background image

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

N (ERV) Series

R e v. :   0 4   A p r i l ,   2 0 1 4

4

C l i m a t e M a s t e r   Wa t e r - S o u r c e   H e a t   P u m p s

times that of the sensible heat load and in the winter it is 
a signi

fi

 cant part of a humidi

fi

 cation heat load.

During both the summer and winter, the ERW transfers 
moisture entirely in the vapor phase. This eliminates wet 
surfaces that retain dust and promote fungal growth as 
well as the need for a condensate pan and drain to carry 
water.

Because it is constantly rotating when in the air stream, 
the ERV is always being cleaned by air, 

fi

 rst in one 

direction then the other. Because it is always dry, dust or 
other particles impinging on the surface during one half 
cycle, are readily removed during the next half cycle.

During the heating season, when outdoor air 
temperatures are below 15ºF, it is recommended to use 
the (optional) low ambient kit (

fi

 eld installed).

Low Ambient Kit is appropriate for climates with limited 
HVAC system operation when outdoor temperatures are 
below 10ºF.

The frost threshold is the outdoor temperature at which 
frost will begin to form on the ERV wheel. For Energy 
Recovery Ventilators, the frost threshold is typically below 
10ºF. Frost threshold is dependent on indoor temperature 
and humidify. The table shows how the frost threshold 
temperatures vary depending on indoor conditions.

Because Energy Recovery Ventilators have a low frost 
threshold, frost control options are not necessary in many 
climates. Where outdoor temperatures may drop below 
the frost threshold during the ERV operational hours, 
exhaust only frost control option is available.

Low Ambient  Kit (Optional)

Low Ambient Kit turns off the supply blower when outdoor 
temperatures fall below the frost threshold. The exhaust 
only thermostat set points are 

fi

 eld adjustable. Supply 

fan operation is automatically restored when the exhaust 
air temperature rises above the thermostat set point. 
Provisions for introducing make-up air into the building 
when the supply blower is off to avoid depressurization 
should be considered.

FROST THRESHOLD TEMPERATURE

INDOOR RH AT 70ºF

FROST THRESHOLD

TEMPERATURE

20%

0ºF

30%

5ºF

40%

10ºF

Recovery Wheel Mode

On a thermostat call for blower operation in heating, 
cooling or continuous blower, the ERW will rotate 
between fresh air and exhaust air streams. Both the 
fresh air and exhaust air blowers will also be operating to 
overcome the air resistance of the ERV.

System Check

1.   Disconnect main power.
2.   Turn to “Cont” for blower operation on thermostat 

controlled models.

3.   Restore power to unit. Observe ERV wheel rotation 

and both fresh air and exhaust air blowers will 
operating.

 

NOTE: If Low ambient kit is used the jumper 
between TB37-5 & TB37-6 should be removed. 
Also if system check out is being conducted at 
low ambient temperatures, technician should  
be aware that this kit can cause system not to 
operate.

4.   Verify that the ERV (3) three phase blower motors 

are phased sequentially ensuring correct rotation and 
operation.

 

a. Disconnect power.

 

b. Reverse any two 

fi

 eld power leads to the ERV. 

c. Reapply power.

5.   Verify that both blower motors are operating under 

their full load AMP rating (FLA). The FLA can be 
found on each motor and the unit nameplate.

A.  Return Damper Settings

 

Manually adjust position of 

fi

 eld installed dampers to 

balance air 

fl

 ow.

B.  Air Flow / Blower Speed Adjustment

 

Blower speed selection is accomplished by changing 
the sheave setting on both fresh air and exhaust air 
blowers. To set ERV for the required air 

fl

 ow (CFM), 

the external static pressure applied to the ERV (duct 
static) must be known. See the CFM vs External 
Static Pressure chart for the appropriate unit to 
determine the correct blower RPM for the speci

fi

 ed 

CFM and External Static Pressure.

After blower speed adjustments have been made. Ensure 
that when the belt is replaced it is tensioned correctly. 
The motor mounting plate can be adjusted to tension the 
belt. If using a belt tension checker, adjust the span to the 
appropriate setting and check the belt defection force. 
The belt de

fl

 ection force should be between 5-8 lbs or the 

lowest tension at which the belt will not slip under peak 

Содержание NB Series

Страница 1: ...ame work In winter the ERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold drier intake air supply during the other half rotation In summer the process is automatically reversed Heat and moisture are absorbed from incoming fresh air supply and transferred to the exhaust air stream This process allows outdoor air ventilati...

Страница 2: ...CL IM ATEM ASTER WATER SOURCE HEAT PUMPS N ERV Series Rev 04 April 2014 2 ClimateMaster Water Source Heat Pumps This Page Intentionally Left Blank ...

Страница 3: ...ing or an earth ground NOTE Unit voltage entries must be sealed weather tight after wiring is complete 9 Remove motor access panels Locate belts fastened to blower assembly Install belt onto motor and blower pulley Adjust motor sheave to correct blower RPM for CFM and external static pressure requirements See charts in this instruction Multiple pulley arrangements are available to meet the entire ...

Страница 4: ...hen the supply blower is off to avoid depressurization should be considered FROST THRESHOLD TEMPERATURE INDOOR RH AT 70ºF FROST THRESHOLD TEMPERATURE 20 0ºF 30 5ºF 40 10ºF Recovery Wheel Mode On a thermostat call for blower operation in heating cooling or continuous blower the ERW will rotate between fresh air and exhaust air streams Both the fresh air and exhaust air blowers will also be operatin...

Страница 5: ...f hand pressure does not fully seat the segment insert the flat tip of a screw driver between the wheel rim and outer corners of the segment and apply downward force while guiding the segment into place D Close and latch each segment retainer under segment retaining catch E Slowly rotate the wheel 180º Install the second segment opposite the first for counterbalance Rotate the two installed segmen...

Страница 6: ...P 5 Filter rack with 2 pleated filters included ERV with Horizontal Ductwork balancing damper s field supplied B C D D E I G H F H A D D I K J ERV Data Dimensional Data ERV Series CFM Range A B C D E F G H I J K NB 300 1100 56 75 32 13 39 50 11 00 27 00 4 50 10 00 2 56 1 00 10 00 4 50 NC 1200 2000 54 38 37 25 37 50 12 00 30 00 8 00 4 00 3 63 1 50 7 00 5 00 ND 1200 2800 60 00 42 62 43 56 14 00 32 0...

Страница 7: ...e Control Harness Optional J40 Jack Cycle Optional J48 Jack Control Box Fresh Air J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J160 Jack Damper Motor Harness K94 Relay On O Optional K163 Contactor Exhaust Air Motor K164 Contactor Fresh Air Motor P33 Plug Cy...

Страница 8: ...k Cycle Optional J48 Jack Control Box Fresh Air J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J152 Jack Transformer High Voltage J160 Jack Damper Motor Harness K94 Relay On Off Optional K163 Contactor Exhaust Air Motor K164 Contactor Fresh Air Motor P33 Plug...

Страница 9: ...es 1 Remove jumper to install field optional low ambient switch 2 Selective voltage terminals for proper unit voltage 3 Optional low ambient switch 4 Optional motorized intake damper 5 Optional Stop Start and Jog Control 6 For energy management systems connect 24v to G and common 24v to C 208 230V 1 PH Desiccant Wheel for Roof top Unit ...

Страница 10: ... Wheel for Roof top Unit Notes 1 Remove jumper to install field optional low ambient switch 2 Step down transformer assembly for 460 575 volt units 3 Selective voltage terminals for proper unit volt age 4 Optional low ambient switch 5 Optional motorized intake damper 6 Optional Stop Start and Jog Control 7 For energy management systems connect 24v to G and common 24v to C ...

Страница 11: ...or Filter in Intake Hood 2HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 1200 990 1075 1220 1380 1480 1605 1720 1400 1030 1165 1280 1410 1520 1620 1740 1600 1135 1250 1340 1445 1570 1665 1760 1800 1240 1330 1425 1550 1625 1720 1785 2000 1295 1405 1540 1615 1705 1760 1830 Barometric Hood 2 Pleated Filters 2HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 1200...

Страница 12: ... Kit Mist Eliminator Filter in Intake Hood 3HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 2000 735 860 920 1005 1075 1150 1220 2400 850 945 1030 1090 1110 1215 1265 2800 935 1020 1080 1145 1200 1255 1335 3200 1015 1075 1105 1195 1285 1325 1380 3600 1065 1125 1220 1305 N A N A N A Barometric Hood 2 Pleated Filters 3HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 ...

Страница 13: ... Mist Eliminator Filter in Intake Hood 5HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 4600 795 900 960 1010 1090 1135 1165 5000 835 945 1000 1060 1135 1155 1230 5400 895 985 1040 1130 1155 1220 1265 5800 940 1025 1085 1145 1225 1250 1300 6200 990 1070 1105 1210 1245 1290 N A Barometric Hood 2 Pleated Filters 5HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM...

Страница 14: ...cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any fl uids refrigerant or other system components or associated labor to repair or replace the same which is incurred as a result of a defective part covered by CM s Limited Express Warranty 2 The costs of labor refrigerant materials or service incurred in removal of the defectiv...

Страница 15: ...THE SMART SOLUTION FOR ENERGY EFFI C I E NC Y N ERV Series Rev 0 4 A pri l 2 0 1 4 15 climatemaster com Notes ...

Страница 16: ...fic information on the current design and specifications Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products For the latest version of this document go to climatemaster com ClimateMaster is a proud supporter of the Geothermal Exchange Organiza...

Отзывы: