opti...

Страница 36: ...ith PVC or CPVC piping may cause failure of the PVC CPVC PVC CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC 410A as system failur...

Страница 37: ...f 1 5 to 2 gpm per ton 2 0 to 2 6 l m per kW is achieved A second method of flow control requires a flow control device mounted on the outlet of the water control valve The device is typically a brass...

Страница 38: ...r temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and C...

Страница 39: ...8 N A N A 50 H 208 230 60 3 197 254 D E 2 13 7 83 1 8 5 35 9 39 3 N A N A 50 F 460 60 3 414 506 A B C 2 6 2 41 0 2 9 15 3 16 9 N A N A 20 F 460 60 3 414 506 D E 2 6 2 41 0 4 1 16 5 18 1 N A N A 20 N 5...

Страница 40: ...38 9 11 6 13 1 N A N A 15 3 2 4 0 N A N A 15 N 575 60 3 518 633 D E 2 5 8 38 9 11 6 13 1 N A N A 15 5 2 6 5 N A N A 15 TCV160 H 208 230 60 3 197 254 A B C 2 23 2 164 0 46 4 52 2 5 600 70 8 5 10 6 N A...

Страница 41: ...a length of flexible conduit to minimize vibration and sound transmission to the building General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial...

Страница 42: ...xtended range applications with antifreeze most ground loops jumper JW3 should be clipped as shown in Figure 17 to change the setting to 10 F 12 2 C refrigerant temperature a more suitable temperature...

Страница 43: ...e following notations 1 The valve will remain open during a unit lockout 2 The valve will draw approximately 25 35 VA through the Y signal of the thermostat Note This valve can overheat the anticipato...

Страница 44: ...ay in certain cases need to be sealed to prevent erroneous temperature measurement Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude thr...

Страница 45: ...THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility Compact Belt Drive TCH V Series Rev July 25 2017 45 climatemaster com Typical Wiring Diagram TCH V Units with CXM...

Страница 46: ...CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact Belt Drive TCH V Series Rev July 25 2017 46 ClimateMaster Water Source Heat Pumps Typical Wiring Diagram TCH V Units with MPC...

Страница 47: ...THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility Compact Belt Drive TCH V Series Rev July 25 2017 47 climatemaster com Typical Wiring Diagram TCH V Units with DXM...

Страница 48: ...CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact Belt Drive TCH V Series Rev July 25 2017 48 ClimateMaster Water Source Heat Pumps Typical Wiring Diagram TCH V Units with LON...

Страница 49: ...g field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field selection to disable the UPS...

Страница 50: ...d to 24VAC or to be a dry contact no connection Not Clipped AL2 connected to R Clipped AL2 dry contact no connection Low pressure normally open Jumper 1 JW1 LP norm open provides field selection for l...

Страница 51: ...t call for compressor stage 2 W1 is the input call for heating stage 3 or emergency heat and O W2 is the input call for reversing valve heating or cooling depending upon DIP 1 4 On Heat Pump Off Heat...

Страница 52: ...sec pause 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault...

Страница 53: ...he unit The green status light will flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED Diagnostic Features The LED on the CXM board advises the technician of the current status...

Страница 54: ...is straight misalignment will cause premature belt failure Adjust sheave if needed Belt Tensioning An overly loose belt will upon motor start produce a slippage squeel and cause premature belt failur...

Страница 55: ...ecker and read the forct applied from the bottom of the small O ring on the deflection force scale 6 Compare the force you have applied with the values given in the table below The force should be bet...

Страница 56: ...67 X 1 BK67 X 1 Motor Sheave 1VP44 X 7 8 1VP34 X 7 8 1VP50 X 7 8 1VP44 X 1 1 8 1VP50 X 1 1 8 Motor 3HP 3HP 3HP 5HP 5HP Belt Qty 1 BX46 BX46 BX46 BX46 BX47 160 Blower Sheave BK80H BK80H BK80H BK80H BK8...

Страница 57: ...en 3 2 5 4 3 5 2 5 2 1 5 1 5 4 3 5 3 2 5 2 1 5 2500 BHP 0 52 0 57 0 61 0 66 0 72 0 78 0 83 0 89 0 94 1 00 1 03 1 08 1 14 1 20 1 25 1 31 Sheave Mtr B B A A A A A A C E E E E E E E RPM 620 660 700 740 7...

Страница 58: ...PM 625 665 705 740 780 815 850 885 920 950 985 1015 1045 1075 1100 1130 Turns Open 4 3 2 5 1 5 5 5 5 4 5 3 5 3 2 5 2 1 5 1 4 3 5 3 2700 BHP 0 60 0 65 0 70 0 75 0 80 0 86 0 91 0 97 1 02 1 08 1 14 1 20...

Страница 59: ...E E E RPM 780 815 845 880 910 940 970 1000 1025 1055 1080 1105 1130 1160 1185 1210 Turns Open 5 5 5 4 5 3 5 3 2 5 2 1 5 1 4 5 4 3 5 3 2 5 2 1 5 3600 BHP 1 24 1 30 1 37 1 44 1 51 1 58 1 65 1 72 1 78 1...

