background image

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

T (ERV) Series

R e v. :   1 5   A p r i l ,   2 0 1 6

3

c l i m a t e m a s t e r. c o m

Installation

1.   Attach duct work to duct flanges on ERV.
2.   Remove ERV control access panel to connect field 

wiring.

3.   Route class II low voltage wire (3 conductor) from 

thermostat or energy management through small 

bushing in end panel of ERV. 

See wiring diagram.

a. Thermostat (dependent) - connect in parallel at 

rooftop unit with “G”, “C” and  “W”. Then connect 

matching color at terminal 1, 2, and 3 respectively 

on ERV circuit board.

b. Energy Management - p24 VAC to “1” and 

common, 24 VAC to “2” terminals on ERV circuit 

board.

c. Thermostat (dedicated) - splice into +24 vac 

(blue wire) at (control circuit board) transformer 

connection run wire to “R” terminal. Then run 

another wire from “G” terminal to ERV (control 

circuit board) terminal block #1.

4.   All electrical connections must conform to any local 

codes and current National Electric Codes (NEC) and 

Canadian Electric Codes (CEC). Refer closely to unit 

wiring diagram in unit and/or in these instructions for 

proper wiring connections.

5.   Refer to the unit nameplate for minimum circuit 

ampacity (MCA) and maximum overcurrent protection 

size (fuse).

6.   Electrical data is listed on unit rating plate and motor   

name plates.

7.   Connect line voltage power supply to ERV fuse block 

in control box of unit from disconnect switch. 

See 

wiring diagram.

8. Ground unit with a suitable ground connection either 

through unit supply wiring or an earth ground.

Note: Unit voltage entries must be sealed  

weather tight after wiring is complete.

9. Remove motor access panels. Locate belts fastened 

to blower assembly. Install belt onto motor and blower 

pulley. Adjust motor sheave to correct blower RPM for 

CFM and external static pressure requirements. See 

charts in this instruction. Multiple pulley arrangements 

are available to meet the entire range.

10.  Replace access panel onto the ERV unit and secure.
11. Restore power to unit.
12. Cleanup once unit is operating properly, caulk 

any open joints, holes or seams to make the units 

completely air and water tight. 

13. Leave this instruction manual with owner or in an 

envelope to be kept near unit.

Operation

(How It Works)

The unit contains an Energy Recovery Wheel (ERW) 

that is a new concept in rotary air-to-air heat exchangers. 

Designed as a packaged unit for ease of installation and 

maintenance, only the connection of electrical power is 

required to make the system operational.

When slowly rotating through counter flowing exhaust 

and fresh air streams the ERW adsorbs sensible heat 

and latent heat from the warmer air stream and transfer 

this total energy to the cooler air stream during the 

second half of its rotating cycle. Rotating at 50-60 

revolutions per minute, the wheel provides constant flow 

of energy from warmer to cooler air stream. The large 

energy transfer surface and laminar flow through the 

wheel causes this constant flow of recovered energy 

to represent up to 85% of the difference in total energy 

contained within the two air streams.

Sensible and latent heat are the two components of total 

heat. Sensible heat is energy contained in dry air and 

latent heat is the energy contained within the moisture 

of the air. The latent heat load from the outdoor fresh air 

on an air conditioning system can often be two to three 

times that of the sensible heat load and in the winter it is 

a significant part of a humidification heat load.

� 

CAUTION!

 �

CAUTION! 

Blower speed must be adjusted for the given 

external static pressure and airflow (CFM) requirements. If 

blower speed is not adjusted  for conditions, possible motor 

over loading can occur.

Содержание TB SERIES

Страница 1: ...e work In winter the ERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold drier intake air supply during the other half rota...

Страница 2: ...CL IM ATEM ASTER WATER SOURCE HEAT PUMPS T ERV Series Rev 15 April 2016 2 ClimateMaster Water Source Heat Pumps This Page Intentionally Left Blank...

Страница 3: ...M for CFM and external static pressure requirements See charts in this instruction Multiple pulley arrangements are available to meet the entire range 10 Replace access panel onto the ERV unit and sec...

Страница 4: ...ff to avoid depressurization should be considered Recovery Wheel Mode On a thermostat call for blower operation in heating cooling or continuous blower the ERW will rotate between fresh air and exhaus...

Страница 5: ...s against the spoke flanges If hand pressure does not fully seat the segment insert the flat tip of a screw driver between the wheel rim and outer corners of the segment and apply downward force while...

Страница 6: ...erate properly without balancing damper 4 See blower performance charts for airflow at various E S P 5 Filter rack with 2 pleated filters included A B C D D E I G H F H ERV Data Dimensional Data ERV S...

Страница 7: ...Jack Cycle Optional J48 Jack Control Box Fresh Air J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harn...

Страница 8: ...sh Air J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J152...

Страница 9: ...t 208 230V 1 PH ERV UNIT WIRING DIAGRAM Notes 1 Remove jumper to install field optional low ambient switch 2 Selective voltage terminals for proper unit voltage 3 Optional low ambient switch 4 Optiona...

Страница 10: ...V UNIT WIRING DIAGRAM Notes 1 Remove jumper to install field optional low ambient switch 2 Step down transformer assembly for 460 575 volt units 3 Selective voltage terminals for proper unit voltage 4...

Страница 11: ...tor Filter in Intake Hood 2HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 1200 1100 1225 1315 1405 1440 1695 1725 1400 1220 1275 1400 1480 1620 1730 1790 1600 1225 1345 1475 1615...

Страница 12: ...ist Eliminator Filter in Intake Hood 3HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 2000 820 930 1015 1095 1160 1245 1315 2400 920 1010 1090 1155 1240 1305 1405 2800 1000 1085 11...

Страница 13: ...MF Mist Eliminator Filter in Intake Hood 5HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 4600 820 910 990 1020 1135 1165 1225 5000 885 965 1040 1100 1160 1225 1280 5400 910 1000 1...

Страница 14: ...or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair or replac...

Страница 15: ...THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y T ERV Series Rev 1 5 A pri l 2 0 1 6 15 climatemaster com Notes...

Страница 16: ...ment at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any b...

Отзывы: