Mode Number
(Press   

  key

Factory-Setting

Other Choices  

(Press 

 or  

▼ 

key to change)

Select

to change)

Display

Description

Display

Description

Not used

25 thru 32

Minimum off  
time for the
compressor

33

00

No minimum off time for
the compressor

01, 02,
03, 04  
or 05

Minimum number of minutes  
(0 thru 5) the compressor will be
off between calls for the
compressor

Heating setpoint
range stop

34

80

Heating setpoint can be
set no higher than 80°F

40 thru
90

Number can be set anywhere
between 40 and 90 in 1°F
increments

Cooling setpoint
range stop

35

60

Cooling setpoint can be
set no lower than 60°F

c

45 thru
99

Number can be set anywhere
between 45 and 99 in 1°F
increments

Not used

36

Temperature
display
adjustment

37

00

No difference in
displayed temperature
and actual room
temperature

-03 thru
03

01—Display adjusts to 1°F higher
than actual room temperature
02—Display adjusts to 2°F higher
than actual room temperature
03—Display adjusts to 3°F higher
than actual room temperature
-01—Display adjusts to 1°F lower
than actual room temperature
-02—Display adjusts to 2°F lower
than actual room temperature
-03—Display adjusts to 3°F lower
than actual room temperature

Table 2. Thermostat installer setup options (continued).

69-1312—1   G.H.   Rev.  5-99  Printed in Taiwan R.O.C.

R

C

Y

W

T8501D

DXM TERMINALS

O

G

X1

R

C

Y1

O/W2

G

AL1