Страница 60: ...740 770 805 840 875 905 935 965 995 1020 1050 1075 1105 1130 1155 1180 Turns Open 4 3 2 5 2 6 5 5 5 4 4 3 2 5 2 5 2 1 5 1 3 5 3400 BHP 1 06 1 13 1 19 1 26 1 33 1 38 1 44 1 50 1 56 1 65 1 72 1 80 1 87...

Страница 61: ...5 1 5 1 3 5 3 2 5 4600 BHP 2 39 2 45 2 54 2 63 2 72 2 83 2 92 3 00 3 10 3 18 3 28 3 38 Sheave Mtr A A A A A A A D D E E E RPM 980 1000 1025 1050 1075 1105 1130 1150 1175 1195 1220 1245 Turns Open 4 3...

Страница 62: ...000 1030 1060 1090 Turns Open 4 5 3 5 2 5 1 5 5 5 5 4 3 5 2 5 2 1 5 3 5 3 2 1 5 1 5800 BHP 1 17 1 28 1 39 1 49 1 60 1 70 1 81 1 90 2 02 2 14 2 28 2 40 2 52 2 67 2 81 2 96 Sheave Mtr B B B B A A A A A...

Страница 63: ...B B A A A A A A A C C C E E E E RPM 700 740 775 810 845 880 910 940 970 1000 1030 1060 1085 1115 1145 1170 Turns Open 3 5 2 5 5 5 5 4 3 2 5 2 1 5 6 5 4 5 4 3 5 3 2 5 6200 BHP 1 70 1 83 1 94 2 06 2 17...

Страница 64: ...BHP 2 22 2 34 2 48 2 62 2 74 2 86 2 98 3 10 3 22 3 34 3 49 3 61 3 73 3 90 4 06 4 22 Sheave Mtr B B B B A A A A A A A A C C C C RPM 755 785 820 855 885 915 945 975 1005 1030 1060 1085 1110 1140 1165 11...

Страница 65: ...5 1 3 5 3 2 5 2 1 5 1 8400 BHP 3 62 3 74 3 89 4 03 4 18 4 33 4 49 4 65 4 81 4 97 5 16 5 36 5 56 5 72 5 92 Sheave Mtr A A A A A A A A C C E E E E E RPM 880 905 935 965 995 1020 1045 1070 1095 1120 1145...

Страница 66: ...0 1290 1315 1340 1360 Turns Open 6 5 5 4 5 4 3 5 3 2 5 1 5 1 3 5 3 2 5 2 1 5 1 5 9300 BHP 4 34 4 56 4 74 4 96 5 14 5 35 5 53 5 71 5 89 6 08 6 29 6 50 6 67 6 88 7 05 Sheave Mtr A A A A A A A A A C C C...

Страница 67: ...normal or continuous operating conditions Minimum maximum limits are start up conditions to bring the building space up to occupancy temperatures Units are not designed to operate under these conditio...

Страница 68: ...m phosphate in a proportion of approximately 150 gallons 1 2 kg per 750 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate th...

Страница 69: ...Condensate line Verify that condensate line is open trapped vented and properly pitched toward drain Water flow balancing Record inlet and outlet water temperatures for each heat pump upon startup Th...

Страница 70: ...e flow rate in U S GPM determined by comparing the pressure drop across the heat exchanger to tables 8a through 8e In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature...

Страница 71: ...5 4 5 31 0 3 6 24 8 3 3 22 8 24 1 514 90 85 9 3 64 1 7 9 54 5 6 6 45 5 6 1 42 1 TCH V120 15 0 946 56 781 4 27 6 3 2 22 1 2 2 15 2 2 13 8 22 5 1 42 85 172 8 6 59 3 7 2 49 6 5 5 37 9 5 1 35 2 30 1 893 1...

Страница 72: ...178 179 187 401 430 411 442 415 455 10 13 12 16 13 18 13 17 14 17 14 16 18 20 12 14 9 11 41 43 43 45 44 46 100 1 5 2 25 3 139 147 138 146 138 146 448 471 420 445 405 432 8 9 8 10 8 10 13 16 11 13 10 1...

Страница 73: ...d costly system failures complete the following checks and data entries before the system is put into full operation External Static Sheave Setting Turns Open Temperatures F or C Antifreeze Pressures...

Страница 74: ...ormance Filters should be inspected every month under normal operating conditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic...

Страница 75: ...SUCTION LINE COMPRESSOR LINE WATER HIGH PRESSURE SWITCHES N C SOURCE WATER OUTLET SOURCE WATER INLET TXV BULB MOTORIZED WATER VALVE OPTIONAL AUTO FLOW REGULATOR COMPONENTS MAY BE INTERNAL OR EXTERNAL...

Страница 76: ...t toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air filter x X Restricted Return Air Flow Find and eliminat...

Страница 77: ...e Check fan motor operation and air flow restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Che...

Страница 78: ...Liquid Line Temp 6 Source Water In Tmp 7 Source Water Out Tmp 8 Source Water In Pres 9 10 11 Source Water Out Pres 9a Press Drop 9b Flow Rate Return Air Temp Supply Air Temp Heat of Extraction Absorp...

Страница 79: ...t of insuf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to...

Страница 80: ...Data Table Corrected TCV drain diameter 08 09 11 Unit Maximum Working Water Pressure Updated to Reflect New Safeties 07 08 11 All Added TCV072 120 01 03 11 Format All Pages Updated 07 26 10 Wiring Di...

Отзывы: