background image

INSTALLATION INSTRUCTIONS

ENERGY RECOVERY VENTILATOR

SERIES TB, TC, TD, TE, TF & TG

Energy recovery COMPONENT certified to the ARI Air-to-
Air Energy Recovery Ventilation Equipment Certification 
Program  in accordance with ARI Standard 1060-2000. 
Actual performance in packaged equipment may vary.

ETL Certified per UL 1995 and CSA 22.2

97B0042N04

Rev.: 15 April, 2016

Installation Instructions For Energy Recovery Ventilator (Fixed)  

For Stand Alone Side-by-Side Indoor Application

Inspection 

Upon receipt of shipment at the job site, carefully check the 

shipment against the bill of lading. Make sure all units have 

been received. Inspect the carton or crating housing of each 

Rooftop Unit and inspect each unit for damage. Assure that 

the carrier makes proper notation of any shortages or damage 

on all copies of the freight bill and that he completes a Carrier 

Inspection Report. Concealed damage not discovered during 

unloading must be reported to the carrier within 15 days of 

receipt of shipment. 

NOTE: It is the responsibility of the 

purchaser to file all necessary claims with the carrier.

Storage 

Upon the arrival of  equipment at the job site, immediately store 

units in a clean, dry area. Do not stack units. 

Do not remove 

equipment from pallets until equipment is required for 

installation.

Unit Protection

Cover rooftop units on the job site. Cap the open ends of pipes. 

In areas where painting, plastering, roofing, or the spraying of 

fireproof material has not been completed, all due precautions 

must be taken to avoid physical damage to the units and 

contamination by foreign material. 

Physical damage and 

contamination may prevent proper start-up and may result 

in costly equipment cleanup.

Application

Field supplied balancing dampers in duct are recommended.

Recovery Wheel Mode

The Recovery Wheel mode is accomplished by two blowers 

providing continuous exhaust of stale indoor air and 

replacement by equal amount of outdoor air. Energy recovery 

is achieved by slowly rotating the energy recovery wheel within 

the cassette frame work. In winter, the ERV adsorbs heat 

and moisture from the exhaust air stream during one half of a 

complete rotation and gives them back to the cold, drier intake 

air supply during the other half rotation. In summer, the process 

is automatically reversed. Heat and moisture are absorbed 

from incoming fresh air supply and transferred to the exhaust 

air stream. This process allows outdoor air ventilation rates 

to be increased by factors of three or more without additional 

energy penalty or increase in size of heating or air conditioning 

systems.

 

Rigging Unit For Lifting

1.  Maximum weight 300-1200 lbs. See Physical Data Table.

2.  Remove crating.

3.  All panels must be in place for rigging.

4.  Remove barometric exhaust hood from door marked filter 

access. Install barometric exhaust hood over exhaust blower 

outlet.

5.  Forklift channels must be removed from the base of

 ERV. 

6.  Position unit and provide service access to ERV control 

access door and wheel.

7.  Duct work should be installed into roof curb before installing 

ERV on curb.

8.  Roof curb gasket must be applied to all top surfaces of the 

curb. 

9.  Position unit on roof curb and provide service access to ERV 

control access door and wheel.

� 

CAUTION!

 �

CAUTION! 

Danger of sharp metallic edges. Can cause 

injury. Take care when servicing unit to avoid accidental 

contact with sharp edges.

� 

WARNING!

 �

WARNING! 

Electric shock hazard. Can cause injury or death. 

Before attempting to perform any service or maintenance, 

turn the electrical power to unit OFF at disconnect switch(es). 

Unit may have multiple power supplies.

� 

WARNING!

 �

WARNING! 

To avoid equipment damage, do not use these 

units as a source of heat during the construction process. 

The mechanical components and filters used in these units 

will quickly become clogged with construction dirt and debris 

which may cause system damage.

� 

WARNING!

 �

WARNING! 

The installation of water-source heat pumps and 

all associated components, parts, and accessories which 

make up the installation shall be in accordance with the 

regulations of ALL authorities having jurisdiction and MUST 

conform to all applicable codes. It is the responsibility of 

the installing contractor to determine and comply with ALL 

applicable codes, regulations and ANSI/NFPA No. 70

Содержание TB SERIES

Страница 1: ...e work In winter the ERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold drier intake air supply during the other half rota...

Страница 2: ...CL IM ATEM ASTER WATER SOURCE HEAT PUMPS T ERV Series Rev 15 April 2016 2 ClimateMaster Water Source Heat Pumps This Page Intentionally Left Blank...

Страница 3: ...M for CFM and external static pressure requirements See charts in this instruction Multiple pulley arrangements are available to meet the entire range 10 Replace access panel onto the ERV unit and sec...

Страница 4: ...ff to avoid depressurization should be considered Recovery Wheel Mode On a thermostat call for blower operation in heating cooling or continuous blower the ERW will rotate between fresh air and exhaus...

Страница 5: ...s against the spoke flanges If hand pressure does not fully seat the segment insert the flat tip of a screw driver between the wheel rim and outer corners of the segment and apply downward force while...

Страница 6: ...erate properly without balancing damper 4 See blower performance charts for airflow at various E S P 5 Filter rack with 2 pleated filters included A B C D D E I G H F H ERV Data Dimensional Data ERV S...

Страница 7: ...Jack Cycle Optional J48 Jack Control Box Fresh Air J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harn...

Страница 8: ...sh Air J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J152...

Страница 9: ...t 208 230V 1 PH ERV UNIT WIRING DIAGRAM Notes 1 Remove jumper to install field optional low ambient switch 2 Selective voltage terminals for proper unit voltage 3 Optional low ambient switch 4 Optiona...

Страница 10: ...V UNIT WIRING DIAGRAM Notes 1 Remove jumper to install field optional low ambient switch 2 Step down transformer assembly for 460 575 volt units 3 Selective voltage terminals for proper unit voltage 4...

Страница 11: ...tor Filter in Intake Hood 2HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 1200 1100 1225 1315 1405 1440 1695 1725 1400 1220 1275 1400 1480 1620 1730 1790 1600 1225 1345 1475 1615...

Страница 12: ...ist Eliminator Filter in Intake Hood 3HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 2000 820 930 1015 1095 1160 1245 1315 2400 920 1010 1090 1155 1240 1305 1405 2800 1000 1085 11...

Страница 13: ...MF Mist Eliminator Filter in Intake Hood 5HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 4600 820 910 990 1020 1135 1165 1225 5000 885 965 1040 1100 1160 1225 1280 5400 910 1000 1...

Страница 14: ...or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair or replac...

Страница 15: ...THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y T ERV Series Rev 1 5 A pri l 2 0 1 6 15 climatemaster com Notes...

Страница 16: ...ment at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any b...

Отзывы: